Section 12. Electrical - High Voltage
12.1 High Voltage Power Supply
The high voltage power supply must agree with
the equipment nameplate.
Power wiring must comply with national, state,
and local codes.
Follow instructions on unit wiring diagram located
on the inside of the control box cover and in the
Service Facts document included with the unit.
12.2 High Voltage Disconnect Switch
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and
troubleshooting of this product, it may be nec-
essary to work with live electrical components.
Failure to follow all electrical safety precau-
tions when exposed to live electrical compo-
nents could result in death or serious injury.
s
WARNING
Install a separate disconnect switch at the
outdoor unit.
For high voltage connections, flexible electri-
cal conduit is recommended whenever vibra-
tion transmission may create a noise problem
within the structure.
Defrost Termination Temperatures
Outdoor
Temperature
Termination
Temperature
As
Shipped
>22°F
47°F
10°F–22°F
ODT + 25°F
6°F–10°F
35°F
Cut
Jumper 2
>30°F
47°F
6°F–30°F
70°F
All
< 6°F
12 min. or 35°F
every 3 hrs.
J1
U1
J2
J3
FRC_DFT
TST
TEST_COMMON
LO
W_F
AN
JUMPER 2
TEST PINS
Defrost Board
Detail