
General Information
OAU-SVX005C-EN
13
•
Wash clothes separately from other clothing: rinse
washer thoroughly.
•
Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring
additional respiratory protection. Use the appropriate
NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact
Flush eyes with water to remove dust. If symptoms persist,
seek medical attention.
Skin Contact
Wash affected areas gently with soap and warm water
after handling.
Storage
Take precautions to prevent condensate from forming
inside the unit’s electrical compartments and motors if:
•
the unit is stored before it is installed; or,
•
the unit is set on the roof curb, and temporary heat is
provided in the building. Isolate all side panel service
entrances and base pan openings (e.g., conduit holes,
S/A and R/A openings, and flue openings) from the
ambient air until the unit is ready for startup.
Note:
Do not use the unit’s heater for temporary heat
without first completing the startup procedure
detailed in
The manufacturer will not assume any responsibility for
equipment damage resulting from condensate
accumulation on the unit’s electrical and/or mechanical
components.
Unit Clearances
Unit Clearances, Curb Dimensions, and Dimensional Data
chapter contains figures that illustrate the minimum
operating and service clearances for either a single or
multiple unit installation. These clearances are the
minimum distances necessary to assure adequate
serviceability, cataloged unit capacity, and peak operating
efficiency.
Providing less than the recommended clearances may
result in condenser coil starvation, “short-circuiting” of
exhaust or recirculation of hot condenser air.