Start-Up

WSHP-SVX11E-EN

27 

Table 4.

Operating pressures in cooling/heating for GEC* units 

Operating Data

Model GEC*

Entering 

Water 

Temp 

(°F)

Water 

Flow 

(GPM)

Cooling

Heating

Suction 

Pressure, 

(psig)

Discharge 

Pressure, 

(psig)

Water 

Temp 

Rise 
(°F)

Air Temp 

Drop 

(°F DB)

Suction 

Pressure 

(psig)

Discharge 

Pressure 

(psig)

Water 

Temp 

Drop 

(°F)

Air Temp 

Rise 

(°F DB)

GEC*006 (60 Hz)

35°

1.4 

91-105

255-325

10-13

21-26

GEC*006 (60 Hz)

35°

1.8 

92-106

255-325

8-10

21-27

GEC*006 (60 Hz)

45°

1.4 

142-164

188-239

12-16

23-29

107-123

267-339

11-14

24-30

GEC*006 (60 Hz)

45°

1.8 

142-163

179-228

10-12

23-29

110-126

269-342

9-12

24-31

GEC*006 (60 Hz)

55°

1.4 

144-165

217-276

12-15

23-29

124-143

279-355

12-16

27-34

GEC*006 (60 Hz)

55°

1.8 

143-165

207-263

9-12

23-29

128-147

282-359

10-13

27-35

GEC*006 (60 Hz)

68°

1.4 

146-168

259-329

12-15

22-28

149-172

297-378

14-18

31-39

GEC*006 (60 Hz)

68°

1.8 

145-167

247-314

9-12

22-28

154-177

300-382

11-14

32-40

GEC*006 (60 Hz)

75°

1.4 

147-169

280-357

11-15

21-27

164-189

307-391

15-19

33-42

GEC*006 (60 Hz)

75°

1.8 

147-169

271-345

9-12

21-27

170-196

310-395

12-15

34-43

GEC*006 (60 Hz)

86°

1.4 

147-170

331-422

12-15

20-26

190-219

323-411

16-21

36-46

GEC*006 (60 Hz)

86°

1.8 

147-169

321-409

9-12

20-26

197-227

327-417

13-17

37-47

GEC*006 (60 Hz)

95°

1.4 

148-170

392-498

12-15

19-24

GEC*006 (60 Hz)

95°

1.8 

148-170

379-483

9-12

19-25

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

35°

1.7 

93-107

258-328

10-12

21-26

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

35°

2.1 

93-107

258-329

8-10

21-27

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

45°

1.7 

149-171

189-241

13-16

23-29

108-125

271-344

11-14

24-30

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

45°

2.1 

146-168

183-233

10-13

23-29

111-128

273-347

9-11

24-31

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

55°

1.7 

144-166

216-275

12-15

23-29

126-145

284-362

12-15

27-34

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

55°

2.1 

145-167

210-267

10-12

23-29

129-149

287-365

10-13

27-35

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

68°

1.7 

146-169

254-323

11-14

22-28

152-175

303-386

14-17

31-39

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

68°

2.1 

146-168

247-315

9-12

22-28

157-180

306-390

11-14

32-40

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

75°

1.7 

146-168

280-356

11-14

21-27

167-193

313-399

14-18

33-42

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

75°

2.1 

146-168

270-344

9-11

21-27

173-199

317-403

12-15

34-43

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

86°

1.7 

146-168

333-424

11-14

20-26

194-224

330-420

16-20

36-46

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

86°

2.1 

147-169

321-409

9-12

20-26

201-232

334-425

13-16

37-47

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

95°

1.7 

147-169

396-504

12-15

19-24

GEC*009 (60 Hz) 
GEC*006 (50 Hz) 

95°

2.1 

146-168

381-485

9-12

19-25

GEC*012 (60 Hz) 
GEC*009 (50 Hz)

35°

2.2 

92-106

276-351

10-12

21-26

GEC*012 (60 Hz) 
GEC*009 (50 Hz)

35°

2.8 

93-106

276-352

8-10

21-27

GEC*012 (60 Hz) 
GEC*009 (50 Hz)

45°

2.2 

143-164

180-229

12-15

23-29

108-124

289-367

11-14

24-30

Содержание Axiom GECE 006

Страница 1: ...ould install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Im...

Страница 2: ...ent that is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the...

Страница 3: ...ede these policies Non Trane personnel should always follow local regulations Introduction WSHP SVX11E EN 3 Copyright This document and the information in it are the property of Trane and may not be u...

Страница 4: ...cal Data 23 Pre Start Checklist 25 Start Up 26 Initial Unit Start up 26 Start Up Checklist and Log 26 Operating Pressures 26 Water Pressure Drop 29 Water Volume 30 Maintenance 31 Preventive Maintenanc...

Страница 5: ...rflow Sensor 3 Condensate Overflow and Filter Maintenance Timer 6 Condensate Overflow and Fan Status J Condensate Overflow Sensor Fan Status and Filter Maintenance Timer Digit 20 Temperature Sensor 0...

Страница 6: ...terior insulation it should be removed and replaced prior to operating the system NOTICE Microbial Growth Failure to follow instructions below could result in odors and damage to the equipment and bui...

Страница 7: ...tons 60 Hz 0 5 to 1 25 tons 50 Hz cabinet RH piping connection 48 12 CONTROL ACCESS PANEL 2 1 2 6 LONG 5 8 I D PLASTIC HOSE PROVIDED FOR CONDENSATE CONNECTION 3 3 8 2 3 4 5 5 8 33 6 3 3 4 4 7 8 1 3 4...

Страница 8: ...OLES FILTER ACCESS 33 3 3 4 FOR CONDENSATE 2 1 2 CONNECTION 2 3 4 3 3 8 PLASTIC HOSE 6 LONG 6 1 3 4 UNIT CONTROLLER 4 3 8 21 7 8 11 1 4 DRAIN CONN 625 I D 10 7 3 8 23 3 4 22 3 8 25 625 ODS WATER IN CO...

Страница 9: ...Figure 5 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase RH 4 3 4 48 9 1 4 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions WSHP SVX11E EN 9...

Страница 10: ...Figure 6 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase LH 4 3 4 48 13 1 4 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions 10 WSHP SVX11E EN...

Страница 11: ...3 4 22 3 8 11 1 4 25 PLASTIC DRAIN CONN 625 I D WATER IN CONN 625 O D S WATER OUT CONN 625 O D S 16 3 8 6 3 8 RECEPTACLE BOX UNIT CONTROLLER 33 3 3 4 FILTER ACCESS 2 1 2 6 LONG PLASTIC HOSE FOR CONDEN...

Страница 12: ...4 3 8 21 7 8 11 1 4 PLASTIC DRAIN CONN 625 I D 7 3 8 23 3 4 22 3 8 25 WATER OUT 625 ODS WATER IN CONN 625 ODS 7 8 6 LONG PLASTIC HOSE FOR CONDENSATE CONN 33 3 3 4 2 1 2 18 1 2 17 3 4 FILTER ACCESS 6 1...

Страница 13: ...Figure 9 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase RH extended length 19 3 4 63 9 1 4 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions WSHP SVX11E EN 13...

Страница 14: ...Figure 10 GEC 0 5 to 1 5 tons 60 Hz 0 5 to 1 25 tons 50 Hz subbase LH extended length 19 3 4 63 28 33 6 15 9 5 8 3 4 11 1 4 3 3 4 3 4 TOP VIEW ISO VIEW Unit Dimensions 14 WSHP SVX11E EN...

Страница 15: ...7 8 6 1 4 RECEPTACLE BOX PIPE ELECTRICAL FIELD HOOK UP 47 1 4 5 15 3 4 4 25 WALL SLEEVE MOUNTING HOLES 4 7 8 34 3 4 1 3 4 RETURN AIR OPENING 1 1 4 6 LONG PLASTIC HOSE PROVIDED FOR CONDENSATE CONNECTI...

Страница 16: ...BI DIRECTIONAL GRILLES 12 34 3 4 1 3 4 1 1 4 6 LONG PLASTIC HOSE PROVIDED FOR CONDENSATE CONNECTION 1 1 2 4 7 8 2 3 4 3 3 8 CONTROL ACCESS PANEL 4 3 8 19 3 8 11 1 4 10 3 8 4 7 8 21 1 4 19 7 8 22 1 2 6...

Страница 17: ...E TERMINAL STRIP 6 1 4 10 1 2 AIR SIDE SERVICE PANEL 20 1 4 REFRIGERATION SERVICE PANEL 625ODS WATER IN 2 1 8 1 1 2 6 LONG 625 I D PLASTIC HOSE PROVIDE FOR CONDENSATE CONNECTION WATER OUT 625 ODS 42 1...

Страница 18: ...4 5 8 2 10 3 8 7 5 8 WATER OUT 625 ODS 2 3 8 1 3 8 2 1 8 CONDENSATE CONNECTION PLASTIC HOSE PROVIDE FOR 6 0 LONG 625 I D 625 ODS WATER IN AIR SIDE SERVICE PANEL REFRIGERATION SERVICE PANEL HIGH VOLTAG...

Страница 19: ...to 1 5 tons Unit Size Shipping Weight with Pallet Shipping Weight without Pallet GEC Unit Weight lbs Chassis Weight lbs Unit Weight lbs Chassis Weight lbs 006 218 170 188 140 009 219 171 189 141 012 2...

Страница 20: ...outside air cut out Level the unit per plan requirements Mark the four mounting locations for wall sleeve mounting to the wall The dimensions should fall in line with Step 5 4 Removethechassisfromthe...

Страница 21: ...o condensate trapping is necessary However it is necessary for the condensate to run in a downward motion to allow gravity to properly drain the system The unit drain connection is 5 8 in I D or 7 8 i...

Страница 22: ...Installation 22 WSHP SVX11E EN 19 For units with the factory provided receptacle box options the receptacle plug may now be connected to the electrical outlet...

Страница 23: ...0 GEC009 220 240 50 1 13 2 5 3 23 0 1 7 4 0 70 1 12 1 16 5 20 3 0 12 5 GEC009 220 240 50 1 17 4 5 3 23 0 1 7 4 0 70 1 12 1 21 7 25 4 0 16 67 GEC009 265 60 1 3 5 2 8 13 0 1 3 7 0 70 1 30 1 4 2 15 0 0...

Страница 24: ...rols Deluxe with Reheat 75 VA Deluxe with Electric Heat 75 VA UC400 B 75 VA ZN524 75 VA x ON a Controller 6 0 6 0 12 5 19 5 1K1 Compressor Contactor 5 5 5 5 5 5 5 5 X 1K2 Fan Relay 9 5 9 5 9 5 9 5 2L1...

Страница 25: ...Guide Is vibration isolation provided i e unit isolation pad hose kits Is unit serviceable Allow a 12 inch clearance at the unit front for serviceability Are the low high side pressure temperature cap...

Страница 26: ...mooth with no frost observed in the refrigeration circuit 10 Check the heating refrigerant pressures against values in Table 4 p 27 11 Set the thermostat to maintain the desired space temperature 12 I...

Страница 27: ...12 15 19 24 GEC 006 60 Hz 95 1 8 148 170 379 483 9 12 19 25 GEC 009 60 Hz GEC 006 50 Hz 35 1 7 93 107 258 328 10 12 21 26 GEC 009 60 Hz GEC 006 50 Hz 35 2 1 93 107 258 329 8 10 21 27 GEC 009 60 Hz GE...

Страница 28: ...45 2 8 144 165 178 227 11 14 23 29 105 121 277 353 11 14 24 30 GEC 015 60 Hz GEC 012 50 Hz 45 3 5 144 165 172 219 9 12 23 29 108 124 279 355 9 11 24 31 GEC 015 60 Hz GEC 012 50 Hz 55 2 8 145 167 206 2...

Страница 29: ...2 172 219 9 11 23 29 110 127 289 368 8 11 24 31 GEC 018 60 Hz GEC 015 50 Hz 55 3 4 141 163 206 262 11 14 23 29 126 145 302 385 11 14 27 34 GEC 018 60 Hz GEC 015 50 Hz 55 4 2 141 162 200 254 9 11 23 29...

Страница 30: ...in calculating glycol requirements for the unit Table 7 Water volume for GEC units Unit Size 60 Hz Unit Size 50 Hz WaterSide Volume in3 Water Side Volume ft3 WaterSide Volume gallons 006 009 006 13 6...

Страница 31: ...ring the unit heat exchanger and to ensure a clean system For units on well water it is important to check the cleanliness of the water to refrigerant heat exchanger Should it become contaminated with...

Страница 32: ...of the controller The LEDs are intended to aid in troubleshooting The LEDs are labeled on the circuit board with numbers as referenced in Table 10 p 32 Table 10 Diagnostic LEDs Color Green Color Red C...

Страница 33: ...se temperature X Inadequate air flow Check clean blower and coil X Dirty filter Clean replace X X Overcharged with refrigerant Decrease charge X X Defective pressure switch Check or replace High head...

Страница 34: ...34 WSHP SVX11E EN Wiring Diagrams Figure 15 Deluxe 24V controls...

Страница 35: ...Figure 16 Tracer ZN524 Wiring Diagrams WSHP SVX11E EN 35...

Страница 36: ...Figure 17 Tracer UC400 B 208V 60 Hz 1pH Wiring Diagrams 36 WSHP SVX11E EN...

Страница 37: ...Figure 18 Tracer UC400 B 208V 60 Hz 1pH with hot gas reheat Wiring Diagrams WSHP SVX11E EN 37...

Страница 38: ...ment There is a standard five year compressor parts warranty Extended Warranty The optional extended warranty is a second through fifth yearwarranty The time startsatthe endofstandard1 year coverage t...

Страница 39: ......

Страница 40: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: