background image

- 7 -

- 6 -

IV. ANNUAL MAINTENANCE

V. ANNUAL SUMMER SHUTDOWN

For best performance, we recommend that you replace the
Humidifier Pad in your Humidifier annually.

To obtain a replacement:

• Call your heating and air conditioning dealer.

• Look in the Yellow Pages under Heating & Air Conditioning Contractors.

• If none of the above are successful and you still need information,

please feel free to write us or send an email to our website.

For Models *HUMD200ABM00B, *HUMD300ABA00B
close the bypass damper .

AUTOMATIC HUMIDIFIER CONTROL:

Humidifiers controlled by the Automatic Humidifier Control require no
control adjustment. Shut off the water supply to the humidifier by closing
the saddle valve.

MANUAL HUMIDIFIER CONTROL:

For humidifiers controlled by a Manual Humidifier Control, simply turn the
Control to the “Off” position. Shut off the water supply to the humidifier
by closing the saddle valve.

III . EFFECT OF WATER CHARACTERISTICS

To check the humidifier operation, set the Humidifier Control above the click
point, make sure that the water saddle valve is open and that there is
electricity to the humidifier. Generally, the furnace and blower motor must be
operating for the Humidifier Control to function. After the humidifier has
operated for several minutes and water is entering the humidifier and coming
out at the drain, reduce the Humidifier Control setting below the click point
and the humidifier should automatically shut off. Now set the Humidifier
Control dial at the recommended inside relative humidity, depending on the
outside temperature. Follow the suggested settings prior to a drop in the
outside temperature.

Additional Information

Be sure to keep fireplace dampers closed when not in use. They provide
an excellent escape route for heat, as well as humidity. Humidity is lost at
an even faster rate than heat because water vapor tends to seek its own
level and your humidifier would not be able to replace it even when
running at full capacity.

On occasion, indoor moisture producing activities such as clothes drying,
cooking, showers, etc., may raise the relative humidity level higher than it
should be, even though the Humidifier is not operating. Telltale
indications, again, are condensation or frost on cold surfaces such as
windows, doors, walls, etc. If such condensation persists for several
hours, your home should be ventilated to dissipate the potentially
damaging excess moisture.

Your humidifier will operate effectively using either hot, cold, hard or
mechanically softened water. Whether to use available tap water, even
though it may be quite hard, or chemically softened water, is a common
concern to homeowners when installing a humidifier. Because of the
humidifier’s design, most of these solids are effectively controlled by
flushing them down the drain.

Water used in homes contains varying amounts of minerals. The residue
remaining as a result of hard water evaporation is primarily calcium and
magnesium components and is usually quite hard, scaly, and dense.

Residue from softened water tends to be soft and fluffy and has a greater
volume than hard water residue. The service life of a Humidifier Pad may
be extended by using hard water, but in either case, the Humidifier Pad
should be changed once a year. This is why proper maintenance is
important and necessary. Service hot water 140°F maximum, is
recommended with flow through, drain type units for increasing capacity.

Содержание HUMD200ABM00B

Страница 1: ...READ AND SAVE THESE INSTRUCTIONS HUMIDIFIERS USE AND CARE MANUAL Includes Safety Operating Instructions and Warranty Information For Models HUMD200ABM00B HUMD300ABA00B HUMD500APA00B May be A or T ...

Страница 2: ...e winter your comfort relies on two things the perfect temperature and the perfect amount of moisture Your new humidifier will provide your home with the recommended indoor relative humidity to ensure your comfort all winter long INTRODUCTION TABLE OF CONTENTS WARNING ELECTRICAL SHOCK HAZARD Disconnect Electrical Power and Shut Off Water Supply Before Servicing Failure to follow this warning may c...

Страница 3: ... FIGURE A Your new humidifier has been installed to operate in conjunction with your furnace When the Humidifier Control calls for humidity and the furnace blower is operating water flows to the distribution tray located at the top of the humidifier The water is evenly distributed across the width of the tray and over the Humidifier Pad Dry hot air is moved through this moisture laden Humidifier P...

Страница 4: ...ome with the possibility of damage resulting Outside Temperature Recommended RH 40 F 45 30 F 40 20 F 35 10 F 30 0 F 25 10 F 20 20 F 15 The Humidifier Control is a precision instrument that can be used to determine the RH accurately in your home during the winter Turn the dial to the lower setting then reverse the dial direction slowly until a click is heard At this point read the RH on the dial Th...

Страница 5: ... outside temperature Additional Information Be sure to keep fireplace dampers closed when not in use They provide an excellent escape route for heat as well as humidity Humidity is lost at an even faster rate than heat because water vapor tends to seek its own level and your humidifier would not be able to replace it even when running at full capacity On occasion indoor moisture producing activiti...

Страница 6: ...l to the OFF position 2 Turn off water supply Turn the integral bypass damper 3 to the SUMMER position 3 Press the tabs in the latches on the top and bottom of front cover 1 and pull cover off base with both hands Set aside 4 Carefully pull the plastic feed tube 2 out of the distribution tray 5 at the top of the evaporative assembly 4 Pull this assembly out by grasping at top and tipping out 5 Uns...

Страница 7: ...ribution tray 6 Slide the Humidifier Pad 6 out from the scale control insert 7 Clean the scale control insert of mineral deposits Replace Humidifier Pad annually with a BAYPAD02A1310A Humidifier Pad Slide the Humidifier Pad back into the scale control insert with the colored spot up and snap the distribution tray 4 back into place 7 Inspect the plastic feed tube by gently flexing it and looking fo...

Страница 8: ...60 days after the Commencement Date to receive the registered limited warranty terms To register online go to http www trane com Residential Trane Owners Warranty Information or http www americanstandardair com sevicesupport pages warranty aspx and click Begin Online Registration If a Purchaser does not register within this stated time period the base limited warranty terms shall apply ELIGIBILITY...

Страница 9: ...RD ZDAMPSM ZDAMPBM ZDAMPRR Base Limited Warranty Period five 5 years Registered Limited Warranty Period ten 10 years HUMIDIFIERS HUMD200 HUMD300 HUMD500 Base Limited Warranty Period five 5 years Registered Limited Warranty Period ten 10 years ENERGY RECOVERY VENTILATOR ERV ERVR100 ERVR200 ERVR300 Base Limited Warranty Period five 5 years Registered Limited Warranty Period ten 10 years AIR CLEANERS...

Отзывы: