Trane 2TWZ9 Скачать руководство пользователя страница 4

4

18-BC53D1-2

Installer’s Guide

12. The gas valve is now open for refrigerant flow. Replace

valve stem cap to prevent leaks. Again, these caps
MUST BE REPLACED to prevent leaks. Replace valve
stem and pressure tap cap finger tight, then tighten an
additional 1/6 turn. See Figure 3.

If refrigerant lines are longer than 15 feet and/or a different
size than recommended, it will be necessary to adjust system
refrigerant charge upon completion of installation. See unit
Service Facts.

E. ELECTRICAL CONNECTIONS

WARNING

!

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility
of electric shock.

1. Power wiring and grounding of equipment must comply

with local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.

4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration

transmission may create a noise problem within the
structure.

6. The use of color coded low voltage wire is recommended

to simplify connections between the outdoor unit, the
thermostat and the indoor unit.

Table 1 — NEC Class II Control Wiring

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

7. Table 1 defines maximum total length of low voltage

wiring from outdoor unit, to indoor unit, and to
thermostat.

8. Mount the indoor thermostat in accordance with instruc-

tion included with the thermostat. Wire per appropriate
hook-up diagram (included in these instructions).

F. DEFROST CONTROL

The demand defrost control measures heat pump outdoor
ambient temperature with a sensor located outside the
outdoor coil. A second sensor located on the outdoor coil is
used to measure the coil temperature. The difference between
the ambient and the colder coil temperature is the difference
or delta-T measurement. This delta-T measurement is
representative of the operating state and relative capacity of
the heat pump system. By measuring the change in delta-T,
we can determine the need for defrost. The coil sensor also
serves to sense outdoor coil temperature for termination of
the defrost cycle.

FAULT IDENTIFICATION

A fault condition is indicated by the flashing light on the
defrost control inside the heat pump control box.

In normal operation, the defrost control light will flash once
each second. If the light is flashing more than once per
second or not at all, refer to the service manual for that unit.

PIN IDENTIFICATION (See Figure 5.)

1. NORMAL (This wire as shipped is unattached to any

pin. In this position, the defrost control is in normal
operation. However, after checking for proper operation,
the wire should be returned to the normal pin.)

2. TST  =  Test (Red wire in this position speeds up all

defrost board timings.)

3. FRC DFT  =  Forced Defrost (Touch the red wire to this

pin for ten [10] seconds to initiate a forced defrost.
Remove the short after defrost initiates.)

  4.  FRC DFT  =  Forced Fault (Touch the red wire to this

pin for ten [10] seconds to demonstrate a fault condition.)

DEFROST CONTROL CHECKOUT

Normal operation requires:

a. LED on board flashing 1 time/second.

b. 24V AC between R & B.

c. 24V AC between Y & B with unit operating.

d. Defrost initiation when test wire is moved to “Forced

Defrost” pin, then return to “Normal Pin”.

If a defrost control problem is suspected, refer to the service
information in control box.

WARNING

!

Do NOT connect 24 VAC to T1 (ODS-A) terminal. ODS-A
thermistor WILL BE BLOWN.

G. COMPRESSOR START UP

After all electrical wiring is complete, SET THE THERMO-
STAT SYSTEM SWITCH IN THE OFF POSITION SO
COMPRESSOR WILL NOT RUN, and apply power by
closing the system main disconnect switch. This will activate
the compressor sump heat (where used). Do not change the
Thermostat System Switch until power has been applied for
one (1) hour. Following this procedure will prevent potential
compressor overload trip at the initial start-up.

5

TEST WIRE

RED TEST WIRE

FRC FL

T

FRC DFT

TST

NORM

COIL

AMBIENT

Содержание 2TWZ9

Страница 1: ...istributor A GENERAL The following instructions cover 2TWZ9 Heat Pump Units NOTE These outdoor units must be used with indoor units equipped with Thermostatic Expansion Valve only Check for transporta...

Страница 2: ...is the same Final refrigerant charge adjustment is necessary Use the Charging Charts in the outdoor unit Service Facts 1 Determine the most practical way to run the lines 2 Consider types of bends to...

Страница 3: ...pressure taps NOTE Unnecessary switching of hoses can be avoided and com plete evacuation of all lines leading to sealed system can be accomplished with manifold center hose and connecting branch hos...

Страница 4: ...rement is representative of the operating state and relative capacity of the heat pump system By measuring the change in delta T we can determine the need for defrost The coil sensor also serves to se...

Страница 5: ...f this installation are the unit Operational and Checkout Procedures which are found in this instruction on page 8 To obtain proper performance all units must be operated and charge adjustments made i...

Страница 6: ...46 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 933 36 3 4 2TWZ9036B 4 1267 49 7 8 946 37 1 4 870 34 1 4 7 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 933 36 3 4 2TWZ9048B 4 1267 49 7 8 946...

Страница 7: ...18 BC53D1 2 7 Installer s Guide MOUNTING HOLE LOCATION NOTE ALL DIMENSIONS ARE IN MM INCHES NOTE For model base size see table on page 6 From Dwg 21D152637 Rev 1...

Страница 8: ...Inadequate or No Cooling Htg ELECTRICAL Compressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blow...

Отзывы: