22
18-BC90D1-4A-EN
STEP 3
- Check the liquid line temperature and
liquid gage pressure to obtain a minimum of 10º
subcooling in heating mode.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSIG
STEP 4
- Add charge if a minimum of 10º
subcooling is not obtained with the nameplate
charge plus additional charge previously added.
STEP 5
- Return to site for adjustment.
Important:
Return in the spring or summer to
accurately charge the system in the cooling
mode with outdoor ambient
above 55º F
.
20 MIN.
STEP 2
- Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a mini-
mum of 20 minutes to stabilize before accurate
measurements can be made.