28
18-CD32D1-3
Installer’s Guide
24V Variable Speed
System Status
Setup Options
[ ] = Current Setting
CMFRT CNT MODE
COMM [24VAC] 24VAC
* Unit specific
COOLING CFM
COOLING CFM
A/TUD2B060
3T [3T] 1.5T 2T 2.5T
*
A/TUD2B080
3T [3T] 3.5T 2.5T
A/TUD2C080
4T [4T] 2.5T 3T 3.5T
CFM PER TON
CFM PER TON
A/TUD2B100
3T [3T] 1.5T 2T 2.5T
400 [ 400 ] 430 450 290 310 330 350 370
A/TUD2C100
5T [5T] 3T 3.5T 4T
A/TUD2D120
5T [5T] 3.5T 4T
CLG STAGES
CLG STAGES
5T [5T] 3T 3.5T 4T
1 STG [1 STG] 2 STGS
A/TDD2B060
3T [3T] 1.5T 2T 2.5T
A/TDD2B080
3.5T [3.5T] 2.5T 3T
CLG 1ST STG CFM
2
CLG 1ST STG CFM
2
A/TDD2C100
5T [5T] 3T 3.5T 4T
50% [50%] 55% 65% 80%
A/TDD2D120
5T [5T] 3.5T 4T
CONT FAN CFM
CONT FAN CFM
** Unit specific
50% [50%] 75% 100% 25%
A/TUD2B060
1000 [1000] 1060 820
A/TUD2B080
1380 [1380] 1470 1200
FAN PRERUN DLY
FAN PRERUN DLY
A/TUD2C080
1260 [1260] 1380 1110
NONE [NONE] 1m@50%
A/TUD2B100
1390 [1390] 1490 1290
A/TUD2C100
1540 [1540] 1650 1300
FAN SHRTRUN DLY
FAN SHRTRUN DLY
A/TUD2D120
1650 [1650] 1900 1300
NONE [NONE] 4m@80% 7.5m@80%
1920 [1920] 2030 1610
A/TDD2B060
960 [960] 1060 860
FAN OFF DLY
FAN OFF DLY
A/TDD2B080
1120 [1120] 1260 1000
1.5m@100% [1.5m@100%] NONE 1m@50% 2m@50% 3m@50%
A/TDD2C100
1460 [1460] 1600 1300
A/TDD2D120
1820 [1820] 2000 1600
HEAT CFM
HEAT CFM
**
HT OFF DELAY
HT OFF DELAY
100s [100s] 140 180 60
W1 W2 STG DLY
W1 W2 STG DLY
00m [00m] 5m 10m 15m
FACTORY DEFLTS
FACTORY DEFLTS
NO [NO] YES
EXIT
EXIT
NO [NO] YES
NOTES:
2
This menu will only display at the comfort control mode when 2 STGS is chosen in previous menu.
A/TUD2D140
A/TUD2D140
USER INTERFACE MENU - 24V SYSTEM