FLASH RATe SuMMARy

SuMMARy OF ALeRT COde & CHARGe ASSIST

TM

 LedS (CONTINued)

      ON

Charge is Correct

1 sec. ON/OFF = 15-20 PSI off target 

3/4 sec. ON/OFF = 10-15 PSI off target

1/2 sec. ON/OFF = 5-10 PSI off target

1/4 sec. ON/OFF = 0-5 PSI off target

1 sec ON/OFF = 6-20 minutes away from a steady operating state.

3/4 sec. ON/OFF = 5-6 minutes away from a steady operating state.

1/2 sec. ON/OFF = 2-4 minutes away from a steady operating state.

1/4 sec. ON/OFF = 1/2 - 2 minutes away from a steady operating state.

Flash 10 times = indicates that Charge Assist™ is not allowed

      ON

Exit Charge Assist™ - need to recover refrigerant

      ON

System requires refrigerant charge (Control has turned on the 24 volt AC output) Use 

Charge Assist™ Tool  (#BAYCAKT001AA)

"ADD" (AMBER LED)

      BLINKING

"CHARGING" (STABILIZING) (AMBER LED)

      BLINKING

"RECOVER" (RED LED)

CA™ procedure allows 1 hour to get within 20 psi of "Charged" and 50 minutes to move 4 psi,                                       

Otherwise Time Out

"CHARGED" LED (GREEN)

 

NOTES:     

 

-

-

-

-

-

-

-

-

-

-

-

-

-

The Comfort Control 

Wait

icon         

will be ON for the following:

Minimum equipment off time (5 min.)

During Low or High Pressure monitor 

"short lockout" (5 min)
During Power-Interrupt protection         

(1 min.)

During Charge Assist™

A working Ambient Temperature Sensor                      

is needed for the following:

Humidifier Dew-Point Control

Compressor Lock Out

Oil Return Mode

LPCO Monitor

Charge Assist (Use Ambient Sensor only)  Do not revert to 

External ODT Sensor if present and Ambient Sensor has failed.

Comfort Control (ODT display)

Aux Heat control during Defrost

Defrost (Heat Pump Models Only) Do not revert to External ODT 

Sensor if present and Ambient Sensor has failed.

Aux Heat Lock Out

Содержание ComfortLink 4TWZ0060A1000A

Страница 1: ...ON WITH ITS USE CAuTION RECONNECT ALL GROUNDING DEVICES ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED IF GROUNDING WIRES SCREWS STRAPS CLIPS NUTS OR WASHERS USED TO C...

Страница 2: ...ms CHARGING METHOD This model has ComfortLink II and Charge Assist features Charge Assist can be used in cooling mode only For complete instructions on using Charge Assist please see page 4 2 Schemati...

Страница 3: ...ambient temperatures 2 When charging for ambient temperatures above 120 F charge to 10 subcooling It is important to return when outdoor ambient temperature is between 55 F and 120 F to verify system...

Страница 4: ...ash slowly Liquid Line Temperature Must be within range If this sensor is shorted or open This error condition causes an 11 flash on FAULT LED Liquid Line Pressure Must be above 90 psig If the liquid...

Страница 5: ...n LED will be turned ON The CA control will then exit the charge assist cycle and return the control of the system to the Communicating Comfort Control The Status Green LED will be slowly flashing The...

Страница 6: ...TM data Low Pressure Cut Out Fault Open outside of defrost Cycle Short lock out Wait Flashing Flash device count when in communication number of COMM products connected in system Rapid flashes followe...

Страница 7: ...sist Tool BAYCAKT001AA ADD AMBER LED BLINKING CHARGING STABILIZING AMBER LED BLINKING RECOVER RED LED CA procedure allows 1 hour to get within 20 psi of Charged and 50 minutes to move 4 psi Otherwise...

Страница 8: ...Z0060A1000AA 200 250 300 350 400 450 500 550 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 40 50 60 70 80 90 100 110 120 130 140 15...

Страница 9: ...Heating Refrigeration Cycle Cooling Refrigeration Cycle Printed from D155711P01 Rev02 9 ReFRIGERATION CIRCUITS...

Страница 10: ...er up 10 hours max if compressors remain OFF Sump Heat OFF When a compressor is running Sump Heat OFF For 30 minutes after compressor s have stopped running Sump Heat OFF When outdoor temperature goes...

Страница 11: ...Sensors J6 J7 TABLE 3 Temp F Temp C THERMISTOR RESISTANCE OHMS Volts DC at plug J8 Only pin to pin 50 10 0 19405 2 22 55 12 8 17002 2 06 60 15 6 14930 1 90 65 18 3 13138 1 75 70 21 1 11586 1 61 75 23...

Страница 12: ...ng 3 9 Flash Low superheat in Cooling Mode Indoor TXV stuck open or ID Fan failure 10 Flash Not used at this time 3 Monitor superheat and pressure 3 SH for 5 minutes with valve minimum position Monito...

Страница 13: ...n Service Facts EEV Hunting Suction pressure moves up down Sensor are out of calibration 1 Verify sensors are accurate See Table 7 8 in Service Facts Verify temperature sensor is clipped tight to suct...

Страница 14: ...ing LPCO may trip Note If jumper is left on pins any faults stored in memory will be cleared after 10 seconds The CLOSE VALVE TEST will clear after 2 minutes and will not reinitiate requires a break a...

Страница 15: ...65 0 66 125 51 7 3298 0 60 130 54 4 2972 0 54 135 57 2 2683 0 50 136 57 8 2629 0 49 137 58 3 2576 0 48 138 58 9 2525 0 47 139 59 4 2474 0 46 140 60 0 2425 0 45 141 60 6 2377 0 45 142 61 1 2330 0 44 14...

Страница 16: ...Trane www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice...

Отзывы: