background image

 18-HE46D1-3B-EN

Installer’s Guide

SYSTEM SETUP

 10. The control board contains a momentary test switch 

(S1) and a 4-position installer selectable dip switch 

(S2). Both components are located in the lower right 

hand corner of the control board. See Figure 8.

TEST SWITCH

The test switch provides a means of verifying that 

the fan motor is under the control of the Low Ambient 

Controller. A “Y” signal must be present in order to test 

the control. Depressing the test switch causes the fan 

to­alternately­cycle­on­(for­3­seconds)­and­off­(for­3­

seconds)­for­a­total­time­of­12­seconds.­The­on/off­fan­

operation may be observed by watching the fan once 

the test function has been invoked or by monitoring the 

head pressure using a gauge set. The LED on the solid 

state relay should light when voltage is being applied to 

the fan motor. Once the 12-second test period is com-

plete the control resumes normal control operation.

DIP SWITCHES

The controller will control to a liquid temperature set 

point as determined by the dip switch settings.  The dip 

switch is used:
  1. To select either Automatic Mode or Manual Mode 

operation (S2 dip switch 4 setting).

  2. To select the liquid temperature set point (S2 dip 

switch 1, 2 and 3 settings).

  

Automatic Mode

­(S2­dip­switch­4­in­“Off”­position)­

– The controller determines the 

approach tempera-

ture

 based upon the liquid and ambient tempera-

ture readings.  The 

approach temperature

 = liquid 

temperature – ambient temperature.  The approach 

temperature is calculated only when the ambient 

temperature is in the range of 65 to 75 deg. F. and 

the outdoor fan is on continuously.  If the controller 

has not yet acquired an approach temperature, S2 

dip switch 1, 2 & 3 settings are used for determin-

ing the liquid temperature set point the same as in 

Manual Mode.  If the controller has acquired an 

ap-

proach temperature

, then the liquid temperature set 

point is determined as follows:

    Liquid Temperature Set Point = 

 

 

Approach Temperature

 + 70 deg. F.

  

Manual Mode 

(S2 dip switch 4 in “On” position) –  

The S2 dip switch 1, 2, 3 settings are read by the 

 controller and used to determine the liquid tempera-

ture set point when

­

1.­Y­is­first­applied

 

2. and after initial start-up mode completion, i.e., 

during the system control mode (no sooner than 

six minutes after Y is applied).  The liquid tem-

perature set point will not change during system 

start-up.

    The dip switches should be set prior to initial appli-

cation of the Y signal to the controller.

­ ­ The­dip­switches­should­be­set­for­each­specific­

HVAC system based upon the following instructions:

    Determine Liquid Temperature Set Point

    Reference appropriate high side charging chart for 

the unit; liquid pressure for cooling units and head 

pressure for heat pump units.

    Locate the high side pressure for 70 deg. F. out-

door temperature at the expected indoor wet bulb 

temperature. Correct the high side pressure accord-

ing­to­the­specific­indoor­unit­being­used.­For­Heat­

pumps subtract 7 psi, for cooling only units subtract 

zero­psi.­Using­the­refrigerant­properties­chart,­find­

the saturation temperature for the calculated liq-

uid pressure. Subtract the anticipated sub-cooling 

temperature (typically 12 degrees) from the satura-

tion temperature to obtain an estimate of the liquid 

temperature. Set S2 dip switch 1, 2 and 3 settings to 

the nearest liquid temperature set point in the table 

below.

    S2 Dip Switch

 

4;  

Off­–­Automatic­Mode

 

 

(recommended setting)

     

On – Manual Mode

LIQUID TEMP

SET POINT°F

DIP 

SWITCH 1

DIP 

SWITCH 2

DIP 

SWITCH 3

70 °F

OFF

OFF

OFF

76 °F

OFF

OFF

ON

82 °F

OFF

ON

OFF

88 °F

OFF

ON

ON

94 °F

ON

OFF

OFF

100 °F

ON

OFF

ON

106 °F

ON

ON

OFF

112 °F

ON

ON

ON

Содержание BAYLOAM103

Страница 1: ...nce and replaced with autho rized parts only INSTALLATION NOTE As the head pressure control is applied to units op erating in low ambient conditions it is required that the units have compressor crank...

Страница 2: ...he insulation tape b If installing on a heat pump unit attach the liquid line sensor to the liquid line running vertically directly behind the control box Apply thermal grease supplied to the liquid l...

Страница 3: ...motor lead to the black wire from the solid state relay on the control module This wire has a sleeved 1 4 male tab for attaching to the fan motor wire terminal Connect the other black wire from the so...

Страница 4: ...the N C terminal on the defrost board relay from where the fan motor was disconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease t...

Страница 5: ...sconnected Low voltage wires Connect the 3 pin wire assembly to J5 on the con trol board 3 pin male connector NOTE To ease the insertion of the connector housing onto the J5 header place the connector...

Страница 6: ...termin ing the liquid temperature set point the same as in Manual Mode If the controller has acquired an ap proach temperature then the liquid temperature set point is determined as follows Liquid Tem...

Страница 7: ...off accordingly SYSTEM CHECK OUT COOLING UNITS ONLY Verify that the control module is installed and wired per the instructions contained within this installer s guide J5 Blue connected to B J5 Yellow...

Страница 8: ...Switch S1 may be used to verify the Control Module has con trol over the fan Momentarily depress the TEST Switch S1 on the Control board The fan should then cycle 3 seconds on then 3 seconds off for...

Отзывы: