background image

18-AD35D1-2D-EN  

5

Installer’s Guide

Maximum airflow setting, CFM

Coil

Upflow

Horizontal Left

4TXCA002DS3HCA

900

800

4TXCA032DS3HCA

1350

1125

4TXCB003DS3HCA

1125

1000

4TXCB004DS3HCA

1350

1200

4TXCC005DS3HCA

1350

1200

4TXCB006DS3HCA

1800

1600

4TXCC007DS3HCA

1800

1600

4TXCD008DS3HCA

1800

1600

4TXCC009DS3HCA

2250

2000

4TXCD010DS3HCA

2250

2000

Coil

Downflow

Horizontal Right

4TXCA002DS3HCA

750

900

4TXCA032DS3HCA

1200

1350

4TXCB003DS3HCA

925

1125

4TXCB004DS3HCA

1100

1350

4TXCC005DS3HCA

1100

1350

4TXCB006DS3HCA

1475

1800

4TXCC007DS3HCA

1475

1800

4TXCD008DS3HCA

1475

1800

4TXCC009DS3HCA

1850

2250

4TXCD010DS3HCA

1850

2250

H. MAXIMUM AIRFLOW SETTING, CFM

NOTE:   

Water blow-off could occur in certain installation posi-

tions if the airflow setting exceeds the maximum values 

listed.

IMPORTANT:  

Do not unseal refrigerant tubing until ready to fit refriger-

ant lines.

There is only a holding charge of dry air in the indoor coil, 
therefore no loss of operating refrigerant charge occurs when 
the sealing plugs are removed.

NOTE:  

TXV bulb MUST be protected (wrapped with wet rag) or 

removed, while brazing the tubing. Overheating of the 

sensing bulb will affect the functional characteristics and 

performance of the comfort coil.

1. Remove both rubber plugs from the indoor coil.
2. Field supplied tubing should be cut square, round and free 
of burrs at the connecting end.  Clean the tubing to prevent 
contaminants from entering the system.
3. Run the refrigerant tubing into the stub tube sockets of 
the indoor unit coil.

PAINTED AREAS OF THE UNIT MUST BE SHIELDED 

DURING BRAZING.

4. Flow a small amount of nitrogen through the tubing while 
brazing.
5. Use good brazing technique to make leakproof joints.
6. Minimize the use of sharp 90 degree bends.
7. Insulate the suction line and its fittings.
8. Do NOT allow un-insulated lines to come into contact with 
each other.

I. INSTALLING / BRAZING REFRIGERANT LINES

CAUTION

!

Do NOT open refrigerant valve at the outdoor unit until the 

refrigerant lines and coil have been brazed, evacuated, and 

leak checked.  This would cause contamination of the refriger-

ant or possible discharge of refrigerant to the atmosphere.

 

1.  The following steps are to be considered when installing 
the refrigerant lines:

a. Determine the most practical way to run the lines.
b. Consider types of bends to be made and space limita-

tions.

c. Route the tubing making all required bends and properly 

secure the tubing before making final connections.

NOTE:

 Refrigerant lines must be isolated from the structure 

and the holes must be sealed weather tight after installation.

NOTE:   

The TXV setting on this unit may run high superheat  

(15-25°F) by design when measured at the outdoor unit.

Содержание 4TXCA002DS3HCA

Страница 1: ...oil before beginning the installation Figure 1 18 AD35D1 2D EN Cased Aluminum Convertible Coils Models 4TXCA002DS3HCA 4TXCA032DS3HCA 4TXCB003DS3HCA 4TXCB004DS3HCA 4TXCB006DS3HCA 4TXCC005DS3HCA 4TXCC00...

Страница 2: ...ency a Remove the coil by sliding the coil out of the coil enclo sure b Optional but recommended Remove the factory in stalled two piece baffle assembly from the top of the coil by removing the 5 16 h...

Страница 3: ...mmended On 4TXCC009DS and 4TXCD010DS only remove the 2 outer water diverter baffles by removing the 5 16 hex head screws See Fig ure 6 IMPORTANT The 4TXC cased coil must be placed downstream of the fu...

Страница 4: ...condensing downflow hori zontal and upflow horizontal furnaces may only be rotated onto their left side Connection brackets for coil furnace alignment are included with the furnaces a In horizontal le...

Страница 5: ...rubber plugs from the indoor coil 2 Field supplied tubing should be cut square round and free of burrs at the connecting end Clean the tubing to prevent contaminants from entering the system 3 Run th...

Страница 6: ...for proper drainage due to the positive pressure of the furnace however it is recommended to prevent efficiency loss of conditioned air 1 The drain hole in the drain pan must be cleared of all insula...

Страница 7: ...ALL WIDTH B IN 14 1 2 14 1 2 17 1 2 21 17 1 2 21 21 OPENING WIDTH C IN 13 5 8 13 5 8 16 5 8 20 1 8 16 5 8 20 1 8 20 1 8 TOP OPENING D 12 3 4 12 3 4 15 3 4 19 1 4 15 3 4 19 1 4 19 1 4 GAS CONNECTION 3...

Страница 8: ...T LBS 50 REFRIGERANT CONTROL TXV NON BLEED HEIGHT A IN 17 1 2 OVERALL WIDTH B IN 17 1 2 OPENING WIDTH C IN 16 5 8 TOP OPENING D 15 3 4 GAS CONNECTION 3 4 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO...

Страница 9: ...EED HEIGHT A IN 26 7 8 30 11 16 OVERALL WIDTH B IN 24 1 2 24 1 2 OPENING WIDTH C IN 23 5 8 23 5 8 TOP OPENING D 22 3 4 22 3 4 GAS CONNECTION 7 8 LIQUID CONNECTION 3 8 MATCHED FURNACE WIDTH NO ADAPTER...

Страница 10: ...NO Is superheat 25F YES NO Is indoor temperature more than 85F NO Is sub cooling less than 8F YES Confirm that charge is correct and look for dirty or restricted outdoor coil Confirm that charge is c...

Страница 11: ...18 AD35D1 2D EN 11 Installer s Guide...

Страница 12: ...icy of continuous product and product data improvement it reserves the right to change design and specifications without notice Trane 6200 Troup Highway Tyler TX 75707 For more information contact you...

Отзывы: