background image

Installer’s Guide

NOTE: 

DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.

NOTE: 

A 3/16" Allen wrench is required to open liquid line service valve. 

A 1/4" Open End or Adjustable wrench is required to open gas 

line valve. A 3/4" Open End wrench is required to take off the 

valve stem cap. 

  9.  The liquid line shut-off valve can now be opened. Remove 

shut-off valve cap. Fully insert hex wrench into the stem and 

backout counterclockwise until valve stem just touches rolled 

edge (approximately five [5] turns) observing 

WARNING 

statement on page 2. See  Figure 3.

 10.  Replace liquid service pressure tap port cap and valve stem 

cap. These caps 

MUST BE REPLACED to prevent leaks. 

Replace valve stem and pressure tap cap finger tight, then 

tighten an additional 1/6 turn.

 11.  The gas valve can now be opened. For a ball type gas valve, 

open the gas valve by removing the shut-off valve cap and turn-

ing the valve stem 1/4 turn counterclockwise, using 1/4" Open 

End or Adjustable wrench. See Figure 4 and refer to Step 8 

prior to opening gas valve. 

 12.  The gas valve is now open for refrigerant flow. Replace valve 

stem cap to prevent leaks. Again, these caps 

MUST BE RE-

PLACED to prevent leaks. Replace valve stem and pressure 

tap cap finger tight, then tighten an additional 1/6 turn. See 

Figure 4.
If refrigerant lines are longer than fifteen (15) feet and/or a 

different size than recommended, it will be necessary to adjust 

system refrigerant charge upon completion of installation. See 

unit Service Facts.

e.  eLectrIcaL connectIonS

WarnInG

!

Live electrical components! 

 

 

during installation, testing, servicing and troubleshooting of this 

product, it may be necessary to work with live electrical com-

ponents.  failure to follow all electrical safety precautions when 

exposed to live electrical components could result in death or 

serious injury.

  1.  Power wiring and grounding of equipment must comply with 

national, state and/or local codes.

  2.  Power supply must agree with equipment nameplate.
  3.  Install a separate disconnect switch at the outdoor unit.
  4.  Ground the outdoor unit per code requirements.
  5.  Provide flexible electrical conduit whenever vibration trans-

mission may create a noise problem within the structure.

  6.  The use of color coded low voltage wire is recommended to 

simplify connections between the outdoor unit, the Com-

fortLink™ II control and the indoor unit

Table 1 – NEC Class II Control Wiring

NOTE: 

The maximum total cable length for the entire Comfort Control 

communicating system is 500 ft. 18 AWG. 

  7.  Mount the ComfortLink™ II control in accordance with in-

struction included with the ComfortLink™ II control.  

Wire per appropriate hook-up diagram (included in these 

 instructions).

  6.

  Precautions should be taken to avoid heat damage 

to the pressure tap valve core during brazing. It is 

recommended that the pressure tap port valve core be 

removed and a wet rag wrapped around the valve body.

NOTE:  

Use care to make sure that no moisture enters pressure tap port, 

while wet rag is being used.

NOTE: 

Precautions should be taken to avoid heat damage to basepan during 

brazing. It is recommended to keep the flame directly off of the basepan.

  7.  Use a Dry Nitrogen Purge and Brazing Alloy without flux 

when brazing the field line to the copper factory connection. 

Flow dry nitrogen into either valve pressure tap port, thru the 

tubing and out the other port while brazing.

  8.  Braze using accepted good brazing techniques.

Leak check

IMPORTANT: 

Replace pressure tap port valve core before attaching hoses for evacuation.

After the brazing operation of refrigerant lines to both the outdoor 

and indoor unit is completed, the field brazed connections must be 

checked for leaks. Pressurize through the service valve ports, the in-

door unit and field refrigerant lines with dry  nitrogen to 350-400 psi. 

Use soap bubbles or other leak-checking methods to see that all 

field joints are leak-free! If not, 

release pressure; then repair!

SySteM evacUatIon

NOTE: 

Since the outdoor unit has a refrigerant charge, the gas and 

liquid line valves must remain closed.

  1.  Upon completion of leak check, evacuate the refrigerant lines 

and indoor coil before opening the gas and liquid line valves.

  2.  Attach appropriate hoses from manifold gauge to gas and 

liquid line pressure taps.

NOTE:  

Unnecessary switching of hoses can be avoided and com plete 

evacuation of all lines leading to sealed system can be accom-

plished with manifold center hose and connecting branch hose to 

a cylinder of R-410A  and vacuum pump.

  3.  Attach center hose of manifold gauges to vacuum pump.
  4.  Evacuate until the micron gauge reads no higher than 350 mi-

crons.

  5.  Close off valve to vacuum pump and observe the micron 

gauge. If gauge pressure rises above 500 microns in one (1) 

minute, then evacuation is incomplete or system has a leak.

  6.  If vacuum gauge does not rise above 500 microns in one (1) 

minute, the evacuation should be complete.

  7.  With vacuum pump and micron gauge blanked off, open valve 

on R-410A cylinder and charge refrigerant lines and indoor 

coil with vapor to tank pressure of R-410A supply.

  8.  Close valve on R-410A supply cylinder.  Close valves on mani-

fold gauge set and remove refrigerant charging hoses from 

liquid and gas pressure tap ports.

caP

1/4 tUrn onLy

coUntercLockWISe

for fULL oPen 

PoSItIon

vaLve SteM

GaS LIne connectIon

UnIt SIde

of vaLve

PreSSUre taP Port

GaS LIne BaLL ServIce vaLve

4

18-BC53D2-3 

 

3

ComfortLink™ II Control Wiring

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

250 FT

Содержание ComfortLink II Charge Assist 4TTZ0 Series

Страница 1: ...be replaced Never break a vacuum with air and always change the driers when opening the system for component replacement For specific handling concerns with R 410A and POE AB oil reference Retrofit Bu...

Страница 2: ...vice Facts Charge level can always be verified with the Refrigerant Charging Chart found in the Service Facts 1 Determine the most practical way to run the lines 2 Consider types of bends to be made a...

Страница 3: ...e hook up diagram included in these instructions 6 Precautions should be taken to avoid heat damage to the pressure tap valve core during brazing It is recommended that the pressure tap port valve cor...

Страница 4: ...horting any of the other pins to this pin causes the function of the other pin to be executed Leaving this pin open results in the normal mode of operation 2 TST Test Shorting TEST_COMMON to this pin...

Страница 5: ...Installer s Guide Field Wiring Diagram Communicating Indoor Unit Communicating Outdoor Unit 7 NOTE For non communicating systems use 24 volt harness accessory BAYACHP024A 18 BC53D2 3 5...

Страница 6: ...Installer s Guide 8 COMMUNICATING INDOOR UNIT WITH 24V Comfort Control 24V 2 STAGE OR 2 STEP Cooling 6 18 BC53D2 3...

Страница 7: ...Installer s Guide 9 COMMUNICATING INDOOR UNIT WITH 24V Comfort COntrol 24V 2 stage OR 2 STEP heat pump 18 BC53D2 3 7...

Страница 8: ...our Once charged the system will exit Charge Assist and control will return to the Comfort Control Direction for Charge Assist If the system charge is low the ADD LED will turn on and stay on up to on...

Страница 9: ...x Lift 25 20 15 10 0 10 20 25 30 40 60 80 Dip Switch 1 ON TOTAL REFRIGERANT LINE LENGTH FEET REFRIGERANT LINE LIFT FEET Max Lift 25 20 15 10 0 10 20 25 30 40 60 80 4TEE3_06 Air Handler 4TXCC008 Coil 4...

Страница 10: ...C H C H C H C H C H C H C H C H C H C H P P P P P P P P P P P P P P S S S S S S S S S S S S S S S S S S S S S S S S S S S S P P P P S S S S P P P P S S P P P P P P P P P P P P P P S S S S S S S S P P...

Страница 11: ...re in MM Inches MODELS BASE A B C D E F G H J K 4TTZ0024A 4TWZ0024A 4 1369 53 7 8 946 37 1 4 870 34 1 4 5 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 1035 40 3 4 4TTZ0036A 4TWZ0036A 4TTZ0048A 4TWZ0048A 4T...

Страница 12: ...tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply...

Отзывы: