General Information
8
RT-SVX35H-EN
Modules (UCM). The acronym UCM is used extensively
throughout this document when referring to the control
system network.
These modules through Proportional/Integral control
algorithms perform specific unit functions which provide
the best possible comfort level for the customer.
They are mounted in the control panel and are factory
wired to their respective internal components. They
receive and interpret information from other unit
modules, sensors, remote panels, and customer binary
contacts to satisfy the applicable request for economizing,
mechanical cooling, heating, and ventilation. Refer to the
following discussion for an explanation of each module
function.
Rooftop Module (RTM - 1U48)
The Rooftop Module (RTM) responds to cooling, heating,
and ventilation requests by energizing the proper unit
components based on information received from other
unit modules, sensors, remote panels, and customer
supplied binary inputs. It initiates supply fan, exhaust fan,
exhaust damper, variable frequency drive output, and
economizer operation based on that information.
Table 1.
RTM resistance input vs. setpoint temperatures
RTM cooling or heating setpoint
input used as the source for a Zone
temp setpoint (°F)
RTM cooling setpoint input used
as the source for SUPPLY AIR
temp setpoint cooling (°F)
Resistance (Ohms)
Max. Tolerance 5%
40
40
1084
45
45
992
50
50
899
55
55
796
60
60
695
65
65
597
70
70
500
75
75
403
80
80
305
n/a
85
208
n/a
90
111
Содержание IntelliPak WEHE Series
Страница 15: ...General Information RT SVX35H EN 15 Figure 1 Unit component layout and ship with locations...
Страница 17: ...Installation RT SVX35H EN 17 Figure 2 Typical control module location...
Страница 29: ...Installation RT SVX35H EN 29 Figure 10 Unit rigging Figure 11 Typical unit base roof curb cross section...
Страница 44: ...Installation 44 RT SVX35H EN Figure 27 Typical field power wiring for W_HE casings 2 through 6...
Страница 56: ...Installation 56 RT SVX35H EN Figure 32 Wiring notes for CV controls...
Страница 60: ...Installation 60 RT SVX35H EN Figure 35 Wiring notes VAV...
Страница 68: ...System Start up 68 RT SVX35H EN Figure 38 Typical fenwall ignition control system...
Страница 69: ...System Start up RT SVX35H EN 69 Figure 39 Typical Fenwall ignition control system...
Страница 70: ...System Start up 70 RT SVX35H EN Figure 40 Typical modulating gas heat schematic connections diagram...
Страница 101: ...Service Maintenance 100 RT SVX35H EN Figure 55 Unit internal fuse replacement data for air cooled units...
Страница 108: ...Service Maintenance RT SVX35H EN 107 Figure 59 Typical wiring schematic for air handler with DX coil casing 2 9...