background image

12

24 VAC at plug J6

Standby

B to R

1st Stage

ON

ON

B to R & Y1

2nd Stage

ON

OFF

ON

ON

ON

B to R, Y1 & Y2

Standby

OFF

OFF

B to R & O

1st Stage

ON

B to R, Y1 & O

2nd Stage

ON

OFF

ON

B to R, Y1, Y2 & O

EEV control

STATUS LED

1 sec

2 sec

3 sec

4 sec

ON Continuous

ON

OFF

OFF

Heat

TABLE 6

Control Input and Status LED - J6

ON

Cool

OFF

OFF

OFF

OFF

eLeCTRONIC exPANSION VALVe (eeV) CONTROL BOARd

LED

Color

EEV 

Fault LED

Description

3 Flash

Suction Pressure Transducer input is out of range

 (Replace transducer) (1)

4 Flash

Suction Temperature Sensor input is out of range

 (Replace sensor) (1)

5 Flash

Coil has short circuit

 (Replace Coil) (2)

6 Flash

Valve is not responding to a position change command

 (Possible stuck valve)

7 Flash

Valve is responding but system is not performing properly

 (Low charge or restriction)

8 Flash

Compressor is not pumping

 (3)

9 Flash

Low superheat in Cooling Mode

 (Indoor TXV stuck open or ID Fan failure)

10 Flash

Not used at this time

(3) Monitor superheat and pressure: <3' SH for 5 minutes with valve @ minimum position, Monitor off-cycle 

pressure and compare to next on-cycle for pressure drop within 60 seconds

Red

(1) Valve will close and LPCO will trip

OFF

1 Flash

Standby
Coil has an open circuit or intermittent short

 (Replace Coil)

(2) Power supply will shut down to protect board

EEV Fault Codes

EEV not used on all models

2 Flash

Control has detected an internal failure

 (Replace EEV control board)

The following may require additional diagnostics

Notes:

Printed from D802247P01 Rev08

Fault LeD (Red)

OPEN

CLOSE

TEST

STATUS LED 
(Green)

Fault LED 
(Red)

Status LeD (green)

On - Control has power

Flashing Fast - Control is driving valve (5 seconds max drive time)

Flashing Pattern - See Table 6.

Fault Storing/Clearing:

Faults 6-9 will be stored in non-volatile memory.  See Close Valve Test for fault clearing procedure.  

Faults 1-5 will clear with a power cycle.

Содержание ComfortLink 4TWZ0060A1000A

Страница 1: ...ON WITH ITS USE CAuTION RECONNECT ALL GROUNDING DEVICES ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED IF GROUNDING WIRES SCREWS STRAPS CLIPS NUTS OR WASHERS USED TO C...

Страница 2: ...ms CHARGING METHOD This model has ComfortLink II and Charge Assist features Charge Assist can be used in cooling mode only For complete instructions on using Charge Assist please see page 4 2 Schemati...

Страница 3: ...ambient temperatures 2 When charging for ambient temperatures above 120 F charge to 10 subcooling It is important to return when outdoor ambient temperature is between 55 F and 120 F to verify system...

Страница 4: ...ash slowly Liquid Line Temperature Must be within range If this sensor is shorted or open This error condition causes an 11 flash on FAULT LED Liquid Line Pressure Must be above 90 psig If the liquid...

Страница 5: ...n LED will be turned ON The CA control will then exit the charge assist cycle and return the control of the system to the Communicating Comfort Control The Status Green LED will be slowly flashing The...

Страница 6: ...TM data Low Pressure Cut Out Fault Open outside of defrost Cycle Short lock out Wait Flashing Flash device count when in communication number of COMM products connected in system Rapid flashes followe...

Страница 7: ...sist Tool BAYCAKT001AA ADD AMBER LED BLINKING CHARGING STABILIZING AMBER LED BLINKING RECOVER RED LED CA procedure allows 1 hour to get within 20 psi of Charged and 50 minutes to move 4 psi Otherwise...

Страница 8: ...Z0060A1000AA 200 250 300 350 400 450 500 550 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 40 50 60 70 80 90 100 110 120 130 140 15...

Страница 9: ...Heating Refrigeration Cycle Cooling Refrigeration Cycle Printed from D155711P01 Rev02 9 ReFRIGERATION CIRCUITS...

Страница 10: ...er up 10 hours max if compressors remain OFF Sump Heat OFF When a compressor is running Sump Heat OFF For 30 minutes after compressor s have stopped running Sump Heat OFF When outdoor temperature goes...

Страница 11: ...Sensors J6 J7 TABLE 3 Temp F Temp C THERMISTOR RESISTANCE OHMS Volts DC at plug J8 Only pin to pin 50 10 0 19405 2 22 55 12 8 17002 2 06 60 15 6 14930 1 90 65 18 3 13138 1 75 70 21 1 11586 1 61 75 23...

Страница 12: ...ng 3 9 Flash Low superheat in Cooling Mode Indoor TXV stuck open or ID Fan failure 10 Flash Not used at this time 3 Monitor superheat and pressure 3 SH for 5 minutes with valve minimum position Monito...

Страница 13: ...n Service Facts EEV Hunting Suction pressure moves up down Sensor are out of calibration 1 Verify sensors are accurate See Table 7 8 in Service Facts Verify temperature sensor is clipped tight to suct...

Страница 14: ...ing LPCO may trip Note If jumper is left on pins any faults stored in memory will be cleared after 10 seconds The CLOSE VALVE TEST will clear after 2 minutes and will not reinitiate requires a break a...

Страница 15: ...65 0 66 125 51 7 3298 0 60 130 54 4 2972 0 54 135 57 2 2683 0 50 136 57 8 2629 0 49 137 58 3 2576 0 48 138 58 9 2525 0 47 139 59 4 2474 0 46 140 60 0 2425 0 45 141 60 6 2377 0 45 142 61 1 2330 0 44 14...

Страница 16: ...Trane www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice...

Отзывы: