4. Symptom: Compressor cycles too short
Possible Causes
Potential Solutions
Temperature differential set too low (4 °F (22 °C) minimum)
Ramp/set temperature set point. Default 5 °F raise up accordingly
with low loads.
Erratic water thermostat device
Replace thermostat assembly.
Insufficient evaporator water flow
Adjust flow rate or clean strainer.
5. Symptom: Compressor oil level in sight glass low
Possible Causes
Potential Solutions
Low refrigerant charge
Check for leaks and repair. Add refrigerant to proper charge
Leak in refrigerant line
Repair leak; add refrigerant
6. Symptom: Low refrigeration suction pressure
Possible Causes
Potential Solutions
Low refrigerant charge
Check for leaks and repair. Add refrigerant to proper charge
Leak in refrigerant line
Repair leak; add refrigerant
Lack of refrigerant
Check for leaks. Repair and add charge
Evaporator fouled
Clean chemically
Low water flow
Increase flow rate
Condensing temperature too low
Check source water modulation valve and temperature
Low water temperature
Raise set point and increase flow; check design specification
Low discharge pressure
Check for refrigerant leak
Expansion valve malfunctioning
Increase suction pressure; suction temperature pressure; check for
proper superheat; check electronic expansion valve replace if
necessary; cabling to stepping motor; contact Trane technical support
Compressor service valves closed
Open service valve (if so equipped) counterclockwise completely
Clogged liquid line filter-drier
Replace liquid line filter-drier or core
Excessive glycol concentration
Drain, refill (deionized water), retest
Liquid line solenoid restricted or faulty
Replace solenoid valve coil
Insufficient chilled water flow
Adjust flow rate across evaporator
Restricted water/glycol line
Clean strainers; check manual and electronic expansion valves
Water/glycol mixture contaminated
Intensive cleanup effort needed to identify source of contamination;
external filter may be required
Evaporator clogged or fouled
Reverse flush with appropriate chemical solutions following approved
procedures
7. Symptom: High refrigeration suction pressure
Possible Causes
Potential Solutions
Expansion valve opened too far closed
Re-adjust to 10° C to 12° C
Excessive refrigerant charge
Creates high pressure alarms; recover excess refrigerant; weigh in
correct charge as indicated on data plate
Entering water temperature excessive
Failing tandem compressors; check design specifications