background image

ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES

IMPORTANT — This Document is customer property and is to remain with this unit.  Please return to service information
pack upon completion of work.

Installer’s Guide

assure the efficient operation of the unit. It is recom-
mended that these precautions be taken for units
being installed in areas where snow accumulation and
prolonged below freezing temperatures occur.

1.

Units should be elevated 3 to 12 inches above the pad or
rooftop, depending on local weather. This additional
height will allow better drainage of snow and ice (melted
during defrost cycle) prior to its refreezing. 

This should

prevent a build-up of ice around the unit which occurs
when unit is not elevated. Insure that drain holes in
unit base pan are not obstructed preventing
draining of defrost water.

2. If possible, avoid locations that are likely to accumulate

snow drifts. If not possible, a snow drift barrier should be
installed around the unit to prevent a build-up of snow
on the sides of the unit and should be of sufficient

18-BC51D1-3

Heat Pumps

4TWR4 & 4TWR2

These instructions do not cover all variations in
systems nor provide for every possible contingency to
be met in connection with installation. All phases of
this installation must comply with NATIONAL, STATE
AND LOCAL CODES. 
Should further information be
desired or should particular problems arise which are not
covered sufficiently for the purchaser’s purposes, the matter
should be referred to your installing dealer or local distributor.

A. GENERAL

WARNING

!

This information is intended for use by individuals posses-
sing adequate backgrounds of electrical and mechanical
experience. Any attempt to repair a central air conditioning
product may result in personal injury and or property
damage. The manufacturer or seller cannot be responsible
for the interpretation of this information, nor can it assume
any liability in connection with its use.

The following instructions cover 4TWR4 & 4TWR2 Heat
Pump Units.

NOTE:
These outdoor units are designed to be installed with
approved/matched Trane indoor systems.

WARNING

!

These units use R-410A refrigerant which operates at 50 to
70% higher pressures than R-22. Use only R-410A approved
service equipment. Refrigerant cylinders are painted a “Rose”
color to indicate the type of refrigerant and may contain a
“dip” tube to allow for charging of liquid refrigerant into the
system. All R-410A systems use a POE oil that readily absorbs
moisture from the atmosphere. To limit this “hygroscopic”
action, the system should remain sealed whenever pos-
sible. Never break a vacuum with air and always change the
driers when opening the system for component replacement.

Check for transportation damage after unit is uncrated.
Report promptly, to the carrier, any damage found to the unit.

To determine the electrical power requirements of the unit,
refer to the nameplate of the unit. The electrical power
available must agree with that listed on the nameplate.

The Weathertron

®

 Heat Pump has been designed and

manufactured to withstand and operate in severe winter
conditions. However, there are precautionary steps which
should be taken at the time of installation which will help

1

CAUTION

!

UNIT CONTAINS R-410A REFRIGERANT!

R-410A OPERATING PRESSURE EXCEEDS THE 
LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS 
REQUIRED. FAILURE TO USE PROPER SERVICE 
TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR 
PERSONAL INJURY.

SERVICE

USE ONLY R-410A REFRIGERANT AND

APPROVED POE COMPRESSOR OIL.

5 FT. ABOVE UNIT — UNRESTRICTED

Содержание 4TWR4

Страница 1: ...trical and mechanical experience Any attempt to repair a central air conditioning product may result in personal injury and or property damage The manufacturer or seller cannot be responsible for the...

Страница 2: ...ure 6 The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty 60 feet 7 If outdoor unit is mounted above the air handler maxi mum lift should not exceed sixty 60 fe...

Страница 3: ...hen depressed opens only to the field brazing side when the valve is in the closed position The Gas Line Service Valve is full open with a 1 4 turn See Figure 5 BRAZING REFRIGERANT LINES 1 Remove lowe...

Страница 4: ...feet and or a different size than recommended it will be necessary to adjust system refrigerant charge upon completion of installation See unit Service Facts F ELECTRICAL CONNECTIONS WARNING When ins...

Страница 5: ...switch This will activate the compressor sump heat where used Do not change the Thermostat System Switch until power has been applied for one 1 hour Following this procedure will prevent potential co...

Страница 6: ...1 841 33 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR2060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 4TWR4018A 3 1 933...

Страница 7: ...18 BC51D1 3 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg D152637 Rev 1...

Страница 8: ...ressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start DEFROST Unit Won t Initiate De...

Отзывы: