6

Unit Installation

(e) Auxiliary Drain Pan

A field fabricated auxiliary drain pan
should be installed under the unit
especially if the unit is installed above
ceilings or in other locations where
condensate overflow may cause
damage.  This drain pan will eliminate
any excess condensation that may be
due to extreme humidity or an
obstructed drain in the primary drain
pan.  Drain lines from this pan must be
installed,  but should not be connected
to the primary drain line from the unit.
Isolate the auxiliary drain pan from both
the air handler and the structure.

(f) Filters

Air handlers are shipped with 1 filters
installed in the unit.  For filter
dimensions, refer to page 5.  (General
data).

To replace filters remove side access
panel (either end and slide old filters
out and replace with new ones.
Figure 3

(g) Duct Connections

The supply and return ducts should be
connected to the unit with flame
retardant duct connectors to reduce
vibration transmission.  The return duct
should be sized to the same
dimensions as the return inlet of the
unit.  Refer to Figure in page 3 for the
dimension.

(h) Electrical Connections

1. All electrical lines, sizing, protection

and ground ing must be in
accordance with the National Electric
Code and local codes.

2. If conduit is used, isolate whenever

vibration transmission may cause a
noice problem within the building
structure.

3. Ensure all connections are tight and

no wires exposed.

4. All accessories must be installed

and wired according to the
instructions packaged with that
accessory.

Installation Checklist

Complete this checklist once the unit is
installed to verify that all recommended
procedures have been accomplished
before the system is started.
Operational checks cannot be
performed until the system in
terconnection is complete.

WARNING: 

WHEN

INSTALLING OR SERVICING
THIS EQUIPMENT, ALWAYS
EXERCISE BASIC SAFETY
PRECAUTIONS TO AVOID THE
POSSIBILITY OF ELECTRIC
SHOCK THAT COULD RESULT
SEVERE PERSONAL INJURY
OR DEATH.

!

1.Verify that the unit electrical power is

disconnected.

2.Inspect all field wiring connections.

All connections should be clean and
tight.

3.Inspect unit suspension

arrangement(s).  Ground must
comply with all applicable codes.

4.Inspect unit suspension

arrangement (if used).  Unit position
must be secure.  Remove any tools
or debris found in or near the unit.

5.Inspect duct outlets.  Outlets must be

open and unrestricted.

6.Inspect unit drain lines.  Pipe

connections must be tight and drain
line unrestricted.

7.Inpect fan assembly to insure all

moving parts move freely.

8.If unit is horizontally mounted, make

sure secondary drain pan has been
installed.

9.Inspect unit for proper filters, securely

installed.  All cabinet panels must be
secured.

10.Instruct owner/operator on proper

system operating and maintenance
procedure.

Содержание FWDP 008

Страница 1: ...TRANE R Installation Operation Maintenance Commercial Chilled Water Blower Coil Unit FWDP Models FWDP 008 FWDP 024 FWDP 014 FWDP 028 FWDP 018 FWDP 032 FWDP SVX01A E4 June 08 ...

Страница 2: ...TRANE ...

Страница 3: ...egistered mail Notify the local Trane Sales Office Concealed damage must be reported within 15 days of delivery Check the unit nameplate to confirm that the proper unit was shipped Available power supply must be compatible with electrical characteristics specified on component nameplates Installation General Information This manual covers the installation operation and maintenance of the Trane FWD...

Страница 4: ...TRANE ii Content General Information Model Nomenclature General Data Dimensional Data Unit Installation Wiring Diagrams Unit Installation i 1 2 3 4 6 7 8 ...

Страница 5: ...TRANE 1 FWDP MODEL NOMENCLATURE ...

Страница 6: ...ominal Net weight unit m m m2 m m m m pc pc KW Amps pc kg FWDP008 9 5 0 26 1 1 speed 1 0 165 1 3 1 16 x25 54 FWDP014 9 5 0 26 1 1 0 55 5 6 5 3 4 5 1 16 x25 58 FWDP018 9 5 0 33 1 1 0 55 5 6 5 3 4 5 1 1 15 x20 15 x15 68 FWDP024 9 5 0 46 2 1 0 75 5 8 5 5 4 4 1 1 16 x20 16 x25 82 FWDP028 9 5 0 62 2 1 1 1 9 8 5 7 5 3 16 x20 114 FWDP032 9 5 0 67 2 1 1 1 9 8 5 7 5 2 1 16 x20 16 x25 120 FC Centrifugal Dir...

Страница 7: ...s Note Dimensions are in mm NOTES KDD FAN FOR FWDP 008 014 018 KD2 FAN FOR FWDP 024 028 032 MODEL 008 014 018 024 028 032 A 635 813 1148 1524 1651 B 669 5 847 5 1182 5 1558 5 1685 5 C 703 5 881 5 1216 5 1592 5 1719 5 MODEL 008 014 018 024 028 032 3 ROWS 161 D 4 ROWS 183 6 ROWS 227 ...

Страница 8: ...AINTENANCE The unit can be moved using a forklift of suitable capacity For lifting the unit into an elevated mounting pasition run lifting straps or slings under the unit and attach securely to the lifting device Use spreader bars to protect the unit casing from damage Test lift the unit to determine proper balance and stability Caution Use spreader bars to prevent straps from damaging the unit In...

Страница 9: ...sting structural beams c Coil Piping Connections Coils are fitted with 1 1 4 32mm BSPT MALE threaded connections To complete piping connections attach the water piping with 1 1 4 inch connection to the coil The water inlet is on the bottom and water outlet on the top of the coil Coil connection size and coil connection locations are given in page 3 d Condensate Drain Connections These air handlers...

Страница 10: ...ion transmission may cause a noice problem within the building structure 3 Ensure all connections are tight and no wires exposed 4 All accessories must be installed and wired according to the instructions packaged with that accessory Installation Checklist Complete this checklist once the unit is installed to verify that all recommended procedures have been accomplished before the system is starte...

Страница 11: ...TRANE 7 Wiring Diagram ...

Страница 12: ...s may result in immendiate cancellation of the warranty Training The equipment described in this manual is the result of many years of research and continuous developement To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time the constructor have at your disposal a refrigeration and air conditioning service school The principal a...

Страница 13: ...this event please refer to your nearest TRANE office For additional information contact FWDP SVX01A E4 June 2008 FWDP SVX01A E4 July 2006 Malaysia Literature Order Number File Number Supersedes Stocking Location Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Only qualified technicians should perform th...

Отзывы: