Trane DD2B060ACV32A Series Скачать руководство пользователя страница 28

28 

 18-CD32D1-3

Installer’s Guide

24V Variable Speed

System Status

Setup Options

[  ] = Current Setting

CMFRT CNT MODE

COMM [24VAC] 24VAC

* Unit specific

COOLING CFM

COOLING CFM

A/TUD2B060

3T [3T]  1.5T  2T  2.5T

*

A/TUD2B080

3T [3T]  3.5T   2.5T 

A/TUD2C080

4T [4T]  2.5T  3T  3.5T

CFM PER TON

CFM PER TON

A/TUD2B100

3T  [3T]  1.5T  2T  2.5T

 400  [ 400 ]  430  450  290  310  330  350  370

A/TUD2C100

5T  [5T]  3T  3.5T  4T

A/TUD2D120

5T  [5T]  3.5T  4T

CLG STAGES

CLG STAGES

5T  [5T]  3T  3.5T  4T

1 STG   [1 STG]    2 STGS

A/TDD2B060

3T  [3T]  1.5T  2T  2.5T

A/TDD2B080

3.5T  [3.5T]  2.5T  3T

CLG 1ST STG CFM 

2

CLG 1ST STG CFM 

2

A/TDD2C100

5T  [5T]  3T  3.5T  4T

50%   [50%]     55%     65%     80%

A/TDD2D120

5T  [5T]  3.5T  4T

CONT FAN CFM

CONT FAN CFM

** Unit specific

50%  [50%]     75%     100%     25%

A/TUD2B060

1000  [1000]    1060    820

A/TUD2B080

1380  [1380]    1470    1200

FAN PRERUN DLY

FAN PRERUN DLY

A/TUD2C080

1260  [1260]    1380    1110

NONE   [NONE]     1m@50%

A/TUD2B100

1390  [1390]    1490    1290

A/TUD2C100

1540  [1540]    1650    1300

FAN SHRTRUN DLY

FAN SHRTRUN DLY

A/TUD2D120

1650  [1650]    1900    1300

NONE   [NONE]      4m@80%     7.5m@80%

1920  [1920]    2030    1610

A/TDD2B060

  960    [960]    1060     860

FAN OFF DLY

FAN OFF DLY

A/TDD2B080

1120  [1120]    1260    1000

1.5m@100%  [1.5m@100%]    NONE     1m@50%     2m@50%     3m@50%

A/TDD2C100

1460  [1460]    1600    1300

A/TDD2D120

1820  [1820]    2000    1600

HEAT CFM

HEAT CFM

**

HT OFF DELAY

HT OFF DELAY

100s [100s]  140  180   60

W1 W2 STG DLY

W1 W2 STG DLY

00m   [00m]   5m     10m     15m 

FACTORY DEFLTS

FACTORY DEFLTS

NO  [NO]             YES

EXIT

EXIT

NO  [NO]             YES

NOTES:

2

  This menu will only display at the comfort control mode when 2 STGS is chosen in previous menu.

A/TUD2D140

A/TUD2D140

USER INTERFACE MENU - 24V SYSTEM

Содержание DD2B060ACV32A Series

Страница 1: ...18 CH23D1 latest version 1 Horizontal Conversion for these furnaces may be left or right side rotation 2 Horizontal Conversion for these furnaces may be left or right side rotation Important See venti...

Страница 2: ...try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If...

Страница 3: ...th temperature rise for cfm versus static is shown in the Service Facts accompanying this furnace 7 When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outsid...

Страница 4: ...ing agency Codes and local utility requirements governing the instal lation of gas fired equipment wiring plumbing and flue connections must be adhered to In the absence of local codes the installatio...

Страница 5: ...CD32D1 3 5 Installer s Guide UD2B060ACV32A UD2B080ACV32A UD2B100ACV32A UD2C080ACV42A UD2C100ACV52A UD2D120ACV52A UD2D140ACV52A From Dwg C341699 Rev 9 UD ACV OUTLINE DRAWING ALL DIMENSIONS ARE IN INCH...

Страница 6: ...C341700 Rev 5 DD2 ACV OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES MODEL A B C D DD2B060ACV32A DD2B080ACV32A 17 1 2 9 5 8 16 1 4 16 DD2C100ACV52A 21 13 1 16 19 3 4 19 1 2 DD2D120ACV52A 24 1 2 15 5 16...

Страница 7: ...naces for installation to stabilize and secure the furnace and TXC cased coil in the horizontal position See Fig ure 4 IMPORTANT The 2 4TXC cased coil must be placed downstream in the supply air of th...

Страница 8: ...Installer s Guide 6 Airflow Airflow Airflow Airflow Airflow Airflow Airflow Downflow Horizontal Furnace Vent Applications Horizontal Vertical NOT APPROVED NOT APPROVED APPROVED APPROVED APPROVED APPR...

Страница 9: ...for combustion ventilation and dilution of flue gases Buildings with tight construction for example weather stripping heavily insulated caulked vapor bar rier etc may need additional air provided as d...

Страница 10: ...t or cool position On any job flexible connections of nonflammable mate rial may be used for return air and discharge connections to prevent transmission of vibration Though these units have been spec...

Страница 11: ...ied for bottom or side return Use the filter clips on either side or on the bottom if the filter is to be used within the furnace cabinet When the upflow furnace is installed in the horizontal right o...

Страница 12: ...tment for UPFLOW furnaces in either a BOTTOM or SIDE left side or right side return air inlet Some filters may need to be trimmed for side or bottom filter use NOTE For upflow 5 ton airflow models whe...

Страница 13: ...rew rests against the side of the bottom panel See Figures 19 21 e Reinstall the furnace filter in the side position by inserting the chamfer end first into the filter rack Filter Rack Furnace Cabinet...

Страница 14: ...N LINE INSTALLING THE FILTER The filter may need to be cut to fit the unit depending on the location of the return air filter A score line and the words CUT HERE are located on the end of the filter I...

Страница 15: ...he bracket VENT PIPING These furnaces have been classified as Fan Assisted Combustion System Category I furnaces under the lat est edition provisions of ANSI Z21 47 and CAN CGA 2 3 standards Category...

Страница 16: ...he National Fuel Gas Code ANSI Z223 1 latest edition 9 Vent connectors serving appliance vented by natural draft or non positive pressure shall not be connected into any portion of a mechanized draft...

Страница 17: ...all gas appliances using electrical power this furnace shall be connected into a per manently live electric circuit It is recommended that it be provided with a separate circuit protection device elec...

Страница 18: ...ommunicating Indoor Unit with Communicating Comfort Control and 24VAC Single Stage Cooling 24VAC Mode Indoor Unit with 24VAC Comfort Control and 24VAC Single Stage Cooling NOTE To locate the BK to R j...

Страница 19: ...AC Comfort Control and 24VAC Single Stage Heat Pump NOTE To locate the BK to R jumper on the IFC board see page 21 24VAC Mode Indoor Unit with 24VAC Comfort Control and 24VAC 2 Stage or 2 Step Cooling...

Страница 20: ...20 18 CD32D1 3 Installer s Guide NOTE To locate the BK to R jumper on the IFC board see page 21 24VAC Mode Indoor Unit with 24VAC Comfort Control and 24VAC 2 Stage or 2 Step Heat Pump Wiring Notes...

Страница 21: ...is installed h HUMIDISTAT HOOKUP 24 V Mode ONLY If an optional humidistat for humidity control in cooling is used the factory installed BK Jumper must be cut The BK Jumper must also be cut if a multi...

Страница 22: ...pres sure to the gas valve for propane is 13 8 W C Minimum pressure is 11 0 W C All gas fittings must be checked for leaks using a soapy solution before lighting the furnace DO NOT CHECK WITH AN OPEN...

Страница 23: ...pressure turn the regulator adjustment screw counterclockwise c Adjust regulator until pressure shown on ma nometer matches the pressure specified in Table 9 1 The input should be more than the name...

Страница 24: ...supplied with the equipment See Table 14 for help in selecting orifices if orifice change is required Furnace input rate and temperature rise should be checked again after changing orifices to confirm...

Страница 25: ...f leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life CAUTION Whenever your house is to be vacant arrange to have someone inspect your...

Страница 26: ...ER to make selection Viewing Window User Interface pictured above adjusts Variable Speed Airflow options and is used for custom setup of Furnace operations See menu options in User Interface on pages...

Страница 27: ...0 1300 A TUD2D140 1920 1920 2030 1610 Information Menu Information Options A TDD2B060 960 960 1060 860 A TDD2B080 1120 1120 1260 1000 MODEL NUMBER MODEL A TDD2C100 1460 1460 1600 1300 A TUD2 A TDD2D12...

Страница 28: ...specific 50 50 75 100 25 A TUD2B060 1000 1000 1060 820 A TUD2B080 1380 1380 1470 1200 FAN PRERUN DLY FAN PRERUN DLY A TUD2C080 1260 1260 1380 1110 NONE NONE 1m 50 A TUD2B100 1390 1390 1490 1290 A TUD...

Страница 29: ...seconds and is not field selectable The blower OFF delay is factory set at 100 seconds and can be adjusted to 60 140 or 180 seconds 24v Mode Thermostat call for 1st stage heat 2 stage heating thermos...

Страница 30: ...d model specific data required for proper furnace operation The Personality Module is tethered to the unit and must remain with the furnace at all times The Personality module must remain plugged into...

Страница 31: ...les will be repeated 3 times per hour Use the or arrows to select a duty cycle and then push the Enter button and then the button Start and NO NO will now be displayed With a NO NO question being aske...

Страница 32: ...ble and the Limit Switch must be replaced After checking the operation of the Limit Control be sure to remove the restriction from the return air inlet AIRFLOW ADJUSTMENT Check inlet and outlet air te...

Страница 33: ...ll close the gas valve The flame control module will then recycle the ignition sequence then if ignition is not achieved it will shut off the gas valve and lock out the system 3 POWER FAILURE If there...

Страница 34: ...rt codes also are displayed on the User Interface menu using a descriptive text message and on the comfort control display using an alert code number A com plete list of the alert codes is included wi...

Страница 35: ...Internal control failure None Device count TWIN ERROR N A 19 Twinning Fault Twinning Not Allowed with Variable Speed PM DATA ERR Data Section is Corrupt but PM is useable CAP MISMATCH Compressor size...

Страница 36: ...es the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact your local dealer distributor Installer s Guide IFC ERROR FLASH COD...

Отзывы: