PRESSURE CURVES FOR  4TWZ0036B1

TAM7A0C36H31

TAM7A0C36H31

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE.  MEASURE INDOOR WET BULB 
TEMPERATURE, OUTDOOR TEMPERATURE, DISCHARGE AND SUCTION PRESSURES.  ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); 
LOCATE INDOOR WET BULB (2);  FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ DISCHARGE OR SUCTION PRESSURE IN LEFT 
COLUMN (4).

EXAMPLE: (1) OUTDOOR TEMP. 82 F. 

                  (2) INDOOR WET BULB 67 F.  

                  (3) AT INTERSECTION

ACTUAL: 

                  (4) DISCHARGE PRESSURE @ 590 CFM IS 285 PSIG.

DISCHARGE PRESSURE SHOULD BE +/- 10 PSI OF CHART

                  (5) SUCTION PRESSURE @ 1160 CFM IS 149 PSIG.

SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINES

GAS - 3/4" O.D.

LIQUID - 3/8" O.D.

DWG.NO. 4TWZ0036B1

200

250

300

350

400

450

500

550

40

60

80

100

120

115

125

135

145

155

165

175

185

40

60

80

100

120

115

125

135

145

155

165

175

185

40

60

80

100

120

40

50

60

70

80

90

100

110

120

130

140

150

160

-5 5 15 25 35 45 55 65

200

250

300

350

400

450

500

-5 5 15 25 35 45 55 65

40

50

60

70

80

90

100

110

120

130

140

150

160

-5 5 15 25 35 45 55 65

200

250

300

350

400

450

500

-5 5 15 25 35 45 55 65

Heating with Electronic Expansion Valve

INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM

80, 70, AND 60 DEG F.

200

250

300

350

400

450

500

550

40

60

80

100

120

Cooling with Electronic Expansion Valve

INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 

71, 67, 63 AND 59 DEG F.

INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM

71, 67, 63 AND 59 DEG F.

INDOOR ENTERING DRY BULB CURVES TOP TO BOTTOM

80, 70, AND 60 DEG F.

OUTDOOR TEMPERATURE (Degree F)

OUTDOOR TEMPERATURE (Degree F)

2ND STAGE

2ND STAGE

1ST STAGE

1ST STAGE

2ND STAGE

2ND STAGE

1ST STAGE

1ST STAGE

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)

D

ISC

H

AR

G

E PR

ESSU

R

E (

PSI

G

)

SU

C

TI

O

N

 PR

ESSU

R

(PSI

G

)

8

Содержание ComfortLink II 4TWZ0036B1000A

Страница 1: ...Y R 410A REFRIGERANT AND APPROVED POE AB COMPRESSOR OIL PRODUCT SPECIFICATIONS OUTDOOR UNIT 12 POWER CONNS V PH HZ 3 MIN BRCH CIR AMPACITY BR CIR PROT RTG MAX AMPS COMPRESSOR NO USED NO SPEEDS VOLTS P...

Страница 2: ...an be used in cooling mode only For complete instructions on using Charge Assist please see page 4 2 SCHEMATIC DIAGRAM MANUAL CHARGING BELOW 55 F OD AMBIENT IN HEATING MODE HP MODELS ONLY 1 The only r...

Страница 3: ...2 When charging for ambient temperatures above 120 F charge to 10 subcooling It is important to return when outdoor ambient temperature is between 55 F and 120 F to verify system charge per these inst...

Страница 4: ...ash slowly Liquid Line Temperature Must be within range If this sensor is shorted or open This error condition causes an 11 flash on FAULT LED Liquid Line Pressure Must be above 90 psig If the liquid...

Страница 5: ...n LED will be turned ON The CA control will then exit the charge assist cycle and return the control of the system to the Communicating Comfort Control The Status Green LED will be slowly flashing The...

Страница 6: ...TM data Low Pressure Cut Out Fault Open outside of defrost Cycle Short lock out Wait Flashing Flash device count when in communication number of COMM products connected in system Rapid flashes followe...

Страница 7: ...sist Tool BAYCAKT001AA ADD AMBER LED BLINKING CHARGING STABILIZING AMBER LED BLINKING RECOVER RED LED CA procedure allows 1 hour to get within 20 psi of Charged and 50 minutes to move 4 psi Otherwise...

Страница 8: ...0 250 300 350 400 450 500 550 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 40 50 60 70 80 90 100 110 120 130 140 150 160 5 5 15 25...

Страница 9: ...Heating Refrigeration Cycle Cooling Refrigeration Cycle NOTE 1 Line Dampener DO NOT REMOVE LINE DAMPENER SEE NOTE 1 LINE DAMPENER SEE NOTE 1 Printed from D155727P01 Rev03 9 REFRIGERATION CIRCUITS...

Страница 10: ...er up 10 hours max if compressors remain OFF Sump Heat OFF When a compressor is running Sump Heat OFF For 30 minutes after compressor s have stopped running Sump Heat OFF When outdoor temperature goes...

Страница 11: ...Sensors J6 J7 TABLE 3 Temp F Temp C THERMISTOR RESISTANCE OHMS Volts DC at plug J8 Only pin to pin 50 10 0 19405 2 22 55 12 8 17002 2 06 60 15 6 14930 1 90 65 18 3 13138 1 75 70 21 1 11586 1 61 75 23...

Страница 12: ...ng 3 9 Flash Low superheat in Cooling Mode Indoor TXV stuck open or ID Fan failure 10 Flash Not used at this time 3 Monitor superheat and pressure 3 SH for 5 minutes with valve minimum position Monito...

Страница 13: ...n Service Facts EEV Hunting Suction pressure moves up down Sensor are out of calibration 1 Verify sensors are accurate See Table 7 8 in Service Facts Verify temperature sensor is clipped tight to suct...

Страница 14: ...g LPCO may trip Note The Close Valve Test will exit after 1 5 minutes 90 seconds and will not reinitiate requires a break and make to initialize To clear faults stored in memory apply a jumper between...

Страница 15: ...65 0 66 125 51 7 3298 0 60 130 54 4 2972 0 54 135 57 2 2683 0 50 136 57 8 2629 0 49 137 58 3 2576 0 48 138 58 9 2525 0 47 139 59 4 2474 0 46 140 60 0 2425 0 45 141 60 6 2377 0 45 142 61 1 2330 0 44 14...

Страница 16: ...Trane www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice...

Отзывы: