SYSTEM CHECK-OUT – HEAT PUMP

Verify that the kit is installed and wired per the instruc-

tions contained within this installer’s guide.  (J5-Blue 

connected to “B”, J5-Yellow connected to “Y”, J5-

Orange connected to “O”, Liquid sensor installed and 

connected, Ambient sensor installed and connected).
If uncertain about dip switch settings (S2-1, 2, 3, 4), 

leave in the factory preset position.
Apply power to the unit.  Apply “Y” and “O” control sig-

nal.

Verify­the­green­LED­is­flashing­at­1/2­second­ON­1/2­

second OFF rate.
Verify no red LED faults are present.
The fan should run continuously for a minimum of 

10 seconds after “Y” and “O” have been applied.  After 

10 seconds the control may begin to cycle the fan if the 

ambient outdoor temperature is 70 deg. or below.  If the 

fan is cycling and the outdoor temperature is below 70 

deg., the control is working.  If after 10 seconds of “Y” 

application the fan is on continuously, the TEST Switch 

(S1) may be used to verify the Control Module has con-

trol over the fan.  Momentarily depress the TEST Switch 

(S1) on the Control board.  The fan should then cycle 3 

seconds­on­then­3­seconds­off­for­12­seconds.

NOTE: 

If the green LED is full on with a blink/flicker OFF 

every second make certain the orange wire from the 

control board is connected to “O” per these instruc-

tions and the “O” signal is present.

The control board will leave the fan ON continuously 

during heating mode, i.e., No “O” signal present.  The 

green­LED­is­full­on­with­a­blink/flicker­off­every­second­

in the heating mode.

About Trane and American Standard Heating and Air Conditioning

Trane and American Standard create comfortable, energy efficient indoor environments for residential applications.

For more information, please visit www.trane.com or www.americanstandardair.com

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications with-

out notice. We are committed to using environmentally conscious print practices.

© 2020

18-HE46D1-3B-EN   08 Jul 2020  
Supersedes 18-HE46D1-3   (July 2004)

Содержание BAYLOAM103

Страница 1: ...nce and replaced with autho rized parts only INSTALLATION NOTE As the head pressure control is applied to units op erating in low ambient conditions it is required that the units have compressor crank...

Страница 2: ...he insulation tape b If installing on a heat pump unit attach the liquid line sensor to the liquid line running vertically directly behind the control box Apply thermal grease supplied to the liquid l...

Страница 3: ...motor lead to the black wire from the solid state relay on the control module This wire has a sleeved 1 4 male tab for attaching to the fan motor wire terminal Connect the other black wire from the so...

Страница 4: ...the N C terminal on the defrost board relay from where the fan motor was disconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease t...

Страница 5: ...sconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease the insertion of the connector housing onto the J5 header place the connector...

Страница 6: ...termin ing the liquid temperature set point the same as in Manual Mode If the controller has acquired an ap proach temperature then the liquid temperature set point is determined as follows Liquid Tem...

Страница 7: ...off accordingly SYSTEM CHECK OUT COOLING UNITS ONLY Verify that the control module is installed and wired per the instructions contained within this installer s guide J5 Blue connected to B J5 Yellow...

Страница 8: ...Switch S1 may be used to verify the Control Module has con trol over the fan Momentarily depress the TEST Switch S1 on the Control board The fan should then cycle 3 seconds on then 3 seconds off for...

Отзывы: