12. Symptom: Compressor thermal protector switch open (overloading)
Possible Causes
Potential Solutions
Liquid floodback
Adjust electronic expansion valve, increase flow, or raise set point
Compressors overamping
Correct refrigerant charge; check electrical connections
13. Symptom: No low voltage (24 Vac)
Possible Causes
Potential Solutions
Control circuit fuse open
Check fuse prong contact points; replace fuse
Phase monitor opened or tripped
Replace transformer,
T1
or
T2
primary or secondary fuse blown
No primary voltage on
T1
or
T2
Check breakers, fuses; check power supply specifications
14. Symptom: Flow switch open
Possible Causes
Potential Solutions
Insufficient water flow
Check strainer for debris; clean strainer
Switch defective
Replace flow switch
15. Symptom: Electronic expansion valve superheat too high
Possible Causes
Potential Solutions
Water/glycol temperature too warm
Low refrigerant level; adjust chiller/heater refrigerant charge as
required
Obstructed filter dryer
Replace filter dryer
Low refrigerant charge
Adjust refrigerant as per data plate
Improperly set superheat valve setting
Reset valve settings to factory specifications
16. Symptom: Electronic expansion valve superheat too low
Possible Causes
Potential Solutions
Suction temperature sensor not properly located
Check if secured to pipe or insulated; check sensor position on pipe at
4-8-10-2 o’clock positions
Improperly set superheat valve setting
Reset valve settings to factory specifications
Low flow
Increase flow or clean strainer
17. Symptom: Contactor/relay inoperative
Possible Causes
Potential Solutions
Coil shorted or open
Replace contactor
Mechanical parts broken or jammed
Replace assembly
Coil shorted or open
Replace contactor
Contacts broken or jammed
Replace contactor
Contacts pitted or burned
Replace contactor
No 24 Vac to coil
Check for loose wiring. Replace secondary fuse to T2 transformer
Bad relay on microprocessor controller
Replace microprocessor controller
Temperature set point too low
Reset above freezing temperature at evaporator or discharge