18-BC51D1-3

Installer’s Guide

NOTE:
Unnecessary switching of hoses can be avoided and com-
plete evacuation of all lines leading to sealed system can
be accomplished with manifold center hose and connect-
ing branch hose to a cylinder of R-410A and vacuum pump.

3. Attach center hose of manifold gauges to vacuum pump.

4. Evacuate until the micron gauge reads no higher than

350 microns.

5. Close off valve to vacuum pump and observe the micron

gauge. If gauge pressure rises above 500 microns in
one (1) minute, then evacuation is incomplete or system
has a leak.

6. If vacuum gauge does not rise above 500 microns in

one (1) minute, the evacuation should be complete.

7. With vacuum pump and micron gauge blanked off, open

valve on R-410A cylinder and charge refrigerant lines and
indoor coil with vapor to tank pressure of R-410A supply.

NOTE:
DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.

8. Close valve on R-410A supply cylinder. Close valves on

manifold gauge set and remove refrigerant charging
hoses from liquid and gas pressure tap ports.

NOTE:
A 3/16" Allen wrench is required to open liquid line service
valve. A 1/4" Open End or Adjustable wrench is required to
open gas line valve. A 3/4" Open End wrench is required to
take off the valve stem cap.

9. The liquid line shut-off valve can now be opened. Remove

shut-off valve cap. Fully insert hex wrench into the stem
and backout counterclockwise until valve stem just
touches rolled edge (approximately five [5] turns)
observing WARNING statement on page 3. See Figure 4.

10. Replace liquid service pressure tap port cap and valve

stem cap. These caps MUST BE REPLACED to
prevent leaks. Replace valve stem and pressure tap cap
finger tight, then tighten an additional 1/6 turn.

11. The gas valve can now be opened. Open the gas valve by

removing the shut-off valve cap and turning the valve
stem 1/4 turn counterclockwise, using 1/4" Open End or
Adjustable wrench. See Figure 5.

12. The gas valve is now open for refrigerant flow. Replace

valve stem cap to prevent leaks. Again, these caps
MUST BE REPLACED to prevent leaks. Replace valve
stem and pressure tap cap finger tight, then tighten an
additional 1/6 turn. See Figure 5.

If refrigerant lines are longer than 15 feet and/or a different
size than recommended, it will be necessary to adjust system
refrigerant charge upon completion of installation. See unit
Service Facts.

F. ELECTRICAL CONNECTIONS

WARNING

!

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility
of electric shock.

1. Power wiring and grounding of equipment must comply

with local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.

4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration

transmission may create a noise problem within the
structure.

6. The use of color coded low voltage wire is recommended

to simplify connections between the outdoor unit, the
thermostat and the indoor unit.

Table 1 — NEC Class II Control Wiring

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

7. Table 1 defines maximum total length of low voltage

wiring from outdoor unit, to indoor unit, and to
thermostat.

8. Mount the indoor thermostat in accordance with instruc-

tion included with the thermostat. Wire per appropriate
hook-up diagram (included in these instructions).

G. DEFROST CONTROL

The demand defrost control measures heat pump outdoor
ambient temperature with a sensor located outside the
outdoor coil. A second sensor located on the outdoor coil is
used to measure the coil temperature. The difference between
the ambient and the colder coil temperature is the difference
or delta-T measurement. This delta-T measurement is
representative of the operating state and relative capacity of
the heat pump system. By measuring the change in delta-T,
we can determine the need for defrost. The coil sensor also
serves to sense outdoor coil temperature for termination of
the defrost cycle.

FAULT IDENTIFICATION

A fault condition is indicated by the flashing light on the
defrost control inside the heat pump control box.

In normal operation, the defrost control light will flash once
each second. If the light is flashing more than once per
second or not at all, refer to the service manual for that unit.

PIN IDENTIFICATION (See Figure 6.)

1. TEST_COMMON (Shorting any of the other pins to

this pin causes the function of the other pin to be
executed. Leaving this pin open results in the normal
mode of operation.)

PIN IDENTIFICATION

6

FRC_DFT

TEST_COMMON

TST

Содержание 4TWR4

Страница 1: ...trical and mechanical experience Any attempt to repair a central air conditioning product may result in personal injury and or property damage The manufacturer or seller cannot be responsible for the...

Страница 2: ...ure 6 The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty 60 feet 7 If outdoor unit is mounted above the air handler maxi mum lift should not exceed sixty 60 fe...

Страница 3: ...hen depressed opens only to the field brazing side when the valve is in the closed position The Gas Line Service Valve is full open with a 1 4 turn See Figure 5 BRAZING REFRIGERANT LINES 1 Remove lowe...

Страница 4: ...feet and or a different size than recommended it will be necessary to adjust system refrigerant charge upon completion of installation See unit Service Facts F ELECTRICAL CONNECTIONS WARNING When ins...

Страница 5: ...switch This will activate the compressor sump heat where used Do not change the Thermostat System Switch until power has been applied for one 1 hour Following this procedure will prevent potential co...

Страница 6: ...1 841 33 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR2060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR4018A 3 1 933...

Страница 7: ...18 BC51D1 3 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg D152637 Rev 1...

Страница 8: ...ressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start DEFROST Unit Won t Initiate De...

Отзывы: