![Trane CVGF 1000 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/trane/cvgf-1000/cvgf-1000_operation-and-maintenance-manual_1149655022.webp)
CVGF-SVU02B-E4
22
Control Panel Devices and
Unit Mounted Devices
Unit Control Panel (UCP)
Safety and operating controls
are housed in the unit control
panel, and the starter panel. The
UCP ‘s operator interface and
main processor is called the
DynaView
™
and is located on the
UCP door. (See Operators
interface section for detailed
information)
The UCP houses several other
controls modules called panel
mounted LLID (Low Level
Intelligent Device), power
supply, terminal block, fuse,
circuit breakers, and transformer.
The IPC (Interprocessor
communication) bus allows the
communications between LLID’s
and the main processor. Unit
mounted devices are called
frame mounted LLID’s and can
be temperature sensors or
pressure transducers. These and
other functional switches
provide analog and binary inputs
to the control system.
Unit Control
Panel (UCP)
Figure 12. Control panel
Содержание CVGF 1000