Trane ComfortLink II Charge Assist 4TTZ0 Series Скачать руководство пользователя страница 2

Installer’s Guide

(INFORMATION APPLICABLE TO 

ALL UNITS:) 

  1.  When removing unit from the pallet, notice the tabs on the 

basepan. Remove tabs by cutting with a sharp tool as shown 

in Figure 2 and slide unit off of pallet.

  2.  The unit should be set on a 

level support pad at least as 

large as the unit base pan, such as a concrete slab. If this is 

not the application used please refer to Application Guide 

SSC-APG005-EN.

  3.  The support pad must NOT be in direct contact with any 

structure. Unit must be positioned a minimum of 12" from 

any wall or surrounding shrubbery to insure adequate airflow. 

Clearance must be provided in front of control box (access 

panels) and any other side requiring service access to meet 

National Electrical Code. Also, the unit location must be far 

enough away from any structure to prevent excess roof run-off 

water from pouring directly on the unit. Do not locate unit(s) 

close to bedroom(s).

  4.  The top discharge area must be unrestricted for at least five 

(5) feet above the unit.  See Figure 1.

  5.  When the outdoor unit is mounted on a roof, be sure the roof 

will support the unit’s weight. Properly selected isolation is 

recommended to prevent transmission to the building struc-

ture.

  6.  The maximum length of refrigerant lines from outdoor to 

indoor unit should NOT exceed eighty 

(80)

 feet.  

  7.  If outdoor unit is mounted above the air handler, maxi  mum 

lift should not exceed twenty-five (25) feet (suction line). If 

air handler is mounted above condensing unit, maximum lift 

should not exceed twenty-five (25) feet (liquid line).

  8.  Locate and install indoor coil or air handler in accordance 

with instruction included with that unit.

c.  InStaLLInG refrIGerant LIneS

caUtIon

!

If using existing refrigerant lines make certain that all joints are 

brazed, not soldered.

Condensing units have provisions for braze connections.
Pressure taps are provided on the service valves of outdoor unit for 

compressor suction and liquid pressures.
The indoor end of the recommended refrigerant line sets may 

be straight or with a ninety (90) degree bend, depending upon 

 situation requirements. This should be thoroughly checked out 

before ordering refrigerant line sets.

NOTE: 

The gas line must always be insulated.  Liquid lines that run 

through attic space must also be insulated.

The units are factory charged with the system charge required 

when using fifteen (15) feet of rated connecting line. See unit 

nameplate.
Final refrigerant charge adjustment is necessary. Use 

Charge Assist™ or the Manual Charging procedure found in the 

outdoor unit Service Facts.  Charge level can always be verified 

with the Refrigerant Charging Chart found in the Service Facts.

 

 

1.  Determine the most practical way to run the lines.

  2.  Consider types of bends to be made and space  limitations.

NOTE: 

Large diameter tubing will be very difficult to rebend once it has 

been shaped.

  3.  Determine the best starting point for routing the refrigerant 

tubing — INSIDE OR OUTSIDE THE STRUCTURE.

  4.  Provide a pull-thru hole of sufficient size to allow both liquid 

and gas lines.

  5.  Be sure the tubing is of sufficient length.
  6.  Uncoil the tubing — do not kink or dent.
  7.  Route the tubing making all required bends and  properly 

secure the tubing before making connections.

  8.  To prevent a noise within the building structure due to vibra-

tion transmission from the refrigerant lines, the following 

precautions should be taken:

 

a.  When the refrigerant lines have to be fastened to floor 

joists or other framing in a structure, use isolation type 

hangers.

 

b.  Isolation hangers should also be used when refrigerant 

lines are run in stud spaces or enclosed ceilings.

 

c.  Where the refrigerant lines run through a wall or sill, they 

should be insulated and isolated.

 

d.  Isolate the lines from all ductwork.

d.  ServIce vaLve oPeratIon

BraSS LIqUId LIne ServIce vaLve

The Brass Liquid Line Service Valve is factory shipped in the 

seated position to hold factory charge. The pressure tap service 

port (when depressed) opens only to the field brazing side of the 

valve when the valve is in the seated position. The liquid line valve 

is 

not a back seating valve (see WARNING below).

WarnInG

!

extreme caution should be exercised when opening the Liquid 

Line Service valve. turn valve stem counterclockwise only until 

the stem contacts the rolled edge. (See figure 3). no torque is 

required. failure to follow this warning will result in abrupt re-

lease of system charge and may result in personal injury and/or 

property damage.

BraSS GaS LIne BaLL ServIce vaLve

The Brass Gas Line Service Valve is shipped in the closed position 

to hold the factory refrigerant charge. The pressure tap service 

port (when depressed) opens only to the field brazing side when the 

valve is in the closed position.
The Gas Line Ball Service Valve is full open with a 1/4 turn. See 

Figure 4.

BraZInG refrIGerant LIneS

  1.  Remove lower access cover to access service valves.
  2.  Before brazing, remove plugs from external copper stub tubes. 

Clean internal and external surfaces of stub tubes prior to 

brazing.

  3.  Cut and fit tubing, minimizing the use of sharp 90° bends.
  4.  Insulate the entire gas line and its fittings.
  5.  Do 

NOT allow uninsulated liquid line to come in direct con-

tact with bare gas line.

LIqUId LIne ServIce vaLve

3

BaSePan  

taB reMovaL

2

© 2009 Trane

 

 

18-BC53D2-3

Содержание ComfortLink II Charge Assist 4TTZ0 Series

Страница 1: ...be replaced Never break a vacuum with air and always change the driers when opening the system for component replacement For specific handling concerns with R 410A and POE AB oil reference Retrofit Bu...

Страница 2: ...vice Facts Charge level can always be verified with the Refrigerant Charging Chart found in the Service Facts 1 Determine the most practical way to run the lines 2 Consider types of bends to be made a...

Страница 3: ...e hook up diagram included in these instructions 6 Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing It is recommended that the pressure tap port valve cor...

Страница 4: ...horting any of the other pins to this pin causes the function of the other pin to be executed Leaving this pin open results in the normal mode of operation 2 TST Test Shorting TEST_COMMON to this pin...

Страница 5: ...Installer s Guide Field Wiring Diagram Communicating Indoor Unit Communicating Outdoor Unit 7 NOTE For non communicating systems use 24 volt harness accessory BAYACHP024A 18 BC53D2 3 5...

Страница 6: ...Installer s Guide 8 COMMUNICATING INDOOR UNIT WITH 24V Comfort Control 24V 2 STAGE OR 2 STEP Cooling 6 18 BC53D2 3...

Страница 7: ...Installer s Guide 9 COMMUNICATING INDOOR UNIT WITH 24V Comfort COntrol 24V 2 stage OR 2 STEP heat pump 18 BC53D2 3 7...

Страница 8: ...our Once charged the system will exit Charge Assist and control will return to the Comfort Control Direction for Charge Assist If the system charge is low the ADD LED will turn on and stay on up to on...

Страница 9: ...x Lift 25 20 15 10 0 10 20 25 30 40 60 80 Dip Switch 1 ON TOTAL REFRIGERANT LINE LENGTH FEET REFRIGERANT LINE LIFT FEET Max Lift 25 20 15 10 0 10 20 25 30 40 60 80 4TEE3_06 Air Handler 4TXCC008 Coil 4...

Страница 10: ...C H C H C H C H C H C H C H C H C H C H P P P P P P P P P P P P P P S S S S S S S S S S S S S S S S S S S S S S S S S S S S P P P P S S S S P P P P S S P P P P P P P P P P P P P P S S S S S S S S P P...

Страница 11: ...re in MM Inches MODELS BASE A B C D E F G H J K 4TTZ0024A 4TWZ0024A 4 1369 53 7 8 946 37 1 4 870 34 1 4 5 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 1035 40 3 4 4TTZ0036A 4TWZ0036A 4TTZ0048A 4TWZ0048A 4T...

Страница 12: ...tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply...

Отзывы: