Mechanical Specifications

General

All units shall be factory assembled, piped,
internally wired and fully charged with
refrigerant. All units shall be designed to
operate at outdoor ambient temperatures
as high as 115°F.  Cooling capacities shall
be rated in accordance with A.R.I.
standards. The 4YCY4 heating/cooling unit
design is UL listed, specifically for outdoor
applications using natural gas or propane

.

All units shall be designed for outdoor
rooftop or ground level installation. Unit
casing is constructed of heavy gauge,
galvanized steel and painted with a
weather-resistant powder paint.

Shipped for horizontal application,
convertible to downflow.

Casings

All panels shall be heavy gauge steel,
gasketed and insulated. Foil-faced
insulation shall be in the heat exchanger
section. Foil-faced insulation shall be in the
evaporator section. Base pan shall be
heavy gauge steel.

 WEATHERGUARD™

exterior corrosion resistant screws shall be
used for added resistance to rust and
corrosion.

Controls

Refrigeration cycle controls shall include
condenser fan, evaporator fan and
compressor contactors. Compressors shall
be equipped with a combination internal
winding thermostat/current overload.
Internal high pressure relief shall also be
provided.

Refrigeration System
Compressors —

The 

Climatuff

®

 

compressor features

internal over temperature and pressure
protector, total dipped hermetic motor.
Other features include: roto lock suction
and discharge refrigeration connections,
centrifugal oil pump, and low vibration and
noise.

Evaporator Coil — 

Internally enhanced

3/8-inch OD seamless copper tubing
mechanically bonded to aluminum fins,
factory pressure and leak tested at 250 to
300 psig. All units have TXV to control
refrigeration flow.

Condenser Coil —

The 

Spine Fin™

 condenser coil shall be

continuously wrapped, corrosion resistant
all aluminum with minimum brazed joints.
This coil is 3/8 inch OD seamless alumi-
num tubing glued to a continuous alumi-
num fin. Coils are lab tested to withstand
2,000 pounds of pressure per square inch.
The outdoor coil provides low airflow
resistance and efficient heat transfer. The
coil is protected on all four sides by
louvered panels.

Indoor Air Fan — 

Direct-drive, forward-

curved, centrifugal wheel in a Composite

Vortica

®

  

Blower  housing. Motor shall

have thermal overload protection.
Permanently lubricated motor bearings.
Motor/blower assembly isolated from unit
with rubber mounts.

Condenser Fan — 

Direct-drive, draw

through propeller type. Weather-proofed
permanent split capacitor fan motor shall
have built-in thermal overload and
permanently lubricated motor bearings.

Low Ambient — 

Standard refrigerant

system operation down to 55°F. Low
ambient accessory required for operation
to 0°F ambient condition.

Gas-Fired Heating System — 

Models

shall provide completely assembled, wired
and piped gas fired heating systems within
unit. Design certified by UL, specifically for
outdoor application. Threaded gas
connection on the unit.

Electronic Ignition System — 

Main

burner is lit each time thermostat calls for
gas heat. Flame sensor proves flame and
keeps the main burners on. Should a loss
of flame occur, the main valve closes and
the spark recurs within 0.8 second. When
thermostat is satisfied, main burner is
extinguished.

Forced Combustion Blower — 

Insures

flame stability under varying wind
conditions. Gives higher combustion
efficiency and location flexibility.

Heat Exchanger — 

stainless steel

tubes. Free floating design.

Burners — 

 stainless  steel. Multi-

port inshot.

Accessories
(U.S. Domestic Models)
Roof Curb — 

The roof curb shall

be designed to mate with the unit
and provide support and complete
weather-tight installation when
properly installed. Curb shall ship
knocked down for field assembly,
and include wood nailer strips.

Modulating Economizer — 

This

accessory shall be field installed
and be composed of the following
items: 0-100% fresh air damper,
damper drive motor fixed dry bulb
enthalpy control, and low voltage
polarized plug for electrical
connections. Solid state enthalpy or
differential enthalpy control is
optional. Economizer operations
shall be controlled by the preset
position of the enthalpy control. A
barometic relief damper shall be
standard with the economizer and
provide a pressure operated
damper that shall be gravity closing
and prohibit entrance of outside air
on equipment “off” cycle.

Manual Fresh Air Hood

Manual outside air provides a fixed
outside air quantity from 0 to 25
percent. Includes hood and
birdscreen.

Low Ambient Control

Control allows cycling of
compressor under low ambient
cooling conditions. Required for
cooling operation to 0°F.

Propane Gas
Conversion Kit — 

For conversion

from natural gas to LP gas.

Trane

6200 Troup Highway
Tyler, TX 75707-9010

The manufacturer

 

has a policy of continuous product and product data improvement and it reserves the right to

change design and specifications without notice.

Содержание 4YCY4024A

Страница 1: ... 2008 Trane Pub No 22 1797 03 Product Data 4YCY4024A through 4YCY4060A Single Packaged Convertible Gas Electric 14 SEER 2 5 Ton 40 120 KBTU R 410A 22 1797 03 ...

Страница 2: ...ctions are all contained in a single cabinet a Trane single packaged convertible gas electric system is easy to install and service It can be flush mounted beside your home at ground level or placed on the roof for horizontal or downflow installation When connected to an optional Trane thermostat control and air distribution ducts you have a highly efficient total home comfort system Single Packag...

Страница 3: ...3 Contents Optional Equipment Listing 4 General Data 5 Performance Data Cooling 9 Indoor Fan 11 TypicalWiring 15 Optional Equipment 18 Dimensional Data 23 Mechanical Specifications 29 ...

Страница 4: ...R201B LP Conversion Kit All 40K 120K Models BAYLPKT100A LP Conversion Kit All 64K 96K Models BAYLPKT101A LP Conversion Kit All 75K Models BAYLPKT102A Head Pressure Control Low Ambient Cool 208 240v Kit 5 BAYLOAM105A Quick Start Kit 4YCY4 A1 BAYQSKT301A Crankcase Heater Recip 4YCY4024A1 230v 5 BAYCCHT101A Crankcase Heater Scroll 4YCY4036 060A1 3 230v 5 BAYCCHT102A Adapter Curb 4YCY4024 036A to BAYC...

Страница 5: ...per 1000 ft elevation 3 3 3 3 3 Convertible to LPG 4 4 4 4 4 This value is approximate For more precise value see Unit Nameplate 5 5 5 5 5 Based on U S Government Standard Tests 6 6 6 6 6 Filtersmustbeinstalledinreturnairstream Squarefootageslistedarebasedon300f p m facevelocity Ifpermanentfiltersareusedsizepermanufacturer srecommendation with a clean resistance of 0 05 W C 7 7 7 7 7 Unit is shipp...

Страница 6: ...08 230 3 60 19 8 30 30 SCROLL 208 230 3 60 11 5 77 SPINE FIN 2 24 15 49 3 8 PLATE FIN 4 15 3 54 3 8 EXPANSION VALVE 3 4 FEMALE NPT PROPELLER 23 4 DIRECT 1 1 5 830 208 230 1 60 1 1 1 9 CENTRIFUGAL 10 X 10 DIRECT VARIABLE SEE FAN PERF TABLE 1 2 VARIABLE 200 230 1 60 4 3 4 3 CENTRIFUGAL DIRECT 2 1 45 2800 1500 208 230 1 60 0 34 NO THROWAWAY 4 0 R410A 6 75 1 2 H X W X L 47 86 44 5 52 03 493 397 4YCY40...

Страница 7: ...FAN TYPE Dia x Width in Drive No Speeds CFM 0 0 in w g n Motor HP R P M Volts Ph Hz F L Amps L R Amps COMBUSTION FAN TYPE Drive No Speeds Motor HP R P M Volts Ph Hz FLA FILTER FURNISHED Type Recommended Recmd Face Area sq ft o REFRIGERANT Charge lbs m GAS PIPE SIZE in DIMENSIONS Crated in WEIGHT Shipping lbs Net lbs 4YCY4048A1096A 208 230 1 60 48000 1605 4 034 11 9 14 2 73 72000 96000 80 0 30 60 3...

Страница 8: ...8 230 3 60 30 6 45 45 SCROLL 208 230 3 60 17 6 123 SPINE FIN 2 24 23 07 3 8 PLATE FIN 4 15 5 0 3 8 EXPANSION VALVE 3 4 FEMALE NPT PROPELLER 28 2 DIRECT 1 1 3 830 208 230 1 60 1 7 3 5 CENTRIFUGAL 11 X 10 DIRECT VARIABLE SEE FAN PERF TABLE 1 VARIABLE 208 230 1 60 6 9 6 9 CENTRIFUGAL DIRECT 2 1 45 2800 1500 208 230 1 60 0 34 NO THROWAWAY 5 3 R410A 9 75 1 2 H X W X L 51 86 47 4 61 75 676 548 4YCY4048A...

Страница 9: ... 7 16 4 16 7 16 7 16 7 2 3 63 17 5 13 0 15 3 17 5 17 5 2 3 67 18 8 9 8 12 1 14 4 16 0 2 3 71 20 3 6 6 8 9 11 2 12 8 2 3 USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW AIR FLOW CAPACITY TOTAL POWER RATE CFM MULTIPLIER MULTIPLIER LOW 700 0 97 0 98 HIGH 900 1 03 1 02 ARI RATING FOR COOLING CFM CAPACITY A TEST SEER EER 790 23400 14 00 11 60 ARI Standard Capacity Rating Conditions ARI S...

Страница 10: ...4 43 0 46 4 46 4 46 4 5 8 63 48 3 34 2 40 2 46 2 48 3 5 8 67 52 1 26 0 32 0 37 9 41 9 5 9 71 56 2 17 7 23 7 29 6 33 7 5 9 USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW AIR FLOW CAPACITY TOTAL POWER RATE CFM MULTIPLIER MULTIPLIER LOW 1750 0 97 0 98 HIGH 2250 1 03 1 02 ARI RATING FOR COOLING CFM CAPACITY A TEST SEER EER 1799 58500 14 00 11 90 ARI Standard Capacity Rating Conditions ...

Страница 11: ...2 899 909 907 895 886 898 910 900 HIGH External Static Pressure in wg LOW MED 4YCY4024A DOWN Motor Speed 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 Watts 113 148 176 203 233 263 291 309 306 267 CFM 880 905 917 918 913 906 901 907 930 979 Watts 146 184 215 243 272 303 330 348 347 312 CFM 996 1009 1013 1012 1008 1003 1000 997 994 991 Watts 195 233 267 303 340 371 388 373 CFM 1122 1132 1134 1136 1138 11...

Страница 12: ...377 1377 1375 1366 1352 1344 1360 1340 HIGH External Static Pressure in wg LOW MED 4YCY4036A DOWN Motor Speed 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 Watts 160 185 214 245 277 308 339 368 396 423 CFM 1206 1211 1213 1215 1215 1214 1212 1208 1201 1190 Watts 231 261 292 325 359 394 431 467 503 536 CFM 1389 1398 1405 1409 1410 1408 1403 1399 1396 1399 Watts 326 362 393 421 450 482 517 556 597 CFM 1582...

Страница 13: ...4 1624 1624 1621 1618 1618 1620 1618 1606 1574 Watts 364 461 518 558 597 643 693 739 764 785 CFM 1816 1829 1836 1839 1840 1840 1844 1835 1830 1825 HIGH External Static Pressure in wg LOW MED 4YCY4048A DOWN Motor Speed 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 Watts 394 427 464 504 548 591 633 668 CFM 1673 1772 1799 1793 1779 1771 1767 1756 Watts 695 642 660 710 764 811 849 893 966 1108 CFM 2054 2036...

Страница 14: ... 3 4YCY4036A 075 4YCY4036A 096 Switch Settings Nominal Airflow Switch Settings Nominal Airflow can be 1 or 3 Selection Low Stage High Stage 7 OFF 8 OFF A 1075 1375 7 ON 8 OFF B 1100 1450 7 OFF 8 ON C 1150 1500 7 ON 8 ON D 1200 1575 4YCY4042A Switch Settings Nominal Airflow Selection Low Stage High Stage 7 OFF 8 OFF A 1075 1375 7 ON 8 OFF B 1100 1450 7 OFF 8 ON C 1150 1500 7 ON 8 ON D 1200 1575 Sel...

Страница 15: ... W2 R COMMON FAN COMPRESSOR HEAT FIRST STAGE HEAT SECOND STAGE 24V UNIT CONTROL BOX GROUND WIRE 3 PH POWER UNIT NOTE 1 1 PH POWER B G Y W1 W2 R COMMON FAN COMPRESSOR HEAT FIRST STAGE HEAT SECOND STAGE 24V B G Y W1 W2 R GR WH WH GR WH WH GR WH WH ...

Страница 16: ...16 Typical Wiring ...

Страница 17: ...17 From Dwg 21D757165 P02 Typical Wiring ...

Страница 18: ...is page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use ...

Страница 19: ...is page are prepared by the manufacturer in order to provide detail regarding job layout only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use ...

Страница 20: ...sis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use BAYFLTR101 201B 1 2 Filter Rack Mounts in Filter Coil Section BAYACCDOR1A BAYACCDOR2A Hinged Filter Access Door Replaces Filter Coil Access Panel Filter ...

Страница 21: ... only These drawings are not intended to be used as a basis to construct build or modify the items depicted in the drawings The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use Economizer Unit ApplicationM odels A BAYECON101A 2 4YC WC3018 036A 4TC 3018 036A 4W T Y DCY4024 060 20 125 BAY...

Страница 22: ...ible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unautho rized use Manual Fresh Air Model Unit Application Models A B C D BAYOSAH001 2 4YC WC3018 036A 4TC 3018 036A 4W T Y DCY4024 036A 4W Y DCZ6036A 22 7 16 20 11 16 12 3 8 9 3 16 BAYOSAH002 2 4YC WC3042 060A 4TC 3042 060A 4W T Y DCY4042 060 4W Y DCZ6048 060A 25 3 16 20 11 16 12 3...

Страница 23: ...23 Dimensional Data 4YCY4024A through 4YCY4036A 1 of 3 ...

Страница 24: ...24 Dimensional Data 4YCY4024A through 4YCY4036A 2 of 3 ...

Страница 25: ...25 4YCY4024A through 4YCY4036A 3 of 3 Dimensional Data ...

Страница 26: ...26 Dimensional Data 4YCY4042A through 4YCY4060A 1 of 3 ...

Страница 27: ...27 Dimensional Data 4YCY4042A through 4YCY4060A 2 of 3 ...

Страница 28: ...28 4YCY4042A through 4YCY4060A 3 of 3 Dimensional Data ...

Страница 29: ...ted motor bearings Motor blower assembly isolated from unit with rubber mounts Condenser Fan Direct drive draw through propeller type Weather proofed permanent split capacitor fan motor shall have built in thermal overload and permanently lubricated motor bearings Low Ambient Standard refrigerant system operation down to 55 F Low ambient accessory required for operation to 0 F ambient condition Ga...

Отзывы: