UNT-SVN006-EN
7
Installation Checklist
The following checklist is provided as
an abbreviated guide to the detailed
installation procedures given in this
manual. Complete this checklist once,
the unit is installed to verify that all
recommended procedures have been
accomplished before the system is
started.
Caution: Verify that the unit electrical
power is disconnected.
• Inspect all fields wiring connections.
All connection should be clean and
tight.
• Inspect unit ground connection.
Ground must comply with all
applicable codes.
• Unit casing is level. Remove any
tools or debris found in or near
the unit.
• Inspect duct outlets. Ductwork
connections are completed and
outlets must be open and
unrestricted.
• Coil connections are completed
and tight.
• Condensate drain pan connections
must be tight and drain
unrestricted.
• Inspect fan assembly to insure all
moving parts move freely.
• Inspect unit for proper filters,
securely installed. All cabinet
panels must be secured.
Caution: Disconnect electrical power
sources and secure in disconnected
position before servicing the unit.
Failure to do so may result in personal
injury or death from electrical shock.
Coil Venting
When water is first introduced into a
coil, air is sometime trapped in the
coil tube. This trapped air has a
tendency to collect at the highest
point in the coil. When there appears
to be air trapped in the coil, resulting
in “bubbling” or “clanking” noises
within the unit. Therefore, a manual air
vent is installed at the highest point of
the header as shown in Figure 6.
To release air from the manual air vent
by rotating the knob. A pair of pliers
can be used if the knob is too tight to
turn by hand. Turn knob counter
clockwise 1-2 turns and allow air to
flow out of the air vent until a steady
stream of water appears. Then
retighten knob.
Figure 6
Содержание HFCC 04
Страница 8: ...8 UNT SVN006 EN Wiring Diagram CHILLED WATER FAN COIL HFCC 04 12 HFCD 14 20...
Страница 9: ...UNT SVN006 EN 9 Dimensional Data CHILLED WATER FAN COIL HFCC 04 12...
Страница 10: ...10 UNT SVN006 EN CHILLED WATER FAN COIL HFCC 04 12 Dimensional Data...
Страница 11: ...UNT SVN006 EN 11 CHILLED WATER FAN COIL HFCD 14 20 Dimensional Data...