System Start-up
RT-SVX35H-EN
85
Casing
Size
CFM Std
Air
Filters
Std Roof
Curb
Econ.with
or w/o
Exhaust
Fan
Throwaway
Perm Wire
Mesh
Bag &
Prefilter
Cartridge
&
Prefilter
Std Fiber
High Effic.
2
4000
.03
.03
.01
.3
.24
.01
.03
6000
.06
.06
.02
.5
.44
.02
.06
8000
.09
.09
.03
.71
.68
.05
.12
9000
.11
.11
.04
.83
.81
.07
.15
10000
.13
.13
.05
.95
.95
.10
.19
12000
.15
.15
.06
1.19
1.26
.14
.27
3
6000
.04
.04
.01
.34
.26
.02
.06
9000
.07
.07
.02
.54
.48
.07
.15
12000
.11
.11
.04
.75
.75
.16
.27
14000
.14
.14
.06
.95
.95
.25
.39
15000
.16
.16
.07
1.03
1.06
.30
.43
17000
.21
.21
.09
1.20
1.30
.39
.59
4
8000
.04
.04
.02
.37
.31
.01
.03
10000
.06
.06
.02
.49
.43
.02
.03
12000
.08
.08
.03
.61
.56
.04
.07
16000
.12
.12
.05
.88
.87
.10
.09
17000
.13
.13
.06
.95
.95
.12
.11
20000
.17
.17
.08
1.17
1.22
.19
.17
22000
.21
.21
.10
—
—
.23
.20
5
10000
.04
.04
.01
.37
.30
.03
.05
14000
.07
.07
.03
.56
.50
.07
.08
17000
.10
.10
.04
.72
.68
.12
.11
20000
.12
.12
.05
.88
.88
.19
.17
24000
.16
.16
.07
1.11
1.17
.30
.23
28000
.20
.20
.10
—
—
.39
.30
6
12000
.05
.05
.01
.44
.37
.02
.07
16000
.07
.07
.02
.63
.58
.05
.10
20000
.10
.10
.03
.84
.82
.10
.16
24000
.11
.11
.04
1.06
1.08
.16
.23
28000
.17
.17
.06
—
—
.30
.30
30000
.20
.20
.07
—
—
.34
.34
9
27000
.11
.13
N/A
.68
.65
—
.20
32000
.14
.16
N/A
.84
.84
—
.31
37000
.17
.19
N/A
1.02
1.04
—
.41
42000
.21
.22
N/A
1.19
1.06
—
.52
45000
.24
.24
N/A
—
—
—
.63
46000
N/A
.24
N/A
—
—
—
.64
Notes:
1.
Static pressure drops of accessory components must be added to external static pressure to enter fan selection tables.
2.
Gas heat section maximum temperature rise of 60°F.
3.
Throwaway filter option limited to 300 ft/min face velocity.
4.
Bag filter option limited to 740 ft/min face velocity.
5.
Horizontal roof curbs assume 0.50” static pressure drop or double the standard roof curb pressure drop, whichever is greater.
6.
No additional pressure loss for model WXHE.
Table 21. Component static pressure drops (in. W.G.)
Содержание IntelliPak WEHE Series
Страница 15: ...General Information RT SVX35H EN 15 Figure 1 Unit component layout and ship with locations...
Страница 17: ...Installation RT SVX35H EN 17 Figure 2 Typical control module location...
Страница 29: ...Installation RT SVX35H EN 29 Figure 10 Unit rigging Figure 11 Typical unit base roof curb cross section...
Страница 44: ...Installation 44 RT SVX35H EN Figure 27 Typical field power wiring for W_HE casings 2 through 6...
Страница 56: ...Installation 56 RT SVX35H EN Figure 32 Wiring notes for CV controls...
Страница 60: ...Installation 60 RT SVX35H EN Figure 35 Wiring notes VAV...
Страница 68: ...System Start up 68 RT SVX35H EN Figure 38 Typical fenwall ignition control system...
Страница 69: ...System Start up RT SVX35H EN 69 Figure 39 Typical Fenwall ignition control system...
Страница 70: ...System Start up 70 RT SVX35H EN Figure 40 Typical modulating gas heat schematic connections diagram...
Страница 101: ...Service Maintenance 100 RT SVX35H EN Figure 55 Unit internal fuse replacement data for air cooled units...
Страница 108: ...Service Maintenance RT SVX35H EN 107 Figure 59 Typical wiring schematic for air handler with DX coil casing 2 9...