CVGF-SVN02B-E4
38
6. Check the clearance on each
isolator. If this dimension is
less than 1/4" (6 mm) on any
isolator, use a wrench to turn
the adjusting bolt one
complete revolution upward.
Repeat this operation until a
1/4" (6 mm) clearance is
obtained at all isolators.
7. After the minimum required
clearance is obtained on each
of the isolators, level the
chiller by turning the adjusting
bolt on each of the isolators
on the low side of the unit. Be
sure to work from one isolator
to the next.
Remember that the chiller
must be level to within 1/4" (6
mm) over its length and width
and that clearance of each
isolator must be 1/4" (6 mm).
Figure 7. Chiller foot or isolator orientation
Side View of Unit
End View of Unit
Center
tube
sheet
support
leg
End of
tube sheet
Outside edge
of tube sheet
Center of Isolator
Spring
Note:
The spring isolator must be
centered in relation to the tube sheet. Do
not
align the isolator with the flat part of
the chiller foot, because the tube sheet is
often off-center.
Note:
Place isolator near outside edge of
tube sheet as shown.
Installation:
Mechanical