UNT-SVN006-EN

7

Installation Checklist

The following checklist is provided as
an abbreviated guide to the detailed
installation procedures given in this
manual. Complete this checklist once,
the unit is installed to verify that all
recommended procedures have been
accomplished before the system is
started.

Caution: Verify that the unit electrical
power is disconnected.

• Inspect all fields wiring connections.

All connection should be clean and
tight.

• Inspect unit ground connection.

Ground must comply with all
applicable codes.

• Unit casing is level. Remove any

tools or debris found in or near
the unit.

• Inspect duct outlets. Ductwork

connections are completed and
outlets must be open and
unrestricted.

• Coil connections are completed

and tight.

• Condensate drain pan connections

must be tight and drain
unrestricted.

• Inspect fan assembly to insure all

moving parts move freely.

• Inspect unit for proper filters,

securely installed. All cabinet
panels must be secured.

Caution: Disconnect electrical power
sources and secure in disconnected
position before servicing the unit.
Failure to do so may result in personal
injury or death from electrical shock.

Coil Venting

When water is first introduced into a
coil, air is sometime trapped in the
coil tube. This trapped air has a
tendency to collect at the highest
point in the coil. When there appears
to be air trapped in the coil, resulting
in “bubbling” or “clanking” noises
within the unit. Therefore, a manual air
vent is installed at the highest point of
the header as shown in Figure 6.

To release air from the manual air vent
by rotating the knob. A pair of pliers
can be used if the knob is too tight to
turn by hand. Turn knob counter
clockwise 1-2 turns and allow air to
flow out of the air vent until a steady
stream of water appears. Then
retighten knob.

Figure 6

Содержание HFCC 04

Страница 1: ...UNT SVN006 EN May 2000 Installation Manual HFCC 400 1 200 CFM HFCD 1 400 2 000 CFM Chilled Water Fan Coil...

Страница 2: ...thin 7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warning Warnings are provided at approp...

Страница 3: ...UNT SVN006 EN 3 Contents General Information 2 Unit Installation 4 Tools Required for Installation 5 Installation Checklist 8 Wiring Diagram 9 Dimensional Data 10 Notes 13...

Страница 4: ...copper tube of Fan Coil Unit and water pipe as shown in Figure 2 Note Before brazing a copper tube to a solder coupling or a copper tube to an expanded tube do not forget to keep them tight Condensat...

Страница 5: ...collar and fasten the duct and collar together with screws Note All ductwork should be properly insulated to prevent condensation installation site Electrical Connections Check the unit nameplate for...

Страница 6: ...urn Air Supporting Structure Ceiling Width 3 8 Inch Expansion Width 3 8 Inch Suspension Rod Width 3 8 Inch Lock Washer Width 3 8 Inch Nut Unit B A Supply Air Chamber Chamber B Screw Top Panel B Rivet...

Страница 7: ...estricted Inspect fan assembly to insure all moving parts move freely Inspect unit for proper filters securely installed All cabinet panels must be secured Caution Disconnect electrical power sources...

Страница 8: ...8 UNT SVN006 EN Wiring Diagram CHILLED WATER FAN COIL HFCC 04 12 HFCD 14 20...

Страница 9: ...UNT SVN006 EN 9 Dimensional Data CHILLED WATER FAN COIL HFCC 04 12...

Страница 10: ...10 UNT SVN006 EN CHILLED WATER FAN COIL HFCC 04 12 Dimensional Data...

Страница 11: ...UNT SVN006 EN 11 CHILLED WATER FAN COIL HFCD 14 20 Dimensional Data...

Страница 12: ...cations without notice Literature Order Number UNT SVN006 EN 0500 Supersedes CFH IOM 2T Stocking Location Bangkok Thailand Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey...

Отзывы: