![Trane GHND Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/trane/ghnd-series/ghnd-series_installation-operation-and-maintenance_1149989009.webp)
Unit Size
30
45
60
75
100
125
150
175
200
225
250
300
350
400
PERFORMANCE DATA ‡
Input BTU/Hr
30,000
45,000
60,000
75,000
100,000 125,000 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
Output BTU/Hr
24,000
36,000
48,000
60,000
80,000
100,000 120,000 140,000 160,000 180,000 200,000 240,000 280,000 320,000
Thermal Efficiency (%)
80
80
80
80
80
80
80
80
80
80
80
80
80
80
Free Air Delivery CFM
750
800
1,050
1,100
1,480
1,650
2,200
2,530
2,640
2,700
3,100
4,400
5,000
5,300
Air Temperature Rise
Deg. F
30
42
42
50
50
56
50
51
56
61
60
50
52
56
Outlet Velocity FPM
680
720
610
640
775
910
1,045
1,070
1,010
950
980
1,100
1,150
1,050
Full Load Amps at 115V
4.5
4.5
4.5
4.5
5.8
6
7.2
8.2
8.2
8.2
8.2
11.2
13.2
13.2
MOTOR DATA : Motor
HP
1/30
1/30
1/30
1/30
1/20
1/10
1/4
1/3
1/3
1/3
1/3
1/4
1/3
1/3
Motor Type
SP
SP
SP
SP
SP
SP
PSC
PSC
PSC
PSC
PSC
PSC
PSC
PSC
R.P.M.
1,050
1,050
1,050
1,050
1,050
1,050
1,140
1,140
1,140
1,140
1,140
1,140
1,140
1,140
Amps @ 115V
1.3
1.3
1.3
1.3
2.6
2.8
4
4.5
4.5
4.5
4.5
8
9
9
DIMENSIONAL DATA in.
“A” Height to Top of
Unit
25-3/4
25-3/4
25-3/4
25-3/4
31-1/4
31-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
36-1/4
“B” Width of Unit
14
14
17-1/2
17-1/2
17-7/8
20-5/8
20-5/8
23-3/8
26-1/8
28-7/8
31-5/8
37-1/8
42-5/8
48-1/8
“C” Height to Top of
Hanger
27-1/2
27-1/2
27-1/2
27-1/2
34-1/8
34-1/8
39-1/8
39-1/8
39-1/8
39-1/8
39-1/8
39-1/8
39-1/8
39-1/8
“D” Depth to Rear of
Housing
30-3/8
30-3/8
30-3/8
30-3/8
37-1/2
37-1/2
37-1/2
37-1/2
37-1/2
37-1/2
37-1/2
37-1/2
37-1/2
37-1/2
“E” Hanging Distance
Width
11
11
16-1/2
16-1/2
14-1/2
17-1/4
17-1/4
20
22-3/4
25-1/2
28-1/4
33-3/4
39-1/4
44-3/4
“F” Discharge Opening
Width
10
10
15-1/2
15-1/2
15-3/8
18-1/8
18-1/8
20-7/8
23-5/8
26-3/8
29-1/8
34-5/8
40-1/8
45-5/8
“G” Depth to Unit Side
Jacket
19-3/8
19-3/8
19-3/8
19-3/8
26-3/4
26-3/4
26-3/4
26-3/4
26-3/4
26-3/4
26-3/4
26-3/4
26-3/4
26-3/4
“H” Discharge Opening
Height
16-1/4
16-1/4
16-1/4
16-1/4
18
18
18
18
18
18
18
18
18
18
“J” to Centerline of
Flue
4
4
5-3/4
5-3/4
5-7/8
7-1/4
7-1/4
8-5/8
10
11-1/4
12-3/4
15-1/2
18-1/4
21
“K” Depth to Centerline
of Flue
23-5/8
23-5/8
23-5/8
23-5/8
30-5/8
30-5/8
30-5/8
30-5/8
30-5/8
30-5/8
30-5/8
30-5/8
30-5/8
30-5/8
“L” Hanger Location
13-3/4
13-3/4
13-1/2
13-1/2
16-1/4
16-3/4
16-3/8
16-3/8
16-3/8
16-3/4
16-3/4
16-3/4
16-3/4
16-3/4
Flue Size Dia.-in.*
4
4
4
4
4
4
4
4
5
5
5
6
6
6
Fan Diameter-in.
12
12
14
14
14
16
16
18
18
18
18
(2) 16
(2) 18
(2) 18
Gas Inlet-Natural Gas-
in.
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
Gas Inlet-LP Gas-in.
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2 or 3/4
Approx. Shipping Wt
lb.
79
94
109
119
174
197
219
238
249
275
305
350
414
461
GHND-SVX01A-EN • High Efficiency Propeller Fan Gas Unit Heater
9
General Information
Note 1.
‡Ratings shown are for unit installations at elevations between 0 and 2,000 ft. For unit installations in U.S.A. above
2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft. (305m) above sea level; refer to local codes,