background image

18-AC74D1-4 

 

    21 

STEP 8

 - Verify typical performance.

Refer to System Pressure Curves in the Service 
Facts to verify typical performance.

STEP 6

 - Adjust refrigerant level to attain 

proper gage pressure.

Add refrigerant

 if the Liquid Gage Pressure 

is lower than the chart value.

Connect gages to refrigerant bottle 

1. 

and unit as illustrated.
Purge all hoses.

2. 

Open bottle.

3. 

Stop adding refrigerant when liquid 

4. 

line temperature and Liquid Gage 
Pressure matches the charging chart 
Final Subcooling value.

Recover refrigerant 

if the Liquid Gage Pres-

sure is higher than the chart value.

(Example only - see Service Facts)

20 MIN.

STEP 7 

-  Stabilize the system.

Wait 20 minutes for the system condi-

1. 

tion to stabilize between adjustments.

Note: When the Liquid Line Temperature and 
Gage Pressure approximately match the chart, 
the system is properly charged.

Remove gages.

2. 

Replace service port caps to prevent 

3. 

leaks.  Tighten finger tight plus an ad-
ditional 1/6 turn.

PRESSURE CURVES FOR  4TTX5049E1000A

4TXCD010CC3

Cooling @ 1400 CFM

L

IQ

U

ID

 PR

ESSU

R

(PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

SU

C

T

IO

N

 PR

ESSU

R

(PSI

G

)

OUTDOOR TEMPERATURE (Degree F)

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.

TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE.  MEASURE INDOOR WET BULB 
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES.  ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); 
LOCATE INDOOR WET BULB (2);  FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .

EXAMPLE: (1) OUTDOOR TEMP. 82 F. 
                  (2) INDOOR WET BULB 67 F.  
                  (3) AT INTERSECTION

ACTUAL: 

                  (4) LIQUID PRESSURE @ 1400 CFM IS 297 PSIG

LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART

                  (5) SUCTION PRESSURE @ 1400 CFM IS 139 PSIG

SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

INTERCONNECTING LINES
GAS - 7/8 " O.D.
LIQUID - 3/8 " O.D.

DWG.NO.

4TTX5049E1

110

115

120

125

130

135

140

145

150

155

160

165

170

40

50

60

70

80

90

100

110

120

170

220

270

320

370

420

470

520

40

50

60

70

80

90

100

110

120

(1)

(1)

(3)

(3)

(5)

(4)

(2)

(2)

INDOOR ENTERING 
WET BULB CURVES
TOP TO BOTTOM 
71, 67, 63 AND 59 DEG F.

INDOOR ENTERING 
WET BULB CURVES
TOP TO BOTTOM 
71, 67, 63 AND 59 DEG F.

Содержание 4TTX5018A1000A

Страница 1: ...matched indoor and outdoor systems All of the manufacture s split systems are A H R I rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and outdoor spl...

Страница 2: ...for component replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN Extreme caution should be exercised when opening the Liquid...

Страница 3: ...SS APG006 EN or Refrigerant Piping Software Program 32 3312 03 or latest revi sion Table 2 1 Unit Dimensions and Weight Models H x D x W in Weight lb 4TTX5018A1000A 41 x 34 x 37 227 4TTX5024A1000A 41...

Страница 4: ...12 to Shrubbery Min 12 to Wall Position the outdoor unit a minimum of 12 from any wall or surrounding shrubbery to ensure adequate airflow Outdoor unit location must be far enough away from any struc...

Страница 5: ...ion 4 Setting the Unit 4 1 Pad Installation When installing the unit on a support pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The...

Страница 6: ...ge Line Length 5 4 Refrigerant Line Insulation Important The Vapor Line must always be insulated DO NOT allow the Liquid Line and Vapor Line to come in direct metal to metal contact Vapor Line Liquid...

Страница 7: ...structure due to vibration transmission from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hanger...

Страница 8: ...or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant Lin...

Страница 9: ...avoid heat damage and continue the dry nitrogen purge Braze the refrigerant lines to the service valves Continue the dry nitrogen purge Do not re move the wet rag until all brazing is completed Import...

Страница 10: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Lea...

Страница 11: ...e blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUNTE...

Страница 12: ...System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches t...

Страница 13: ...umper wire from W3 to W2 If electric heat does not have 2nd contactor BH connect a jumper wire from W2 to W1 2 Ylo and BK may not be present on unit Air Handler Hook up Diagram Notes 1 If single stage...

Страница 14: ...Y2 B O BK D Y1 R Neatly bundle all low voltage wires behind the service valve cover as shown Yellow Yellow Blue Blue Yellow Yellow Blue Blue Notes 1 See User Interface setup menu for cooling CFM opti...

Страница 15: ...flow circuits to work properly Internally mounted con 4 densate switch is optional and must be ordered separately If 3rd party condensate 5 overflow switches are installed they should be wired in seri...

Страница 16: ...Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be ne...

Страница 17: ...to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is u...

Страница 18: ...to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient tempera ture is above 55 F STEP 1 Use the refrigerant line total length and lift measurements...

Страница 19: ...60 Use Design Subcooling Add 1 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABLE TOTAL REFRIGERANT LINE LENGTH FT 042 Units 60 Add 5 50 Add 4 40 30 25 20 15 10 0 10 20 25 30 40 60 Add...

Страница 20: ...sure should be ap proximately 327 PSI This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 195...

Страница 21: ...S FOR 4TTX5049E1000A 4TXCD010CC3 Cooling 1400 CFM LIQUID PRESSURE PSIG OUTDOOR TEMPERATURE Degree F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDO...

Страница 22: ...eckout Procedures and Troubleshooting 15 1 Operational And Checkout Procedures Checkout Procedure After installation has been completed it is recommended that the entire system be checked against the...

Страница 23: ...C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N C...

Страница 24: ...www trane com The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustra...

Отзывы: