GHND-SVX01A-EN • High Efficiency Propeller Fan Gas Unit Heater
17
Gas Supply Piping
Notes:
Determine the required Cu. Ft. / Hr. by dividing the rated heater input by 1000. For SI / Metric
measurements: Convert unit Btu. / Hr. to kilowatts. Multiply the units input (kW) by 0.0965 to determine
Cubic Meters / Hour.
Notes:
FOR NATURAL GAS: Select the pipe size directly from the table.
Notes:
FOR PROPANE GAS: Multiply the Cu. Ft. / Hr. (Cubic Meters per Hour) value by 0.633; then use the table.
Table 3.
Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less,
and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)(Based on a 0.60 Specific Gravity Gas)
Nominal
Iron
Internal
Length of Pipe, Feet
Pipe
Size
Dia.
10
20
30
40
50
60
70
80
90
100
125
150
175
200
1/2
0.622
175
120
97
82
73
66
61
57
53
50
44
40
37
35
3/4
0.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
1 1/4
1.38
1400
950
770
660
580
530
490
460
430
400
360
325
300
280
1 1/2
1.61
2100
1460
1180
990
900
810
750
690
650
620
550
500
460
430
2
2.067
3950
2750
2200
1900
1680
1520
1400
1300
1220
1150
1020
950
850
800
2 1/2
2.469
6300
4350
3520
3000
2650
2400
2250
2050
1950
1850
1650
1500
1370
1280
3
3.068
11000
7700
6250
5300
4750
4300
3900
3700
3450
3250
2950
2650
2450
2280
4
4.026
23000
15800
12800
10900
9700
8800
8100
7500
7200
6700
6000
5500
5000
4600
Gas Pipe Size