background image

18-CD32D1-3  

7

Installer’s Guide

FURNACE 

FRONT

A (width)

B (depth)

C

D

3

UPFLO

W

FURNA

CE

CASED

COIL

SCREWS

(BOTH SIDES)

STANDOFFS

(BOTH SIDES)

STANDOFFS (4)

DRILL SCREWS (4)

FOR VERTICAL  

INSTALLATIONS:

1

2

UPFLOW INSTALLATION

Standoffs and screws (See Figure 1) are included with the 

cased coils for attachment to the furnace.  There are clear-

ance alignment holes near the bottom of the coil wrapper.  

Drill screws are used to engage the furnace top flanges.  

The standoff is inserted into the cabinet alignment hole. 

The drill screws are inserted through the standoffs then 

screwed into the furnace flange.  The coil is always placed 

downstream of the furnace airflow.  The above instructions 

apply only if the coil is on top of an upflow furnace.

DOWNFLOW INSTALLATION

WARNING

!

FIRE HAZARD 
Do not install the furnace directly on carpeting, tile or 
other combustible material other than wood flooring.  
For vertical downflow application, subbase (BAY-
BASE205) must be used between the furnace and 
combustible flooring.  When the downflow furnace is 
installed vertically with a cased coil, a subbase is not 
required.  Failure to follow this warning could result 
in property damage, personal injury or death.

REQUIRED FLOOR OPENING:  (DOWNFLOW)

 

See Figure 3 and Table 1

TABLE 1

CABINET

WIDTH

RETURN 

DUCT WIDTH

FLOOR  OPENING                                PLENUM OPENING

"A"   

"B"

"C"

"D"

17-1/2"

16-1/4"

16-5/8"

20-1/8"

15-5/8"

19-3/8"

21"

19-3/4"

20-1/8"

20-1/8"

19-1/8"

19-3/8"

24-1/2"

23-1/4"

23-5/8"

20-1/8"

22-5/8"

19-3/8"

HORIZONTAL INSTALLATION

The coil and furnace must be fully supported when used in 

the horizontal.
Three brackets (with screws) are included with downflow 

furnaces for installation to stabilize and secure the furnace 

and TXC cased coil in the 

horizontal position

. See Fig-

ure 4.

IMPORTANT: 

The 2/4TXC cased coil must be placed downstream in the 

supply air of the furnace.  In horizontal installations, the 

apex of the coil may point either toward or away from the 

furnace.  See the 2/4TXC coil Installer's Guide for more 

details. 

The cased coil is secured to the furnace and both the fur-

nace 

and

 the cased coil must be properly supported.  The 

brackets mount using the rear screws on the coil case and 

use the screws provided to secure the bracket to the fur-

nace.  The remaining bracket is placed as close to center as 

possible (horizontally) between the coil case front and the 

 furnace bottom channel (for downflow/horizontal furnace).  

Use four of the screws provided to secure the bracket.

This furnace may be installed in an attic or crawl space in 

the horizontal position by placing the furnace on the left or 

right side (as viewed from the front in the upright posi-

tion).  The horizontal furnace installation in an attic should 

be on a service platform large enough to allow for proper 

clearances on all sides and service access to the front of 

the furnace (See Clearance Table on Outline Drawings and 

Figure 5).

If the furnace is suspended using perforated steel strap 

(plumber’s strap), it must be supported at all four corners 

and in the middle at the front of the furnace.  The forward 

most screw on the side of the furnace may be used to con-

nect the strapping (See Figure 7).  Line contact is only per-

missible between lines formed by the intersection of the top 

and two sides of the furnace casing and the building joists, 

studs, or framing.

CASED COIL CONNECTION 

BRACKET FOR DOWNFLOW FUR-

NACE IN HORIZONTAL

4

5

Typical Upflow/Horizontal Attic Installation

Содержание DD2B060ACV32A Series

Страница 1: ...18 CH23D1 latest version 1 Horizontal Conversion for these furnaces may be left or right side rotation 2 Horizontal Conversion for these furnaces may be left or right side rotation Important See venti...

Страница 2: ...try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If...

Страница 3: ...th temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace 7 When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outsid...

Страница 4: ...ing agency Codes and local utility requirements governing the instal lation of gas fired equipment wiring plumbing and flue connections must be adhered to In the absence of local codes the installatio...

Страница 5: ...CD32D1 3 5 Installer s Guide UD2B060ACV32A UD2B080ACV32A UD2B100ACV32A UD2C080ACV42A UD2C100ACV52A UD2D120ACV52A UD2D140ACV52A From Dwg C341699 Rev 9 UD ACV OUTLINE DRAWING ALL DIMENSIONS ARE IN INCH...

Страница 6: ...C341700 Rev 5 DD2 ACV OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES MODEL A B C D DD2B060ACV32A DD2B080ACV32A 17 1 2 9 5 8 16 1 4 16 DD2C100ACV52A 21 13 1 16 19 3 4 19 1 2 DD2D120ACV52A 24 1 2 15 5 16...

Страница 7: ...naces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal position See Fig ure 4 IMPORTANT The 2 4TXC cased coil must be placed downstream in the supply air of th...

Страница 8: ...Installer s Guide 6 Airflow Airflow Airflow Airflow Airflow Airflow Airflow Downflow Horizontal Furnace Vent Applications Horizontal Vertical NOT APPROVED NOT APPROVED APPROVED APPROVED APPROVED APPR...

Страница 9: ...for combustion ventilation and dilution of flue gases Buildings with tight construction for example weather stripping heavily insulated caulked vapor bar rier etc may need additional air provided as d...

Страница 10: ...t or cool position On any job flexible connections of nonflammable mate rial may be used for return air and discharge connections to prevent transmission of vibration Though these units have been spec...

Страница 11: ...ied for bottom or side return Use the filter clips on either side or on the bottom if the filter is to be used within the furnace cabinet When the upflow furnace is installed in the horizontal right o...

Страница 12: ...tment for UPFLOW furnaces in either a BOTTOM or SIDE left side or right side return air inlet Some filters may need to be trimmed for side or bottom filter use NOTE For upflow 5 ton airflow models whe...

Страница 13: ...rew rests against the side of the bottom panel See Figures 19 21 e Reinstall the furnace filter in the side position by inserting the chamfer end first into the filter rack Filter Rack Furnace Cabinet...

Страница 14: ...N LINE INSTALLING THE FILTER The filter may need to be cut to fit the unit depending on the location of the return air filter A score line and the words CUT HERE are located on the end of the filter I...

Страница 15: ...he bracket VENT PIPING These furnaces have been classified as Fan Assisted Combustion System Category I furnaces under the lat est edition provisions of ANSI Z21 47 and CAN CGA 2 3 standards Category...

Страница 16: ...he National Fuel Gas Code ANSI Z223 1 latest edition 9 Vent connectors serving appliance vented by natural draft or non positive pressure shall not be connected into any portion of a mechanized draft...

Страница 17: ...all gas appliances using electrical power this furnace shall be connected into a per manently live electric circuit It is recommended that it be provided with a separate circuit protection device elec...

Страница 18: ...ommunicating Indoor Unit with Communicating Comfort Control and 24VAC Single Stage Cooling 24VAC Mode Indoor Unit with 24VAC Comfort Control and 24VAC Single Stage Cooling NOTE To locate the BK to R j...

Страница 19: ...AC Comfort Control and 24VAC Single Stage Heat Pump NOTE To locate the BK to R jumper on the IFC board see page 21 24VAC Mode Indoor Unit with 24VAC Comfort Control and 24VAC 2 Stage or 2 Step Cooling...

Страница 20: ...20 18 CD32D1 3 Installer s Guide NOTE To locate the BK to R jumper on the IFC board see page 21 24VAC Mode Indoor Unit with 24VAC Comfort Control and 24VAC 2 Stage or 2 Step Heat Pump Wiring Notes...

Страница 21: ...is installed h HUMIDISTAT HOOKUP 24 V Mode ONLY If an optional humidistat for humidity control in cooling is used the factory installed BK Jumper must be cut The BK Jumper must also be cut if a multi...

Страница 22: ...pres sure to the gas valve for propane is 13 8 W C Minimum pressure is 11 0 W C All gas fittings must be checked for leaks using a soapy solution before lighting the furnace DO NOT CHECK WITH AN OPEN...

Страница 23: ...pressure turn the regulator adjustment screw counterclockwise c Adjust regulator until pressure shown on ma nometer matches the pressure specified in Table 9 1 The input should be more than the name...

Страница 24: ...supplied with the equipment See Table 14 for help in selecting orifices if orifice change is required Furnace input rate and temperature rise should be checked again after changing orifices to confirm...

Страница 25: ...f leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life CAUTION Whenever your house is to be vacant arrange to have someone inspect your...

Страница 26: ...ER to make selection Viewing Window User Interface pictured above adjusts Variable Speed Airflow options and is used for custom setup of Furnace operations See menu options in User Interface on pages...

Страница 27: ...0 1300 A TUD2D140 1920 1920 2030 1610 Information Menu Information Options A TDD2B060 960 960 1060 860 A TDD2B080 1120 1120 1260 1000 MODEL NUMBER MODEL A TDD2C100 1460 1460 1600 1300 A TUD2 A TDD2D12...

Страница 28: ...specific 50 50 75 100 25 A TUD2B060 1000 1000 1060 820 A TUD2B080 1380 1380 1470 1200 FAN PRERUN DLY FAN PRERUN DLY A TUD2C080 1260 1260 1380 1110 NONE NONE 1m 50 A TUD2B100 1390 1390 1490 1290 A TUD...

Страница 29: ...seconds and is not field selectable The blower OFF delay is factory set at 100 seconds and can be adjusted to 60 140 or 180 seconds 24v Mode Thermostat call for 1st stage heat 2 stage heating thermos...

Страница 30: ...d model specific data required for proper furnace operation The Personality Module is tethered to the unit and must remain with the furnace at all times The Personality module must remain plugged into...

Страница 31: ...les will be repeated 3 times per hour Use the or arrows to select a duty cycle and then push the Enter button and then the button Start and NO NO will now be displayed With a NO NO question being aske...

Страница 32: ...ble and the Limit Switch must be replaced After checking the operation of the Limit Control be sure to remove the restriction from the return air inlet AIRFLOW ADJUSTMENT Check inlet and outlet air te...

Страница 33: ...ll close the gas valve The flame control module will then recycle the ignition sequence then if ignition is not achieved it will shut off the gas valve and lock out the system 3 POWER FAILURE If there...

Страница 34: ...rt codes also are displayed on the User Interface menu using a descriptive text message and on the comfort control display using an alert code number A com plete list of the alert codes is included wi...

Страница 35: ...Internal control failure None Device count TWIN ERROR N A 19 Twinning Fault Twinning Not Allowed with Variable Speed PM DATA ERR Data Section is Corrupt but PM is useable CAP MISMATCH Compressor size...

Страница 36: ...es the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor Installer s Guide IFC ERROR FLASH COD...

Отзывы: