background image

18-BC51D1-3

3

Installer’s Guide

The units are factory charged with the system charge
required when using fifteen (15) feet of connecting line. Unit
nameplate charge is the same.

Final refrigerant charge adjustment is necessary. Use
the Charging Charts in the outdoor unit Service Facts.

1. Determine the most practical way to run the lines.

2. Consider types of bends to be made and space limitations.

NOTE:
Large diameter tubing will be very difficult to rebend once it
has been shaped.

3. Determine the best starting point for routing the refriger-

ant tubing — INSIDE OR OUTSIDE THE STRUCTURE.

4. Provide a pull-thru hole of sufficient size to allow both

liquid and gas lines.

5. Be sure the tubing is of sufficient length.

6. Uncoil the tubing — do not kink or dent.

7. Route the tubing making all required bends and properly

secure the tubing before making connections.

8. To prevent a noise within the building structure due to

vibration transmission from the refrigerant lines, the
following precautions should be taken:

a. When the refrigerant lines have to be fastened to floor

joists or other framing in a structure, use isolation
type hangers.

b. Isolation hangers should also be used when refriger-

ant lines are run in stud spaces or enclosed ceilings.

c. Where the refrigerant lines run through a wall or sill,

they should be insulated and isolated.

d. Isolate the lines from all ductwork.

E. SERVICE VALVE OPERATION

BRASS LIQUID LINE SERVICE VALVE

The Brass Liquid Line Service Valve is factory shipped in the
seated position to hold factory charge. The pressure tap service
port (when depressed) opens only to the field brazing side of
the valve when the valve is in the seated position. The liquid
line valve is not a back seating valve (see WARNING below).

WARNING

!

Extreme caution should be exercised when opening the
Liquid Line Service Valve. Turn valve stem counterclock-
wise only until the stem contacts the rolled edge. (See
Figure 4) No torque is required.

BRASS GAS LINE SERVICE VALVE

The Brass Gas Line Service Valve is shipped in the closed
position to hold the factory refrigerant charge. The pressure
tap service port (when depressed) opens only to the field
brazing side when the valve is in the closed position.

The Gas Line Service Valve is full open with a 1/4 turn. See
Figure 5.

BRAZING REFRIGERANT LINES

1. Remove lower access cover to access service valves.

2. Before brazing, remove plugs from external copper stub

tubes. Clean internal and external surfaces of stub tubes
prior to brazing.

3. Cut and fit tubing, minimizing the use of sharp 90°

bends.

4. Insulate the entire gas line and its fittings.

5. Do NOT allow uninsulated liquid line to come in direct

contact with bare gas line.

6. Precautions should be taken to avoid heat damage

to the pressure tap valve core during brazing. It is
recommended that the pressure tap port valve
core be removed and a wet rag wrapped around
the valve body.

NOTICE:
Use care to make sure that no moisture enters pressure tap
port, while wet rag is being used.

NOTICE:
Precautions should be taken to avoid heat damage to
basepan during brazing. It is recommended to keep the
flame directly off of the basepan.

7. Use a Dry Nitrogen Purge and Brazing Alloy without

flux when brazing the field line to the copper factory
connection. Flow dry nitrogen into either valve pressure
tap port, thru the tubing and out the other port while
brazing.

8. Braze using accepted good brazing techniques.

LEAK CHECK

IMPORTANT:
Replace pressure tap port valve core before attaching hoses for
evacuation.

After the brazing operation of refrigerant lines to both the
outdoor and indoor unit is completed, the field brazed
connections must be checked for leaks. Pressurize through
the service valve ports, the indoor unit and field refrigerant
lines with dry nitrogen to 350-400 psi. Use soap bubbles or
other leak-checking methods to see that all field joints are
leak-free! If not, release pressure; then repair!

SYSTEM EVACUATION

NOTE:
Since the outdoor unit has a refrigerant charge, the gas and
liquid line valves must remain closed.

1. Upon completion of leak check, evacuate the refrigerant

lines and indoor coil before opening the gas and liquid
line valves.

2. Attach appropriate hoses from manifold gauge to gas

and liquid line pressure taps.

GAS LINE SERVICE VALVE

5

CAP

1/4 TURN ONLY
COUNTERCLOCKWISE
FOR FULL OPEN 
POSITION

VALVE STEM

GAS LINE CONNECTION

UNIT SIDE
OF VALVE

CAP

BODY

COOLING

CORE

PRESSURE TAP PORT

HEATING

Содержание 4TWR4

Страница 1: ...trical and mechanical experience Any attempt to repair a central air conditioning product may result in personal injury and or property damage The manufacturer or seller cannot be responsible for the...

Страница 2: ...ure 6 The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty 60 feet 7 If outdoor unit is mounted above the air handler maxi mum lift should not exceed sixty 60 fe...

Страница 3: ...hen depressed opens only to the field brazing side when the valve is in the closed position The Gas Line Service Valve is full open with a 1 4 turn See Figure 5 BRAZING REFRIGERANT LINES 1 Remove lowe...

Страница 4: ...feet and or a different size than recommended it will be necessary to adjust system refrigerant charge upon completion of installation See unit Service Facts F ELECTRICAL CONNECTIONS WARNING When ins...

Страница 5: ...switch This will activate the compressor sump heat where used Do not change the Thermostat System Switch until power has been applied for one 1 hour Following this procedure will prevent potential co...

Страница 6: ...1 841 33 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR2060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR4018A 3 1 933...

Страница 7: ...18 BC51D1 3 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg D152637 Rev 1...

Страница 8: ...ressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start DEFROST Unit Won t Initiate De...

Отзывы: