STEP 9:
Route the Wire from Control to Sensor
Run a separate 18 ga. control wire to the outdoor temperature sensor.
Sensor is not affected by lead length. In either case, do not run outdoor
temperature sensor alongside wires carrying high voltage (120 VAC or
higher). Secure the sensor bracket with a #8 galvanized screw.
STEP 10:
Attach Sensor Wire to Humidifier Control
Strip wire 1/4 inch, and
insert the wires from the
Sensor into the terminals
labeled “ODT” on the
Humidifier Control. See
Figure F
for location of
terminals.
Installing the Humidifier Control for Manual Operation
If it is not feasible to use the Outdoor Temperature Sensor, the
Humidifier Control can be operated in Manual Mode.
1. Connect the Manual Mode Resistor Case wires to the terminals
labeled “ODT” on the Humidifier Control.
2. Snap the Manual Mode Resistor Case into the slot provided so that
Resistor Case sticks out from the bottom edge of the base.
3. Remove the
control knob
and apply the
Manual Mode
label to the
cover, aligning
the sticker and
knob holes.
Re-install the
knob.
STEP 8:
Alternate Location for Outdoor Temperature Sensor
The Sensor can also be mounted in the center of either:
• 2 inch PVC fresh air intake pipe for the furnace
OR
• 6 inch fresh air intake duct. Mount the sensor with a #8 galvanized screw.
In both cases, the Sensor must
be no more than 3 feet from
the outside wall. See Figure E.
If it is not feasible to use the
Outdoor Temperature Sensor
in any of the ways described,
the Humidifier Control can be
installed for Manual Operation.
See box “Installing the
Humidifier Control for Manual
Operation” and
Figure G
for
details.
STEP 11:
Determine Power Source for Humidifier Control
Determine where you will get 24 VAC to power the Humidifier Control
(see options below).
OPTION 1:
FURNACES WITH ACCESSORY TERMINALS.
If the accessory terminals provide:
• 24 VAC: Wire these directly to the “R” and “C” terminals on the
Humidifier Control.
• 120 VAC: Wire to a 24 VAC transformer, which in turn connects to the “R”
and “C” terminals on the Humidifier Control.
OPTION 2:
EXTERNAL 24 VAC TRANSFORMER:
Wire into a power source other than the furnace blower circuit. The
transformer can be powered off the 120 VAC line at the junction box before
it enters the furnace. The 24 volt side of the transformer is connected to
the “R” and “C” terminals on the Humidifier Control.
In either case, the voltage to the Humidifier Control must be between
22 VAC and 30 VAC. Run a separate 18 ga. wire from a 24-volt supply to the
humidifier control.
NOTES:
• The Humidifier Control will operate properly with either a switched or
continuous power source.
• Whether using ACCESSORY TERMINALS OR an EXTERNAL
TRANSFORMER, the minimum VA required is; 2.0 VA for Power
Humidifiers; or 10.0 VA for Bypass Humidifiers.
• When power is connected for the first time, the red and green LEDs will
light momentarily.
STEP 12:
Wiring
See
Diagrams A-D
for wiring options.
24V
R
C
BYP
ASS
ODT
H
PO
WER
R
24V
BYP
ASS
C
ODT
H
PO
WER
Figure G
STEP 6:
Determine Location for Outdoor Temperature Sensor
The location of the Outdoor Temperature Sensor must meet these three
requirements:
1. Must be mounted on North, East or West side of house out of direct
sunlight
2.
Must be at least
3 feet from all
exhaust vents
3. Must be above
expected snow line
(See
Figure D
)
Incorrect humidity
levels will result if
these requirements
are not met.
STEP 7:
Locate Existing Access Hole to Outside
A convenient way to get the Sensor wire outside is to make use of unused
wires running to the A/C condensing unit (if applicable). Other ways are to
use existing holes for Cable TV lines, telephone lines, A/C lines, etc. Read
all equipment instructions beforehand for possible conflicts and warnings.
90-1013
Figure F
90-1012
36" MAX.
CENTER LINE
OUTSIDE WALL
Figure E
90-999
STEP 5:
Determine Location for Humidifier Control
and Mount It
Humidifier Control must be mounted in the Return Duct. For proper operation,
the Humidifier Control must be at least 6 inches upstream of any of the
following:
• Humidifier
• Humidifier Bypass Ductwork (if applicable)
• Fresh Air Intake Ductwork (if applicable) (see
Figure C
)
After location for Control
is selected, use the
perforated Humidifier
Control template
(attached to these
instructions) to mark the
duct opening and cut it.
Use 4 sheet metal screws
(not provided) to mount
the Humidifier Control in
the duct opening and
make sure Humidifier
Control is sealed tightly
to duct.
6" MIN.
RETURN
DUCT
HUMIDIFIER
CONTROL
FRESH AIR
INTAKE
COIL
HUMIDIFIER
BYPASS
CONNECTION
Figure C
90-1137
NORTH, EAST
OR WEST SIDE
OF HOME
OUTDOOR
TEMPERATURE
SENSOR
SENSOR
BRACKET
SENSOR
ABOVE EXPECTED
SNOW LINE
OUTDOOR
TEMPERATURE SENSOR
LEADS
Figure D
90-998
CAUTION
Do not mount control on supply air plenum or duct. Failure to follow this
caution my cause property damage.
18-CH31D1-3