STEP 9:

Route the Wire from Control to Sensor

Run a separate 18 ga. control wire to the outdoor temperature sensor.
Sensor is not affected by lead length. In either case, do not run outdoor
temperature sensor alongside wires carrying high voltage (120 VAC or
higher). Secure the sensor bracket with a #8 galvanized screw.

STEP 10:

Attach Sensor Wire to Humidifier Control

Strip wire 1/4 inch, and
insert the wires from the
Sensor into the terminals
labeled “ODT” on the
Humidifier Control. See

Figure F

for location of

terminals.

Installing the Humidifier Control for Manual Operation

If it is not feasible to use the Outdoor Temperature Sensor, the
Humidifier Control can be operated in Manual Mode.

1. Connect the Manual Mode Resistor Case wires to the terminals

labeled “ODT” on the Humidifier Control.

2. Snap the Manual Mode Resistor Case into the slot provided so that

Resistor Case sticks out from the bottom edge of the base.

3. Remove the

control knob
and apply the
Manual Mode
label to the
cover, aligning
the sticker and
knob holes.
Re-install the
knob.

STEP 8:

Alternate Location for Outdoor Temperature Sensor

The Sensor can also be mounted in the center of either:

• 2 inch PVC fresh air intake pipe for the furnace

OR

• 6 inch fresh air intake duct. Mount the sensor with a #8 galvanized screw.

In both cases, the Sensor must
be no more than 3 feet from
the outside wall. See Figure E.

If it is not feasible to use the
Outdoor Temperature Sensor
in any of the ways described,
the Humidifier Control can be
installed for Manual Operation.
See box “Installing the
Humidifier Control for Manual
Operation” and 

Figure G

for

details.

STEP 11:

Determine Power Source for Humidifier Control

Determine where you will get 24 VAC to power the Humidifier Control 
(see options below).

OPTION 1: 

FURNACES WITH ACCESSORY TERMINALS. 

If the accessory terminals provide:

• 24 VAC: Wire these directly to the “R” and “C” terminals on the

Humidifier Control.

• 120 VAC: Wire to a 24 VAC transformer, which in turn connects to the “R”

and “C” terminals on the Humidifier Control.

OPTION 2: 

EXTERNAL 24 VAC TRANSFORMER: 

Wire into a power source other than the furnace blower circuit. The
transformer can be powered off the 120 VAC line at the junction box before
it enters the furnace. The 24 volt side of the transformer is connected to
the “R” and “C” terminals on the Humidifier Control.

In either case, the voltage to the Humidifier Control must be between 
22 VAC and 30 VAC. Run a separate 18 ga. wire from a 24-volt supply to the
humidifier control.

NOTES:

• The Humidifier Control will operate properly with either a switched or

continuous power source.

• Whether using ACCESSORY TERMINALS OR an EXTERNAL

TRANSFORMER, the minimum VA required is; 2.0 VA for Power
Humidifiers; or 10.0 VA for Bypass Humidifiers.

• When power is connected for the first time, the red and green LEDs will

light momentarily.

STEP 12:

Wiring

See 

Diagrams A-D

for wiring options.

24V

R

C

BYP

ASS

ODT

H

PO

WER

R

24V

BYP

ASS

C

ODT

H

PO

WER

Figure G

STEP 6:

Determine Location for Outdoor Temperature Sensor

The location of the Outdoor Temperature Sensor must meet these three
requirements:

1. Must be mounted on North, East or West side of house out of direct

sunlight

2.

Must be at least 
3 feet from all
exhaust vents

3. Must be above

expected snow line
(See 

Figure D

)

Incorrect humidity
levels will result if
these requirements
are not met.

STEP 7:

Locate Existing Access Hole to Outside

A convenient way to get the Sensor wire outside is to make use of unused
wires running to the A/C condensing unit (if applicable). Other ways are to
use existing holes for Cable TV lines, telephone lines, A/C lines, etc. Read
all equipment instructions beforehand for possible conflicts and warnings.

90-1013

Figure F

90-1012

36" MAX.

CENTER LINE

OUTSIDE WALL

Figure E

90-999

STEP 5:

Determine Location for Humidifier Control 
and Mount It

Humidifier Control must be mounted in the Return Duct. For proper operation,
the Humidifier Control must be at least 6 inches upstream of any of the
following:

• Humidifier
• Humidifier Bypass Ductwork (if applicable)
• Fresh Air Intake Ductwork (if applicable) (see 

Figure C

)

After location for Control
is selected, use the
perforated Humidifier
Control template
(attached to these
instructions) to mark the
duct opening and cut it.
Use 4 sheet metal screws
(not provided) to mount
the Humidifier Control in
the duct opening and

make sure Humidifier
Control is sealed tightly
to duct.

6" MIN. 

RETURN 

DUCT 

HUMIDIFIER 

CONTROL 

FRESH AIR 

INTAKE 

COIL 

HUMIDIFIER 

BYPASS 

CONNECTION 

Figure C

90-1137

NORTH, EAST
OR WEST SIDE
OF HOME

OUTDOOR

TEMPERATURE

SENSOR

SENSOR

BRACKET

SENSOR

ABOVE EXPECTED 

SNOW LINE

OUTDOOR

TEMPERATURE SENSOR

LEADS

Figure D

90-998

CAUTION

Do not mount control on supply air plenum or duct. Failure to follow this
caution my cause property damage.

18-CH31D1-3