13

TROUBLESHOOTING THE EEV

System is pumping down

in heat mode

EEV is not sensing that the compressor is

ON and in the Heat Mode

1. Check plug and harness to J6

2. Verify 24VAC at Y1 and/or Y2  inputs to

EEV control J6 are present (not “O”) See

Table 6 in Service Facts.

EEV valve is stuck closed

1. See Service Facts for Open Valve Test

System is very low on charge

1. Check charge per Service Facts

Low superheat (flooding) in

heating mode

EEV valve is stuck open

1. See Service Facts for Close Valve Test

Sensors are out of calibration

1. Verify sensors are accurate.  See Table 7

& 8 in Service Facts

High superheat (low

suction pressure) in

heating mode

System is low on charge

1. Check charge per Service Facts

EEV valve is stuck closed

1. See Service Facts for Open Valve Test

Sensors are out of calibration

1. Verify sensors are accurate.  See Table 7

& 8 in Service Facts

EEV Hunting

(Suction pressure moves

up & down)

Sensor are out of calibration

1. Verify sensors are accurate.  See Table 7

& 8 in Service Facts

Verify temperature sensor is clipped tight

to suction line and insulated

Verify Outdoor Unit:

1. Is free and clear of ice and debris

2. Has adequate clearance

3. Distributor tubes are not bent or kinked

The 

Electronic Expansion Valve (EEV)

 installed in this heat pump is designed to control

superheat entering the compressor when the system is running in mechanical heating mode.

During cooling mode, refrigerant flow bypasses the EEV via a check valve and is controlled

by the expansion device in the indoor unit.  Therefore, 

any operational problems

observed in cooling mode are not caused by the EEV

.

The following flow chart was designed to assist in troubleshooting the EEV.
Note:  The EEV closes with every OFF cycle in the heating mode of operation.  During

Defrost and in the cool

sound can be heard when valve is changing positions.

ing mode of operation, the EEV will drive to 1/2 open.  An audible 

Содержание ComfortLink II 4TWZ0036B1000A

Страница 1: ...Y R 410A REFRIGERANT AND APPROVED POE AB COMPRESSOR OIL PRODUCT SPECIFICATIONS OUTDOOR UNIT 12 POWER CONNS V PH HZ 3 MIN BRCH CIR AMPACITY BR CIR PROT RTG MAX AMPS COMPRESSOR NO USED NO SPEEDS VOLTS P...

Страница 2: ...an be used in cooling mode only For complete instructions on using Charge Assist please see page 4 2 SCHEMATIC DIAGRAM MANUAL CHARGING BELOW 55 F OD AMBIENT IN HEATING MODE HP MODELS ONLY 1 The only r...

Страница 3: ...2 When charging for ambient temperatures above 120 F charge to 10 subcooling It is important to return when outdoor ambient temperature is between 55 F and 120 F to verify system charge per these inst...

Страница 4: ...ash slowly Liquid Line Temperature Must be within range If this sensor is shorted or open This error condition causes an 11 flash on FAULT LED Liquid Line Pressure Must be above 90 psig If the liquid...

Страница 5: ...n LED will be turned ON The CA control will then exit the charge assist cycle and return the control of the system to the Communicating Comfort Control The Status Green LED will be slowly flashing The...

Страница 6: ...TM data Low Pressure Cut Out Fault Open outside of defrost Cycle Short lock out Wait Flashing Flash device count when in communication number of COMM products connected in system Rapid flashes followe...

Страница 7: ...sist Tool BAYCAKT001AA ADD AMBER LED BLINKING CHARGING STABILIZING AMBER LED BLINKING RECOVER RED LED CA procedure allows 1 hour to get within 20 psi of Charged and 50 minutes to move 4 psi Otherwise...

Страница 8: ...0 250 300 350 400 450 500 550 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 40 50 60 70 80 90 100 110 120 130 140 150 160 5 5 15 25...

Страница 9: ...Heating Refrigeration Cycle Cooling Refrigeration Cycle NOTE 1 Line Dampener DO NOT REMOVE LINE DAMPENER SEE NOTE 1 LINE DAMPENER SEE NOTE 1 Printed from D155727P01 Rev03 9 REFRIGERATION CIRCUITS...

Страница 10: ...er up 10 hours max if compressors remain OFF Sump Heat OFF When a compressor is running Sump Heat OFF For 30 minutes after compressor s have stopped running Sump Heat OFF When outdoor temperature goes...

Страница 11: ...Sensors J6 J7 TABLE 3 Temp F Temp C THERMISTOR RESISTANCE OHMS Volts DC at plug J8 Only pin to pin 50 10 0 19405 2 22 55 12 8 17002 2 06 60 15 6 14930 1 90 65 18 3 13138 1 75 70 21 1 11586 1 61 75 23...

Страница 12: ...ng 3 9 Flash Low superheat in Cooling Mode Indoor TXV stuck open or ID Fan failure 10 Flash Not used at this time 3 Monitor superheat and pressure 3 SH for 5 minutes with valve minimum position Monito...

Страница 13: ...n Service Facts EEV Hunting Suction pressure moves up down Sensor are out of calibration 1 Verify sensors are accurate See Table 7 8 in Service Facts Verify temperature sensor is clipped tight to suct...

Страница 14: ...g LPCO may trip Note The Close Valve Test will exit after 1 5 minutes 90 seconds and will not reinitiate requires a break and make to initialize To clear faults stored in memory apply a jumper between...

Страница 15: ...65 0 66 125 51 7 3298 0 60 130 54 4 2972 0 54 135 57 2 2683 0 50 136 57 8 2629 0 49 137 58 3 2576 0 48 138 58 9 2525 0 47 139 59 4 2474 0 46 140 60 0 2425 0 45 141 60 6 2377 0 45 142 61 1 2330 0 44 14...

Страница 16: ...Trane www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice...

Отзывы: