MUA-SVX006B-EN
23
Vent Systems Termination Clearance Requirements
Structure/Object
Minimum Clearance for Termination Locations
USA
CANADA
Door, window, or gravity vent inlet;
combustion air inlet for other
appliances
9 inch for 10,000 to 50,000 BTU/Hr
input; 12 inch for input exceeding
50,000 BTU/Hr.
9 inch (230mm) for 10,000 to
50,000 BTU/Hr input; 12 inch
(305mm) for input exceeding
50,000 BTU/Hr.
Forced air inlet within 10 feet
3 feet above
6 feet (1.8m)
Adjoining Building or parapet
6 feet
6 feet (1.8m)
Adjacent public walkways
7 feet above grade
7 feet (2.1m) above grade
Electric, gas meters & regulators
4 feet horizontal
3 feet (0.9m) horizontally from
meter/regulator assembly. 6 feet
(1.8m), any direction, from a gas
service regulator vent outlet
Above grade level*
1 foot*
1 foot (0.3m)*
N
No
otte
e:: *If the vent terminal is to be installed near ground level, the vent terminal must be
positioned at least six inches (152mm) above the maximum anticipated snow depth.
Duct Connections
All ductwork must be properly supported so that no strain is put on the unit. Do not alter or bend
the discharge duct flanges supplied on your make-up air unit.
•
Duct connections must have a removable access panel in the duct which is connected to a
duct furnace. The duct openings shall be accessible when the unit is installed in service, and
shall be of such size that smoke or reflected light may be observed inside the casing to
indicate the presence of leaks in the heating element. The covers for the panels shall be
attached in such a manner as to prevent leaks. Ducts (or optional outside air hoods) exposed
to the outdoors must be insulated and sealed to prevent water from entering either the unit or
building through the duct.
•
If a single, double or triple duct furnace only unit is connected to a return air duct, or any
other inlet air restriction, the appliance shall be installed on the positive pressure side of the
air circulating blower.
•
When connecting return air duct to Standard or High CFM cabinets, attach duct to return air
opening flange when no dampers are used. Otherwise, if dampers are used, attach return air
duct around collar at bottom of damper assembly. Also refer to the Dimensional Data section
of this manual, Submittal Data Sheets and Indoor Duct Furnace Manual specified for your
unit.
Gas Piping††
All gas piping must be installed in accordance with local codes. It is required that a ground union
be installed adjacent to the gas valve of each duct furnace, and a ground union be installed just
external of each duct furnace for unit servicing. On vertical runs, a drip leg should be provided
upstream of any control manifold. A gas shutoff valve should be, or may be required by local
codes, installed upstream of the external ground union for each duct furnace. A 1/8" N.P.T.
plugged tapping, accessible for test gauge connection, must be installed immediately upstream
of the unit gas supply connection.
Содержание GXAA
Страница 16: ...16 MUA SVX006B EN Figure 7 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 17: ...MUA SVX006B EN 17 Figure 8 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 18: ...18 MUA SVX006B EN Figure 9 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 19: ...MUA SVX006B EN 19 Figure 10 Flexible Connector Kit Install I In ns st ta al ll la at ti io on n...
Страница 48: ...48 MUA SVX006B EN Dimensional Data Arrangements Indoor Arrangement A Capacity 50 80...
Страница 55: ...MUA SVX006B EN 55 Motor Electric Data Table 4 Full Load Current in Amperes...
Страница 58: ...58 MUA SVX006B EN Coil Cabinet Dimensional Data Figure 25 Coil Cabinet Dimensional Data...
Страница 62: ...62 MUA SVX006B EN Gas Equipment Start Up...
Страница 63: ...MUA SVX006B EN 63 N No ot te es s...