background image

 

18-AC74D1-4

Section 1. Safety

WARNING

!

This information is intended for use by individuals 
possessing adequate backgrounds of electrical and 
mechanical experience. Any attempt to repair a central 
air conditioning product may result in personal injury 
and/or property damage. The manufacture or seller 
cannot be responsible for the interpretation of this 
information, nor can it assume any liability in connec-
tion with its use.

These units use R-410A refrigerant which operates 
at 50 to 70% higher pressures than R-22. Use only 
R-410A approved service equipment. Refrigerant cyl-
inders are painted a “Rose” color to indicate the type 
of refrigerant and may contain a “dip” tube to allow 
for charging of liquid refrigerant into the system. All 
R-410A systems use a POE oil that readily absorbs 
moisture from the atmosphere. To limit this “hygro-
scopic” action, the system should remain sealed 
whenever possible. If a system has been open to the 
atmosphere for more than 4 hours, the compressor oil 
must be replaced. Never break a vacuum with air and 
always change the driers when opening the system 
for component replacement. For specific handling 
concerns with R-410A and POE oil reference Retrofit 
Bulletins SS-APG006-EN and APP-APG011-EN.

Extreme caution should be exercised when opening 
the Liquid Line Service Valve. Turn counterclockwise 
until the valve stem just touches the rolled edge. No 
torque is required. Failure to follow this warning will 
result in abrupt release of system charge and may 
result in personal injury and /or property damage.

UNIT CONTAINS R-410A REFRIGERANT!
R-410A operating pressures exceed the limit of R-22. 
Proper service equipment is required. Failure to use 
proper service tools may result in equipment damage 
or personal injury.

SERVICE

USE ONLY R-410A REFRIGERANT AND AP-

PROVED POE COMPRESSOR OIL.

WARNING

!

WARNING

!

LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and trouble-
shooting of this product, it may be necessary to work 
with live electrical components. Failure to follow all 
electrical safety precautions when exposed to live 
electrical components could result in death or serious 
injury.

WARNING

!

If using existing refrigerant lines make certain that all 
joints are brazed, not soldered.

CAUTION

!

Scroll compressor dome temperatures may be hot. Do 
not touch the top of compressor; it may cause minor to 
severe burning.

CAUTION

!

WARNING

!

Содержание 4TTX5018A1000A

Страница 1: ...matched indoor and outdoor systems All of the manufacture s split systems are A H R I rated only with TXV EEV indoor systems Some of the benefits of installing approved matched indoor and outdoor spl...

Страница 2: ...for component replacement For specific handling concerns with R 410A and POE oil reference Retrofit Bulletins SS APG006 EN and APP APG011 EN Extreme caution should be exercised when opening the Liquid...

Страница 3: ...SS APG006 EN or Refrigerant Piping Software Program 32 3312 03 or latest revi sion Table 2 1 Unit Dimensions and Weight Models H x D x W in Weight lb 4TTX5018A1000A 41 x 34 x 37 227 4TTX5024A1000A 41...

Страница 4: ...12 to Shrubbery Min 12 to Wall Position the outdoor unit a minimum of 12 from any wall or surrounding shrubbery to ensure adequate airflow Outdoor unit location must be far enough away from any struc...

Страница 5: ...ion 4 Setting the Unit 4 1 Pad Installation When installing the unit on a support pad such as a concrete slab consider the following The pad should be at least 1 larger than the unit on all sides The...

Страница 6: ...ge Line Length 5 4 Refrigerant Line Insulation Important The Vapor Line must always be insulated DO NOT allow the Liquid Line and Vapor Line to come in direct metal to metal contact Vapor Line Liquid...

Страница 7: ...structure due to vibration transmission from the refrigerant lines For Example When the refrigerant lines have to be fastened to floor joists or other framing in a structure use isolation type hanger...

Страница 8: ...or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant Lin...

Страница 9: ...avoid heat damage and continue the dry nitrogen purge Braze the refrigerant lines to the service valves Continue the dry nitrogen purge Do not re move the wet rag until all brazing is completed Import...

Страница 10: ...2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For Lea...

Страница 11: ...e blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUNTE...

Страница 12: ...System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches t...

Страница 13: ...umper wire from W3 to W2 If electric heat does not have 2nd contactor BH connect a jumper wire from W2 to W1 2 Ylo and BK may not be present on unit Air Handler Hook up Diagram Notes 1 If single stage...

Страница 14: ...Y2 B O BK D Y1 R Neatly bundle all low voltage wires behind the service valve cover as shown Yellow Yellow Blue Blue Yellow Yellow Blue Blue Notes 1 See User Interface setup menu for cooling CFM opti...

Страница 15: ...flow circuits to work properly Internally mounted con 4 densate switch is optional and must be ordered separately If 3rd party condensate 5 overflow switches are installed they should be wired in seri...

Страница 16: ...Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be ne...

Страница 17: ...to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is u...

Страница 18: ...to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient tempera ture is above 55 F STEP 1 Use the refrigerant line total length and lift measurements...

Страница 19: ...60 Use Design Subcooling Add 1 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABLE TOTAL REFRIGERANT LINE LENGTH FT 042 Units 60 Add 5 50 Add 4 40 30 25 20 15 10 0 10 20 25 30 40 60 Add...

Страница 20: ...sure should be ap proximately 327 PSI This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 195...

Страница 21: ...S FOR 4TTX5049E1000A 4TXCD010CC3 Cooling 1400 CFM LIQUID PRESSURE PSIG OUTDOOR TEMPERATURE Degree F SUCTION PRESSURE PSIG OUTDOOR TEMPERATURE Degree F COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDO...

Страница 22: ...eckout Procedures and Troubleshooting 15 1 Operational And Checkout Procedures Checkout Procedure After installation has been completed it is recommended that the entire system be checked against the...

Страница 23: ...C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E F U N D E R C H A R G E R E F O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N C...

Страница 24: ...www trane com The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustra...

Отзывы: