Dimensions
GEV 1/2 through 5 Ton
Clearance Dimensions
Access to the unit for service
purposes should be provided at
installation. All configurations
require an 24" (610 mm) surround
clearance from other mechanical and
electrical equipment (where shown)
to enable panel removal from the
unit for service/maintenance ability.
Some local codes require a greater
service clearance than listed below.
Check all code requirements prior to
unit installations. Units in a free
return application will require more
than a 1" (25.4) clearance to provide
proper air flow to the units air-to-
refrigerant coil.
GEV 6 through 10 Ton
Clearance Dimensions
Minimum access for service
clearances are provided below. Any
one unit side other than the control
panel or return-air side may be
placed against a wall. The unit may
be serviced through the three
remaining open sides. Some local
codes require a greater service
clearance than listed below. Check all
code requirements prior to unit
installations.
GEV 12 1/2 through 25
Ton Clearance
Dimensions
The diagram below outlines the
minimum required unit service
clearances. Any one unit side other
than the control panel or return-air
side may be placed against a wall.
The unit may be serviced through the
three remaining open sides. Some
local codes require a greater service
clearance than listed below. Check all
code requirements prior to unit
installations.
Figure 5.
GEV 1/2 through 5 ton clearance
Figure 6.
GEH 6 through 15 ton clearance
Figure 7.
GEV 12 1/2 through 25 ton clearance
1"
(25.4)
24"
(61
0)
1"
(25.4)
24"
(610)
UNIT FRONT
RI
G
HT RETURN
TOP/BACK SUPPLY
1"
(25.4)
24"
(61
0)
1"
(25.4)
24"
(610)
UNIT FRONT
LEFT RETURN
TOP/BACK SUPPLY
ACCESS PANEL FOR
SHEAVES AND BELTS
20"
(508)
SERVICE
CLEARANCE
FRONT RETURN
TOP SUPPLY
36"
(
9
14)
SERVICE
CLEARANCE
CONTROL BOX
UNIT FRONT
NEC RE
Q
.
MIN. 36" (
9
14)
C.B. TO WALL
CLEARANCE
16" (406) TO
FILTER FRAME
FOR RETURN-AIR
18" (457)
MIN. SERVICE
CLEARANCE FOR
EITHER LEFT
OR RIGHT SIDE
IS 18" (457). FOR
FAN SHAFT REMOVAL,
A 22" (55
9
) CLEARANCE
MUST BE PROVIDED
ON EITHER THE
LEFT OR RIGHT SIDE.
FRONT RETURN-AIR
BACK SUPPLY-AIR
Содержание Axiom GEHB 006
Страница 25: ...WSHP SVX01E EN 25 Dimensions Figure 22 GEH 150 180 60Hz GEH 120 150 50Hz GEH right return left supply...
Страница 26: ...26 WSHP SVX01E EN Dimensions Figure 23 GEH 150 180 60Hz GEH 120 150 50Hz GEH right return back supply...
Страница 27: ...WSHP SVX01E EN 27 Dimensions Figure 24 GEH 150 180 60Hz GEH 120 150 50Hz GEH left return right supply...
Страница 28: ...28 WSHP SVX01E EN Dimensions Figure 25 GEH 150 180 60Hz GEH 120 150 50Hz GEH left return back supply...
Страница 33: ...WSHP SVX01E EN 33 Dimensions Figure 30 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz front return back supply...
Страница 34: ...34 WSHP SVX01E EN Dimensions Figure 31 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz back return front supply...
Страница 35: ...WSHP SVX01E EN 35 Dimensions Figure 32 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz front return top supply...
Страница 36: ...36 WSHP SVX01E EN Dimensions Figure 33 12 1 2 15 ton 60Hz 10 and 12 1 2 ton 50Hz back return top supply...
Страница 88: ...88 WSHP SVX01E EN Figure 1 Basic 208 V 60 Hz 1Ph Wiring...
Страница 89: ...WSHP SVX01E EN 89 Wiring Figure 2 Deluxe 380 420 V 50 Hz 3 Ph...
Страница 90: ...90 WSHP SVX01E EN Wiring Figure 3 ZN510 208 V 60 Hz 1 Ph...
Страница 91: ...WSHP SVX01E EN 91 Wiring Figure 4 ZN524 460 V 60 Hz 3 Ph...
Страница 95: ......