18-AC74D1-4
21
STEP 8
- Verify typical performance.
Refer to System Pressure Curves in the Service
Facts to verify typical performance.
STEP 6
- Adjust refrigerant level to attain
proper gage pressure.
Add refrigerant
if the Liquid Gage Pressure
is lower than the chart value.
Connect gages to refrigerant bottle
1.
and unit as illustrated.
Purge all hoses.
2.
Open bottle.
3.
Stop adding refrigerant when liquid
4.
line temperature and Liquid Gage
Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant
if the Liquid Gage Pres-
sure is higher than the chart value.
(Example only - see Service Facts)
20 MIN.
STEP 7
- Stabilize the system.
Wait 20 minutes for the system condi-
1.
tion to stabilize between adjustments.
Note: When the Liquid Line Temperature and
Gage Pressure approximately match the chart,
the system is properly charged.
Remove gages.
2.
Replace service port caps to prevent
3.
leaks. Tighten finger tight plus an ad-
ditional 1/6 turn.
PRESSURE CURVES FOR 4TTX5049E1000A
4TXCD010CC3
Cooling @ 1400 CFM
L
IQ
U
ID
PR
ESSU
R
E
(PSI
G
)
OUTDOOR TEMPERATURE (Degree F)
SU
C
T
IO
N
PR
ESSU
R
E
(PSI
G
)
OUTDOOR TEMPERATURE (Degree F)
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
ACTUAL:
(4) LIQUID PRESSURE @ 1400 CFM IS 297 PSIG
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
(5) SUCTION PRESSURE @ 1400 CFM IS 139 PSIG
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
INTERCONNECTING LINES
GAS - 7/8 " O.D.
LIQUID - 3/8 " O.D.
DWG.NO.
4TTX5049E1
110
115
120
125
130
135
140
145
150
155
160
165
170
40
50
60
70
80
90
100
110
120
170
220
270
320
370
420
470
520
40
50
60
70
80
90
100
110
120
(1)
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.