92
WSHP-SVX01E-EN
WARNING
Hazardous Service
Procedures!
The maintenance and trouble
shooting procedures recommended
in this section of the manual could
result in exposure to electrical,
mechanical or other potential safety
hazards. Always refer to the safety
warnings provided throughout this
manual concerning these
procedures. When possible,
disconnect all electrical power
including remote disconnects before
servicing.
Follow proper lockout/tagout
procedures to ensure the power can
not be inadvertently energized.
When necessary to work with live
electrical components, have a
qualified licensed electrician or other
individual who has been trained in
handling live electrical components
per these tasks. Failure to follow all
of the recommended safety
warnings provided, could result in
death or serious injury.
Deluxe Controls
Troubleshooting units which contain
the deluxe control option may be
made easy by using the three LEDs
(light emitting diodes). These LEDs
are provided for indicating the
operating mode of the controller.
The LEDs are intended to aid in
troubleshooting maintenance. The
LEDs are labeled on the circuit board
with numbers as referenced in
Table 8
.
Table 8.
Diagnostic LEDs
Color: Green Color: Red
Controller
Mode
LED1
LED2
LED3
OFF
OFF
OFF
Control OFF
ON
OFF
OFF
Normal/Compressor OFF
ON
OFF
FLASH
Anti-short cycle
ON
OFF
ON
Normal/Compressor ON
FLASH
ON
OFF
Brownout Condition
ON
FLASH
ON
Soft Lockout (low pressure)
ON
FLASH
FLASH
Soft Lockout (high pressure)
ON
ON
ON
Manual Lockout (low pressure)
ON
ON
FLASH
Manual Lockout (high pressure)
ON
FLASH
OFF
Manual Lockout (condensate overflow)
ON
ON
OFF
Compressor Disable
Troubleshooting
Содержание Axiom GEHB 006
Страница 25: ...WSHP SVX01E EN 25 Dimensions Figure 22 GEH 150 180 60Hz GEH 120 150 50Hz GEH right return left supply...
Страница 26: ...26 WSHP SVX01E EN Dimensions Figure 23 GEH 150 180 60Hz GEH 120 150 50Hz GEH right return back supply...
Страница 27: ...WSHP SVX01E EN 27 Dimensions Figure 24 GEH 150 180 60Hz GEH 120 150 50Hz GEH left return right supply...
Страница 28: ...28 WSHP SVX01E EN Dimensions Figure 25 GEH 150 180 60Hz GEH 120 150 50Hz GEH left return back supply...
Страница 33: ...WSHP SVX01E EN 33 Dimensions Figure 30 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz front return back supply...
Страница 34: ...34 WSHP SVX01E EN Dimensions Figure 31 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz back return front supply...
Страница 35: ...WSHP SVX01E EN 35 Dimensions Figure 32 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz front return top supply...
Страница 36: ...36 WSHP SVX01E EN Dimensions Figure 33 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz back return top supply...
Страница 88: ...88 WSHP SVX01E EN Figure 1 Basic 208 V 60 Hz 1Ph Wiring...
Страница 89: ...WSHP SVX01E EN 89 Wiring Figure 2 Deluxe 380 420 V 50 Hz 3 Ph...
Страница 90: ...90 WSHP SVX01E EN Wiring Figure 3 ZN510 208 V 60 Hz 1 Ph...
Страница 91: ...WSHP SVX01E EN 91 Wiring Figure 4 ZN524 460 V 60 Hz 3 Ph...
Страница 95: ......