MS-SVN004-EN

Location and Preparation of Units

Indoor Unit

1. Select a convenient location that

allows the air to reach every corner
of the room and where it is easy to
route the refrigerant tubing, wiring
and drain to the outside.

2. The ceiling construction should be

strong enough to support the
weight of the unit.

3. The refrigerant tubing, drain piping

and wiring conduit are connected
through the wall.

4. Refrigerant tubes between the

indoor and the outdoor units and
drain pipes should be as short as
possible (Figure 1).

5. If a refrigerant charge adjustment is

necessary, follow the Installation
Manual for the Outdoor Unit.

Outdoor Unit

See instructions for location and
preparation  of  the   unit  in  the   Installation
Manual for the Outdoor Unit.

Installation Method:

Indoor Unit

After selecting the location to place
the unit, follow these steps:
1. Make a hole in the wall to route

tubing and wiring through a locally
purchased PVC pipe. The hole
should slope downwards slightly,
towards the outside (Figure 2).

Figure 1

2. Before cutting, check that no pipes

or studs are directly behind the
place to be cut. Avoid areas where
electrical wiring or conduits are
located.

3. Hang the unit on a solid and level

roof. Noise, vibration or leakage
could occur on and unstable
foundation (Figure 3,4).
For correct installation of duct
work see (Figure 6).

4. Support the unit solidly.
5. To have access to electrical

terminals, remove the right side
junction box (Figure 2).

6. Note that refrigerant tubing,

interconnecting wiring and drain
hose should go through the wall.
Shape these items so that they will
easily fit through the wall.

Figure 2

Outdoor Unit

See the proper installation method
provided in the Installation Manual
for the Outdoor Unit.

Installation Requirements

Important

- Read the Installation Manual

completely before installing and
operating the system.

- Turn on the mains power at least

five (5) hours before operating
the system.

Installation Requirements

Following is a brief outline of where
and how to install the unit. Please read
over the entire set of instructions for
indoor and outdoor units and make
sure all accessory parts list are with
the unit before beginning.

1. Tools Required for Installation

(not supplied)

- Level
- Hole saw or saw
- Core bits
- Hammer
- Drill
- Torque wrench
- Adjustable wrench
- Standard screwdriver
- Phillips head screwdriver
- Knife or wire stripper
- Tape measure
- 4 Anchor bolts for ceiling

mounting

2. Refrigerant Piping and Insulation

Material

- See the Installation Manual

included with the Outdoor Unit.

- The length of wiring will determine

the wire size. See local codes and
refer to Section Electrical
Installation.

Caution

Check local electrical codes and
regulations before buying any wire.
Also check for any specitic wiring
instructions or limitations.

3. Additional Materials Required

for Installation

- Saddles or clamps to secure

refrigerant tubing.

- Insulated clamps or staples for

connecting wire. See local codes.

- Ceiling mount: Use nuts and bolts

as required to mount the unit on the
ceiling. Use 4 (3/8) fasteners or
closest standard metric with nuts
and lock washers. The length will
vary with application.

- Refrigerant oil and tape

(insulation).

- Putty or similar filler.

L/O- 02091985TRA

21/4/03, 2:44 PM

6

Содержание ILLUSION MCD 048 D1

Страница 1: ... Series 50 60 Hz Cooling Only Cooling Heating 50 Hz Models MCD 512 DB MCD 518 DB MCD 524 DB MCD 530 DB MCD 536 DB MCD 048 DB MCD 060 DB Cooling Only Cooling Heating 60 Hz Models MCD 512 D1 MCD 518 D1 MCD 524 D1 MCD 530 D1 MCD 536 D1 MCD 048 D1 MCD 060 D1 L O 02091985TRA 21 4 03 2 44 PM 1 ...

Страница 2: ...e time The unit should be totally inspected within 7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warranty Warranty is based on the general terms and conditions by country The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company if the ...

Страница 3: ...stem Appearance 4 Location and Preparation of Units 6 Units Installation 7 Connection of Refrigerant Tubing 9 Condensate Drain Piping 10 Electrical Installation 11 Wiring Diagram 12 Dimensional Data 15 Maintenance 18 L O 02091985TRA 21 4 03 2 44 PM 3 ...

Страница 4: ...4 MS SVN004 EN System Appearance MCD 512 536 DB D1 Condensate Drain Pan Electric Heater Option Evaporator Coil Outlet Collar Motor Blower Outdoor Unit Indoor unit L O 02091985TRA 21 4 03 2 44 PM 4 ...

Страница 5: ...MS SVN004 EN MCD 048 060 DB D1 Blower Return Air Plenum Standard Outdoor Unit Indoor Unit Electric Heater Option Condensate Drain Pan Motor Evaporator Coil Outlet Collar L O 02091985TRA 21 4 03 2 44 PM 5 ...

Страница 6: ...nd drain hose should go through the wall Shape these items so that they will easily fit through the wall Figure 2 Outdoor Unit See the proper installation method provided in the Installation Manual for the Outdoor Unit Installation Requirements Important Read the Installation Manual completely before installing and operating the system Turn on the mains power at least five 5 hours before operating...

Страница 7: ...GTH PLEASE SEE PAGE 15 16 AND 17 I J H A B C D E F G DISTANCE M M I CELING WALL DRAIN PIPE DRAIN PIPE RETURN PLENUM WITH FIL TER DET AIL X FLEXIBLE CONNECTER CHAMBER CHAMBER FILTER FILTER RETURN AIR GRILLE SLANT 1 50 SUPPLY DUCT SUPPLY DUCT FIGURE 3 SIDE VIEW FIGURE 4 TOP VIEW Unit Installation L O 02091985TRA 21 4 03 2 44 PM 7 ...

Страница 8: ...8 MS SVN004 EN Units Installation 6 L O 02091985TRA 21 4 03 2 44 PM 8 ...

Страница 9: ...ubes before they are used 2 Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together This is effective for reducing gas leaks Figure 11 Figure 11 Apply refrigerant lubricant here 3 For proper connection align the union tube and flare tube straight with each other then screw in the flare nut lightly at first to obtain a smooth match Figu...

Страница 10: ...laced in the room insulate the hose with foampolyethylenetoavoiddamage to the ceiling or furniture 5 After completing installation of refrigerant lines wiring and drain connections bind the tubing wiring and drain piping check if local codes permit binding into a bundle by using tape at 100 or 200 mm 4 to 8 intervals Make sure the drain tube is at the bottom of the bundle Figure 16 Figure 16 P V C...

Страница 11: ...r will accept no responsibility for problems caused by unauthorized changes in the internal wiring Connect the wiring firmly Indoor Unit Remove the right side junction box see previous instructions to access the terminal base System Wiring Routing Pass the system wiring through the PVC pipe referred to in the Section of Installation Method both power and control lines to interconnect indoor and ou...

Страница 12: ...K HI MED LOW COM BR BL RD WH BLOWER MOTOR 1 2 3 4 L2 L1 C1 C2 THERMOSTAT 3 SPEED SWITCH POWER SUPPLY 200 240V 1PH 60Hz 220 240V 1PH 50Hz 200 240 VAC CONTROL WIRING TO CONDENSING UNIT NOTE 1 Power wiring and grounding of equipment must comply with local codes 2 Ensure that power supply agrees with equipment nameplate 3 Use only copper conductors LEGEND FIELD WIRING FACTORY WIRING LOW MEDHI L O 0209...

Страница 13: ...HERMAL OVERLOAD PROTECTOR AUTO RESET MAX 20AMP NON INDUCTIVE FULL LOAD CURRENT HEATER H C H C 1 0 2 4 6 8 HEAT COOL TO HEATING TO COOLING THERMOSTAT COOLING HEATING SWITCH 3 SPEED SWITCH h OFF LOWMED HI POWER SUPPLY 200 240V 1PH 60Hz 220 240V 1PH 50Hz 200 240 VAC CONTROL WIRING TO CONDENSING UNIT LEGEND FIELD WIRING FACTORY WIRING 1 POWER WIRING AND GROUDING OF EQUIPMENT MUST COMPLY WITH LOCAL COD...

Страница 14: ...SET MAX 20AMP NON INDUCTIVE FULL LOAD CURRENT HEATER THERMAL OVERLOAD PROTECTOR AUTO RESET MAX 20AMP NON INDUCTIVE FULL LOAD CURRENT FIELD WIRING FACTORY WIRING COOLING HEATING LEGEND MOTOR BLOWER EXTRA HI RD RD WH LOW COM BLK MED HI RD BL BR BLK TO HEATING TO COOLING COOL SWITCH h HEAT OFF LOW MED HI L N C1 5 2 4 6 8 0 1 6 4 3 2 1 C2 POWER SUPPLY 200 240V 1pH 60Hz 220 240V 1pH 50Hz 200 240 VAC CO...

Страница 15: ...4 1098 3 8 9 52 5 8 15 87 30 762 34 3 4 882 37 1 4 946 3 8 9 52 5 8 15 87 42 1067 34 7 8 1087 49 1 4 1251 3 8 9 52 3 4 19 05 VIEW A Ø16 32 111 127 63 5 HANGER HOLES X6 SEE VIEW A A B C C SUCTION CONNECTION LIQUID CONNECTION 284 252 166 254 174 40 DRAIN CONN Ø22 5 MPT 210 234 Note From the experience of our Trane technician based on the design condition at velocity at supply air grille of 300 ft mi...

Страница 16: ... 3 4 882 37 1 4 946 30 762 33 15 16 862 1 4 6 35 1 2 12 7 2 1 MCD 524 30 762 34 3 4 882 37 1 4 946 30 762 33 15 16 862 3 8 9 52 5 8 15 87 2 1 MCD 530 36 914 40 1 4 1034 43 1 4 1098 36 914 39 15 16 1014 3 8 9 52 5 8 15 87 2 1 MCD 536 42 1067 42 7 8 1087 49 1 4 1251 42 1067 45 15 16 1167 3 8 9 52 3 4 19 05 2 1 Number Of Model Note From the experience of our Trane technician based on the design condi...

Страница 17: ... 42 08 1069 46 73 1187 49 21 1250 41 73 1060 45 90 1166 1 1 8 28 57 3 8 9 52 2 1 External Dimensions Return Air Plenum is Standard All External Dimensions are in inch mm Refrig Line Conn Size Number Of Model Note From the experience of our Trane technician based on the design condition at velocity at supply air grille of 300 ft min for bedroom and 400 ft min for office based on free face area the ...

Страница 18: ...rom return air plenum set 1 2 How to clean the air filter Wash away dust from the air filter with clean water or vacuum it with an electric vacuum cleaner Note Once the air filter is washed dry it completely befor e returning it to its original position After cleaning be sure to return it to its original position Cautions Do not wash the air filter in water that is over 40ºC or it may shrink Do no...

Страница 19: ...19 MS SVN004 EN Notes L O 02091985TRA 21 4 03 2 44 PM 19 ...

Страница 20: ...policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey Bangkok 10110 Amair Limited 35 Mu 8 Poochaosamingprai Road Samrong Tai Samutprakarn 10130 http www trane com An American Standard Company L O 02091985TRA 21 4 03 2 45 PM 20 ...

Отзывы: