18-GD06D1-5

Installer’s Guide

  5.  Do  not  use  reducing  fittings  in  the  condensate 

drain lines. 

  6.  Slope the drain lines downward a minimum of 1/4" 

per foot.

  7.  Insulate the primary drain to prevent sweating.
  8. 

Provide  means  for  drainage  to  prevent  win-
ter freeze-up of condensate line

.

  9.  Do not connect the drain line to a closed drain sys-

tem.

 10.  Use Teflon

®

 tape on the air handler drain line con-

nections! Do Not Use pipe joint compound or PVC/
CPVC cement!

It is always recommended that an auxiliary drain pan 
be installed under a horizontally installed air handler. 
Connect  the  auxiliary  drain  line  to  a  separate  drain 
line (no trap is needed in this line) and terminate ac-
cording to local codes. 

NOTE:

DO  NOT  use  a  torch  or  flame  near  the  plastic  drain 

pan coupling.

NOTE:

DO  NOT  tighten  the  drain  pipe  excessively.  Support 

the  condensate  piping  and  traps  outside  the  unit  to 
prevent strain on the drain coupling.

G.  ELECTRICAL — POWER WIRING

1.   These  Air  Handlers  are  shipped  from  the  factory 

wired for 230 volts. The units may be wired for 208 
volts.  Follow  instructions  on  unit  wiring  diagram 
located on blower housing and in the Service Facts 
document included with the unit.

  2.  The selection of wire and fuse sizes should be made 

according to the Minimum Branch Circuit Ampac-
ity and the Maximum Overcurrent Device listed on 
the unit nameplate.

  3.  Field wiring diagrams for electric heaters and unit   

accessories are shipped with the accessory.

  4.  Wiring must conform to National and Local codes. 

Ground unit per Local codes with good safety pro-
cedures.

If  an  electric  heater  is  not  installed,  the  Knockout 
Plate  provided  in  the  Accessory  Kit  MUST  be  in-
stalled on the air handler and the conduit terminated 
to  it.    The  electrical  connections  are  made  using  the 
two  power  leads  and  ground  wire  connections  which 
are located near the discharge of the blower.

EZT-105

Figure 4

NOTE:
If  air  handler  is  used  with  or    without  a  heater,  the 
7/8" electrical entry hole as well as any other cabinet 
penetrations must be sealed air tight.

H.  CONTROL WIRING

 

1.  Connect  wiring  between  indoor  unit,  outdoor  unit 

and thermostat. The use of color-coded low-voltage 
wires is recommended.

  2.  Field wiring diagrams are provided which show the 

low voltage wiring hookup for a single speed cool-
ing only system (with supplementary heaters) and 
a heat pump system (with supplementary heaters). 
Plug in type electrical connectors are provided for 
use with supplementary heaters.

I

MPORTANT:

When supplementary heaters are installed, inspect to 
insure that all packaging material has been removed.

NOTE:

Direct  drive  motors  have  bearings  which  are  perma-

nently  lubri cated  and  under  normal  use  lubrication 
is not recommended.

WARNING

!

TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL 
SHOCK OR CONTACT WITH MOVING PARTS, LOCK 
UNIT DISCONNECT SWITCH IN OPEN POSITION 
BEFORE SERVICING UNIT.

2" MINIMUM 

2" MINIMUM 

Manufactured traps

Field fabricated trap

2" MIN.

2" MIN.

CAP OR PLUG

Trap must be within 4' 

of air handler condensate

drain connection.

Close as possible

Figure 5

Содержание 4TGB3F18A

Страница 1: ...only Refer to Section B beginning on page 2 for additional information INSPECTION Check carefully for any shipping damage This must be reported to and claims made against the transporta tion company i...

Страница 2: ...s are suitable for instal lation in an attic garage or crawl space with ducted supply and return air This equipment for models 2 4TGB3F18 25 30 36A only has been evaluated in accordance with the Code...

Страница 3: ...NOTE TXV Equipped is Non Bleed and may require a start kit on the outdoor unit NOTE Refrigerant line openings must be sealed along with field wiring E BRAZING TO EVAPORATOR SECTION IMPORTANT Do not un...

Страница 4: ...are shipped with the accessory 4 Wiring must conform to National and Local codes Ground unit per Local codes with good safety pro cedures If an electric heater is not installed the Knockout Plate prov...

Страница 5: ...18 GD06D1 5 5 Installer s Guide 2 4TGB AIR HANDLERS WITH SINGLE STAGE COOLING 1 STAGE HEAT...

Страница 6: ...6 18 GD06D1 5 Installer s Guide 2 4TGB AIR HANDLERS WITH SINGLE STAGE COOLING AND TWO STAGE HEATING 2 4TGB AIR HANDLERS WITH SINGLE SPEED HEAT PUMP From Dwg B801081 Rev 2...

Страница 7: ...18 GD06D1 5 7 Installer s Guide OUTLINE DRAWING FOR 2 4TGB3F18 25 30 36A From Drawing D810094P01 Rev 3...

Страница 8: ...ts per unit nameplate 8 Check filters for proper size Inform owner of proper procedure for removal and reinstallation 9 Energize the system and carefully observe its opera tion make any necessary adju...