Installation

4. Remove the cover from the Wireless Receiver by firmly pressing the thumb tab at the bottom 

of the cover and pulling the cover away from the back plate.

5. Arrange the receiver back plate on the mounting bracket so that the release thumb tab is at the 

top of the bracket. See

 

Figure 1

 

Figure 5

.

6. Using two #6-32 x ½" screws, mount the Receiver back plate to the bracket.
7. Connect the included Wire Harness to the receiver J1. Route the Wire Harness through the 

opening in the Receiver back plate and bracket toward the RTRM.

8. Connect the stripped ends of the Wire Harness to the ReliaTel RTRM board header J6 as 

described in 

Table 1

.

Table 1.

Wire (Label)

RTRM J6 
Termination

ZONE

J6-1

GND-SIGNAL

J6-2

SETPOINT

J6-3

FAN/SYSTEM

J6-4

HEAT SETPOINT

J6-5

24 VAC/DC

J6-14

GND-POWER

J6-6

9. Check all connections. Once connections are verified correct, reapply power to the unit and 

UCM.

10. Refer to the Wireless Sensor Installation, Operation, and Maintenance (BAS-SVX04*-EN) 

document to associate the receiver with the Wireless Display Sensor.

11. Once the Wireless Display Sensor and Receiver are setup and communicating properly, make 

sure all excess wire from the Harness goes through the bracket.

12. Once the wire harness is routed out of the way, replace the Wireless Receiver front cover over 

the back plate. Line up the thumb tab and apply light pressure until the cover snaps back in 
place. 

13. Install a security retaining screw in the top of the receiver through the thumb tab. See 

Figure 2

.

Содержание BAYSENS050m

Страница 1: ... equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that a...

Страница 2: ...d personnel Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards To avoid these hazards you MUST follow requirements for field wiring installation and grounding as described in NEC and your local state electrical codes Failure to follow code could result in death or serious injury WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capaci...

Страница 3: ...irements for arc flash protection PRIOR to servicing the unit NEVER PERFORM ANY SWITCHING DISCONNECTING OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE WARNING Follow EHS Policies Failure to follow instructions below could result in death or serious injury All Trane personnel must follow the comp...

Страница 4: ...troduction InstallationKit The installation kit includes the following Wireless Receiver Wireless Zone Sensor Wire Harness Mounting Bracket Two 8 32 x Pan Head Screws Two 6 32 x Pan Head Screws Two 10 32 x Pan Head Screws ...

Страница 5: ...t holes in the right hand back corner of the control box floor Use the two 8 32 x 1 2 screws to mount the bracket to the Odyssey control box See Figure 3 10 12 ton split system units If the control box does not have pre drilled holes to mount the bracket using a 29 drill Diameter 0 136 hole drill two engagement holes in the front edge of the control box floor Use the two 8 32 x 1 2 screws to mount...

Страница 6: ...Figure 2 3 10 Ton Packaged Rooftop Units Figure 3 6 7 Ton Split System Units 6 ACC SVN129D EN Installation ...

Страница 7: ...Figure 4 10 12 Ton Split System Units Figure 5 15 25 Ton Split System Units ACC SVN129D EN 7 Installation ...

Страница 8: ...Table 1 Table 1 Wire Label RTRM J6 Termination ZONE J6 1 GND SIGNAL J6 2 SETPOINT J6 3 FAN SYSTEM J6 4 HEAT SETPOINT J6 5 24 VAC DC J6 14 GND POWER J6 6 9 Check all connections Once connections are verified correct reapply power to the unit and UCM 10 Refer to the Wireless Sensor Installation Operation and Maintenance BAS SVX04 EN document to associate the receiver with the Wireless Display Sensor...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...cations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and residential applications For more information please visit trane com or americanstandardair com ACC SVN129D EN 05 Jun 2020 Supersedes ACC SVN129C EN Jan 2015 ...

Отзывы: