ACC-SVN67D-EN
15
Electrical Data
480 Volts Three Phase
6
TSC072E4
BAYHTRS409*
9.0
1
18.2
25
18.8
25
6
TSC072E4
BAYHTRS418*
18.0
1
30.3
35
31.0
35
6
TSC072E4
BAYHTRS427*
27.0
2
43.8
45
44.5
45
6
TSC072E4
BAYHTRS436*
36.0
2
57.3
60
58.0
60
7½
TSC090E4
BAYHTRW409*
9.0
1
19.5
30
22.4
35
7½
TSC090E4
BAYHTRW418*
18.0
1
29.3
30
32.9
35
7½
TSC090E4
BAYHTRW427*
27.0
2
42.8
45
46.4
50
7½
TSC090E4
BAYHTRW436*
36.0
2
56.3
60
59.9
60
7½
(
2
)
TSC092E4
BAYHTRT409*
9.0
1
21.5
25
23.0
30
7½
(
2
)
TSC092E4
BAYHTRT418*
18.0
1
31.0
35
32.9
35
7½
(
2
)
TSC092E4
BAYHTRT427*
27.0
2
44.5
45
46.4
50
7½
(
2
)
TSC092E4
BAYHTRT436*
36.0
2
58.0
60
59.9
60
8½
TSC102E4
BAYHTRT409*
9.0
1
21.9
25
23.4
30
8½
TSC102E4
BAYHTRT418*
18.0
1
31.0
35
32.9
35
8½
TSC102E4
BAYHTRT427*
27.0
2
44.5
45
46.4
50
8½
TSC102E4
BAYHTRT436*
36.0
2
58.0
60
59.9
60
10
TSC120E4
BAYHTRA418*
18.0
1
32.5
35
—
—
10
TSC120E4
BAYHTRA427*
27.0
2
46.0
50
—
—
10
TSC120E4
BAYHTRA436*
36.0
2
59.5
60
—
—
10
TSC120E4
BAYHTRA454*
54.0
2
70.4
80
—
—
575 Volts Three Phase
6
TSC072EW
BAYHTRSW09*
9.0
1
13.0
20
14.0
20
6
TSC072EW
BAYHTRSW18*
18.0
1
23.8
25
24.8
25
6
TSC072EW
BAYHTRSW27*
27.0
2
34.6
35
35.6
40
6
TSC072EW
BAYHTRSW36*
36.0
2
45.4
50
46.4
50
7½
TSC090EW
BAYHTRWW18*
18.0
1
23.4
25
7½
TSC090EW
BAYHTRWW27*
27.0
2
34.3
35
7½
TSC090EW
BAYHTRWW36*
36.0
2
45.0
45
7½
(2)
TSC092EW
BAYHTRTW18*
18.0
1
24.8
25
26.3
30
7½
(2)
TSC092EW
BAYHTRTW27*
27.0
2
35.6
40
37.1
40
7½
(2)
TSC092EW
BAYHTRTW36*
36.0
2
46.4
50
47.9
50
8½
TSC102EW
BAYHTRTW18*
18.0
1
24.8
25
26.3
30
8½
TSC102EW
BAYHTRTW27*
27.0
2
35.6
40
37.1
40
8½
TSC102EW
BAYHTRTW36*
36.0
2
46.4
50
47.9
50
10
TSC120EW
BAYHTRAW18*
18.0
1
27.0
30
—
—
10
TSC120EW
BAYHTRAW36*
36.0
2
48.6
50
—
—
10
TSC120EW
BAYHTRAW54*
54.0
2
57.4
60
—
—
(1) No optional motors available for 3-5 tons. The standard motor for 1-phase models is a Multispeed, Direct Drive Motor. The Standard Motor for the 3-
phase models is a Belt Drive Motor.
(2) Dual refrigeration system.
Table 4.
Unit wiring with electric heat (single point connection) - standard efficiency (continued)
Standard Indoor Motor
Oversized Indoor Motor
Tons
Unit Model
Number
Heater Model
Number
Heater kW
Rating
(1)
Control
Stages
MCA
Max Fuse Size or
Max Circuit
Breaker
MCA
Max Fuse Size or
Max Circuit
Breaker