CSRA-SVX02A-EN
29
Installation
Figure 9 — (Incorrect Horizontal Hose Installation)
Incorrect horizontal hose installation shows an incorrect hose installation.
Elbows are not installed. This causes the top of the hose to be in tension,
which stretches the hose out of the coupling; and the bottom of the hose to
be in compression, which causes it to crimp. It also causes the hose to crimp
at the ground.
The following figures illustrate the correct and incorrect methods for installing
hose in a vertical hookup application.
Figure 10— Correct Vertical Hose Installation
Correct vertical hose installation shows a correct vertical hose installation. In
this configuration, the hose is installed with an elevation less than 7 feet off
the ground. A 45° elbow is installed to reduce the stress in the hose coupling
connection. This elbow also directs the hose to the ground at an appropriate
angle to minimize the crimping of the hose at the ground or supporting
surface.
Содержание CSRA025FAF0
Страница 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Страница 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Страница 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Страница 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Страница 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Страница 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Страница 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Страница 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...