4TWZ0060-SF-1B

ComfortLink

 II System

Heat Pump

4TWZ0060A1000A

4TWZ0060A1000A

200/230/1/60

31

50

50

CLIMATUFF

®

2 - 1

200/230/1/60

23.4 - 128.7

YES

YES

YES

PROPELLER

26.6 - 1

DIRECT - 2

4630/3330 

1 - 1/3

971/652

200/230/1/60

2.80

SPINE FIN™

2 - 24

29.15

3/8

EEV

R-410A

15 LBS.- 13 OZ.

YES

3/4

3/8

See Charging Chart (page 3)

H  X  W  X  D

57.4 X 35.1 X 38.7

480

430

20’

30’

40’

50’

60’

70’

80’

3/4”

3/4”

3/4”

3/4”

3/4”

3/4”

3/4”

3/8”

3/8”

3/8”

3/8”

3/8”

3/8”

3/8”

3 oz.

9 oz.

15 oz.

21 oz.

27 oz.

32 oz.

38 oz.

© 2009 Trane

IMPORTANT — This document contains a wiring diagram, a parts list, and service information. This is customer prop-

erty and is to remain with this unit. Please return to service information pack upon completion of work.

PROduCT SPeCIFICATIONS

 OuTdOOR uNIT 

12 

 

POWeR CONNS.

 — V/PH/HZ 

3

 MIN. BRCH. CIR. AMPACITY

 BR. CIR. 

MAX. (AMPS)

 PROT. RTG. 

}

  MIN. (AMPS)

 

COMPReSSOR

 NO. USED - NO. SPEEDS

 VOLTS/PH/HZ

 R.L. AMPS 

7

 - L.R. AMPS

 FACTORY INSTALLED

  START COMPONENTS 

8

  INSULATION/SOUND BLANKET

  COMPRESSOR HEAT
 

OuTdOOR FAN

 DIA. (IN.) - NO. USED

 TYPE DRIVE - NO. SPEEDS

 CFM @ 0.0 IN. W.G. 

(HIGH/LOW)

 NO. MOTORS - HP

 MOTOR R.P.M. (HIGH/LOW)

 VOLTS/PH/HZ

 F.L. AMPS
 

OuTdOOR COIL

 — TYPE

 ROWS - F.P.I.

 FACE AREA (SQ. FT.)

 TUBE SIZE (IN.)

 REFRIGERANT CONTROL
 

ReFRIGeRANT

 LBS. — R-410A (O.D. UNIT) 

5

 FACTORY SUPPLIED

 LINE SIZE - IN. O.D. GAS 

6

 LINE SIZE - IN. O.D. LIQ. 

6

 

CHARGING SPeCIFICATION

 

 SUBCOOLING
 

dIMeNSIONS

 CRATED (IN.)
 

WeIGHT

 SHIPPING (LBS.)

 NET (LBS.)

Service Facts

NOTICe: 

The manufacturer has a policy of continuous product and product data  improvement 
and reserves the right to change design and specifications without notice.

WARNING

!

THIS INFORMATION IS INTENDED FOR USE BY INDIVIDUALS POS SES-

S ING  ADEQUATE  BACKGROUNDS  OF  ELECTRICAL  AND  MECHANICAL 

 EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITION-

ING PRODUCT MAY RESULT IN PERSONAL INJURY AND OR  PROPERTY 

DAMAGE.  THE  MANUFACTURER  OR  SELLER  CANNOT  BE  RESPON-

SIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT 

 ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.

CAuTION

!

RECONNECT ALL GROUNDING DEVICES.

ALL  PARTS  OF  THIS  PRODUCT  CAPABLE  OF  CONDUCTING 

ELECTRICAL  CURRENT  ARE  GROUNDED.  IF  GROUNDING  WIRES, 

SCREWS, STRAPS, CLIPS, NUTS OR WASHERS USED TO COMPLETE 

A  PATH  TO  GROUND  ARE  REMOVED  FOR  SERVICE,  THEY  MUST 

BE  RETURNED  TO  THEIR   ORIGINAL  POSITION  AND  PROPERLY 

FASTENED.

WARNING:

 

HAZARdOuS VOLTAGe - dISCONNeCT POWeR and dISCHARGe 

  

CAPACITORS BeFORe SeRVICING

CAuTION

!

uNIT CONTAINS R-410A ReFRIGeRANT!

R-410A OPERATING PRESSURE EXCEEDS THE 
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS 
REQUIRED. FAILURE TO USE PROPER SERVICE 
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR 
PERSONAL INJURY.

SeRVICe

USE ONLY R-410A REFRIGERANT AND

APPROVED POE/AB COMPRESSOR OIL.

TuBING INFORMATION

 

Tubing Sizes 

Tubing 

Additional

 

Suction 

Liquid 

Length 

Refrigerant

 

Tubing lengths in excess of eighty (80) feet see application software.

02/09

1

  Certified in accordance with the Air-Source Unitary Air-conditioner Equipment certi-

fication program, which is based on ARI standard 210/240.  In order to achieve ARI 

standard rating, the indoor fan time delay on the comfort control must be enabled.

2

  Rated in accordance with ARI standard 270.

3

  Calculated in accordance with Natl. Elec. Codes. Use only HACR circuit breakers or 

fuses.

4

  Standard Air — Dry Coil — Outdoor

5

  This value approximate. For more precise value see unit nameplate.

6

  Max. linear length 80 ft.; Max. lift - Suction 25 ft.; Max lift - Liquid 25 ft.  

For greater length consult refrigerant piping software Pub. No. 32-3312-0*  

(* denotes latest revision).

7

  This value shown for compressor RLA on the unit nameplate and on this specification 

sheet is used to compute minimum branch circuit ampacity and max. fuse size. The 

value shown is the branch circuit selection current.

8

  NO means no start components. YES means quick start kit components. PTC means 

positive temperature coefficient starter.

CONTAINS ReFRIGeRANT!

SySTeM CONTAINS OIL ANd ReFRIGeRANT uNdeR 

HIGH PReSSuRe. ReCOVeR ReFRIGeRANT TO ReLIeVe 

PReSSuRe BeFORe OPeNING SySTeM.
Failure to follow proper procedures can result in personal

illness or injury or severe equipment damage.

CAuTION

!

Содержание ComfortLink 4TWZ0060A1000A

Страница 1: ...ON WITH ITS USE CAuTION RECONNECT ALL GROUNDING DEVICES ALL PARTS OF THIS PRODUCT CAPABLE OF CONDUCTING ELECTRICAL CURRENT ARE GROUNDED IF GROUNDING WIRES SCREWS STRAPS CLIPS NUTS OR WASHERS USED TO C...

Страница 2: ...ms CHARGING METHOD This model has ComfortLink II and Charge Assist features Charge Assist can be used in cooling mode only For complete instructions on using Charge Assist please see page 4 2 Schemati...

Страница 3: ...ambient temperatures 2 When charging for ambient temperatures above 120 F charge to 10 subcooling It is important to return when outdoor ambient temperature is between 55 F and 120 F to verify system...

Страница 4: ...ash slowly Liquid Line Temperature Must be within range If this sensor is shorted or open This error condition causes an 11 flash on FAULT LED Liquid Line Pressure Must be above 90 psig If the liquid...

Страница 5: ...n LED will be turned ON The CA control will then exit the charge assist cycle and return the control of the system to the Communicating Comfort Control The Status Green LED will be slowly flashing The...

Страница 6: ...TM data Low Pressure Cut Out Fault Open outside of defrost Cycle Short lock out Wait Flashing Flash device count when in communication number of COMM products connected in system Rapid flashes followe...

Страница 7: ...sist Tool BAYCAKT001AA ADD AMBER LED BLINKING CHARGING STABILIZING AMBER LED BLINKING RECOVER RED LED CA procedure allows 1 hour to get within 20 psi of Charged and 50 minutes to move 4 psi Otherwise...

Страница 8: ...Z0060A1000AA 200 250 300 350 400 450 500 550 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 115 125 135 145 155 165 175 185 40 60 80 100 120 40 50 60 70 80 90 100 110 120 130 140 15...

Страница 9: ...Heating Refrigeration Cycle Cooling Refrigeration Cycle Printed from D155711P01 Rev02 9 ReFRIGERATION CIRCUITS...

Страница 10: ...er up 10 hours max if compressors remain OFF Sump Heat OFF When a compressor is running Sump Heat OFF For 30 minutes after compressor s have stopped running Sump Heat OFF When outdoor temperature goes...

Страница 11: ...Sensors J6 J7 TABLE 3 Temp F Temp C THERMISTOR RESISTANCE OHMS Volts DC at plug J8 Only pin to pin 50 10 0 19405 2 22 55 12 8 17002 2 06 60 15 6 14930 1 90 65 18 3 13138 1 75 70 21 1 11586 1 61 75 23...

Страница 12: ...ng 3 9 Flash Low superheat in Cooling Mode Indoor TXV stuck open or ID Fan failure 10 Flash Not used at this time 3 Monitor superheat and pressure 3 SH for 5 minutes with valve minimum position Monito...

Страница 13: ...n Service Facts EEV Hunting Suction pressure moves up down Sensor are out of calibration 1 Verify sensors are accurate See Table 7 8 in Service Facts Verify temperature sensor is clipped tight to suct...

Страница 14: ...ing LPCO may trip Note If jumper is left on pins any faults stored in memory will be cleared after 10 seconds The CLOSE VALVE TEST will clear after 2 minutes and will not reinitiate requires a break a...

Страница 15: ...65 0 66 125 51 7 3298 0 60 130 54 4 2972 0 54 135 57 2 2683 0 50 136 57 8 2629 0 49 137 58 3 2576 0 48 138 58 9 2525 0 47 139 59 4 2474 0 46 140 60 0 2425 0 45 141 60 6 2377 0 45 142 61 1 2330 0 44 14...

Страница 16: ...Trane www trane com Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice...

Отзывы: