Wiring Inputs and Outputs
Wiring 0–20 mA Analog Inputs
Connect any 0–20 mA analog input to sensors such as humidity sensors and pressure sensors.
1.
Connect the shield to a common terminal at the terminal board and tape it back at the input
device.
Note:
Do Not use the shield as the common connection. For 3-wire applications, use a 3-
conductor cable with shield and for 2-wire applications, use a 2-conductor cable with
separate shield.
2. Connect the signal wire to an available input terminal.
3. Connect the supply wire to a 24 VDC or 24 VAC terminal as required.
4. Use the Tracer TU service tool to configure the analog input that references the corresponding
hardware termination.
Figure 12. Typical wiring, 0–20 mA
1
IMC
UI
8
UI
7
UI
6
UI
5
UI
4
UI
3
UI
2
UI
1
OUT
+24
VDC
+24
VDC
OUT
24
VAC
MBUS
OUT
24
VAC
XFMR
24
VAC
OUT
IMC
IMC
+24
VDC
LINK
OUT
+24
VDC
+24
VDC
AO
6
UI
14
AO
5
UI
13
AO
4
UI
12
AO
3
UI
11
AO
2
UI
10
AO1
UI
9
ADDRESS
0 1
2
3
4
56
7
8
9
x1
0 1
2
3
4
56
7
8
9
x10
0 1
2
3
4
56
7
8
9
x100
UI
8
UI
7
UI
6
0-20 mA out
0-20 mA out
Common
24 VDC
24 VDC
Tape shield back
2-wire
3-wire
3-wire
Tape shield back
2-wire
0-20 mA out
24 VDC
Common
24 VDC
0-20 mA out
Top tier wiring: connect to any
UI input
Bottom tier wiring: connect to any
AO/UI input. Connect 24 VDC wire
to available 24 VDC on top tier.