28
Custom
Report
Chiller
Report
Cycle
Report
Pump/Purge
Report
Cycle Report
The
CYCLE REPORT
is used to display the current machine
operating temperatures and pressures. The following
menu identifies the cycle report.
1.
Cycle Report
Press (Next)(Previous) to Continue
2.
Solution Temperature Leaving HTG:
xxx.xf/c
Interstage Vapor Temperature
xxx.xf/c
3.
Solution Temperature Entering Level Control:
xxxf/c
Mixed Solution Temperature Entering LTHX:
xxx.xf/c
4.
Solution Temperature Leaving LTG:
xxx.xf/c
Interstage Vapor Pressure:
xxx.xpsig/kpa
5.
HTG Leaving Concentration:
xxx.x%
LTG Leaving Concentration:
xxx.x%
6.
Burner Exhaust Gas Temperature:
xxx.xf/c
7. Sensing Detection and Recovery (SDR)
Temperature and Trip Temperature. The SDR temperature
monitor determines if lithium bromide flow is restricted at
the low temperature heat exchanger. When a solution
restriction is detected the SDR initiates a recovery mode to
protect the solution from crystallization.
SDR Temperature:
xxx.xf/c
Trip Temperature:
xxx.xf/c
8.
Solution Temperature Leaving LTG:
xxx.xf/c
Saturated Condenser Refrigerant Temperature:
xxx.xf/c
9.
Absorber Entering Concentration:
xxx.x%
Lithium Bromide Crystallization Margin:
xxx.xf/c
The Lithium Bromide Crystallization margin is the
difference between the mixed lithium bromide solution
temperature leaving the low temperature heat exchanger
and its theoretical crystallization temperature.
10.
Solution Temperature Entering Absorber:
xxx.x f/c
Absorber Spray:
xxx.xf/c
11.
Solution Temperature Leaving Absorber:
xxx.xx%
Lithium Bromide
Solution Temperature Entering LTG.
xxx.xf/c
12.
Saturated Evaporator Refrigerant Temperature: xxx.xf/c
Evaporator Leaving Water Temperature:
xxx.xf/c
13.
Evaporator Entering Water Temperature:
xxx.xf/c
Evaporator Leaving Water Temperature:
xxx.xf/c
14.
Absorber Leaving Water Temperature:
xxx.xf/c
Condenser Leaving Water Temperature:
xxx.xf/c
15. Solution Pump speed Reported Command: If the
solution pump AFD Speed is set to Auto/[manual] Control
Solution Pump AFD Auto or [manual] Speed
Command: xxx.x
Press (Next)(Previous) To Continue
Or if in limit mode
Solution Pump AFD Auto or [manual] Speed
Command: xxx.x
[Limit Mode]
16. Heating:
Auxiliary Heat Valve Step Position:
xxxxx steps
Auxiliary Heat Valve Position:
xxx%
17.
Energy Input Auto or [manual] Command:
xxx.x
Press (Next) (Previous) To Continue
If limit
Energy Auto or manual] Command: xxx.x
[limit mode]