18-BC51D2-3

Installer’s Guide

3. Attach center hose of manifold gauges to vacuum pump.

4. Evacuate until the micron gauge reads no higher than

350 microns.

5. Close off valve to vacuum pump and observe the micron

gauge. If gauge pressure rises above 500 microns in one
(1) minute, then evacuation is incomplete or system has
a leak.

6. If vacuum gauge does not rise above 500 microns in one

(1) minute, the evacuation should be complete.

7. With vacuum pump and micron gauge blanked off, open

valve on HCFC-22 cylinder and charge refrigerant lines
and indoor coil with vapor to tank pressure of HCFC-22
supply.

NOTE:
DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.

8. Close valve on HCFC-22 supply cylinder. Close valves on

manifold gauge set and remove refrigerant charging
hoses from liquid and gas pressure tap ports.

NOTE:
A 3/16" Allen wrench is required to open liquid line service
valve. A 1/4" Open End or Adjustable wrench is required to
open gas line valve. A 3/4" Open End wrench is required to
take off the valve stem cap.

9. The liquid line shut-off valve can now be opened.

Remove shut-off valve cap. Fully insert hex wrench into
the stem and backout counterclockwise until valve stem
just touches rolled edge (approximately five [5] turns)
observing WARNING statement on page 3. See Figure 4.

10. Replace liquid service pressure tap port cap and valve

stem cap. These caps MUST BE REPLACED to
prevent leaks. Replace valve stem and pressure tap cap
finger tight, then tighten an additional 1/6 turn.

11. The gas valve can now be opened. For a ball type gas

valve, open the gas valve by removing the shut-off valve
cap and turning the valve stem 1/4 turn counterclock-
wise, using 1/4" Open End or Adjustable wrench. See
Figure 5. For brass gas line service valve opening, follow
9 and 10 above. See Figure 6.

12. The gas valve is now open for refrigerant flow. Replace

valve stem cap to prevent leaks. Again, these caps
MUST BE REPLACED to prevent leaks. Replace valve
stem and pressure tap cap finger tight, then tighten an
additional 1/6 turn. See Figure 4.

If refrigerant lines are longer than 15 feet and/or a different
size than recommended, it will be necessary to adjust system
refrigerant charge upon completion of installation. See unit
Service Facts.

F. ELECTRICAL CONNECTIONS

WARNING

!

When installing or servicing this equipment, ALWAYS
exercise basic safety precautions to avoid the possibility
of electric shock.

1. Power wiring and grounding of equipment must comply

with local codes.

2. Power supply must agree with equipment nameplate.

3. Install a separate disconnect switch at the outdoor unit.

4. Ground the outdoor unit per local code requirements.

5. Provide flexible electrical conduit whenever vibration

transmission may create a noise problem within the
structure.

6. The use of color coded low voltage wire is recommended

to simplify connections between the outdoor unit, the
thermostat and the indoor unit.

Table 1 --- NEC Class II Control Wiring

24 VOLTS

WIRE SIZE

MAX. WIRE LENGTH

18 AWG

150 FT

16 AWG

225 FT.

14 AWG

300 FT.

7. Table 1 defines maximum total length of low voltage

wiring from outdoor unit, to indoor unit, and to
thermostat.

8. Mount the indoor thermostat in accordance with instruc-

tion included with the thermostat. Wire per appropriate
hook-up diagram (included in these instructions).

G. DEFROST CONTROL

The demand defrost control measures heat pump outdoor
ambient temperature with a sensor located outside the
outdoor coil. A second sensor located on the outdoor coil is
used to measure the coil temperature. The difference be-
tween the ambient and the colder coil temperature is the
difference or delta-T measurement. This delta-T measure-
ment is representative of the operating state and relative
capacity of the heat pump system. By measuring the change
in delta-T, we can determine the need for defrost. The coil
sensor also serves to sense outdoor coil temperature for
termination of the defrost cycle.

FAULT IDENTIFICATION

A fault condition is indicated by the flashing light on the
defrost control inside the heat pump control box.

In normal operation, the defrost control light will flash once
each second. If the light is flashing more than once per
second or not at all, refer to the service manual for that unit.

PIN IDENTIFICATION (See Figure 7.)

1. TEST_COMMON (Shorting any of the other pins to this

pin causes the function of the other pin to be executed.
Leaving this pin open results in the normal mode of
operation.)

2. TST  =  Test (Shorting TEST_COMMON to this pin

speeds up all defrost board timings.)

PIN IDENTIFICATION

7

FRC_DFT

TEST_COMMON

TST

Содержание 2TWR1

Страница 1: ...red sufficiently for the purchaser s purposes the matter should be referred to your installing dealer or local distributor A GENERAL The following instructions cover 2TWR1 and 2TWR2 Heat Pump Units NO...

Страница 2: ...are brazed not soldered Condensing units have provisions for braze connections Pressure taps are provided on the service valves of outdoor unit for compressor suction and liquid pressures The indoor...

Страница 3: ...zing It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body NOTE Use care to make sure that no moisture enters pressure tap port while wet rag i...

Страница 4: ...e upon completion of installation See unit Service Facts F ELECTRICAL CONNECTIONS WARNING When installing or servicing this equipment ALWAYS exercise basic safety precautions to avoid the possibility...

Страница 5: ...r sump heat where used Do not change the Thermostat System Switch until power has been applied for one 1 hour Following this procedure will prevent potential compressor overload trip at the initial st...

Страница 6: ...4 829 32 5 8 756 29 3 4 1 1 8 3 8 137 5 3 8 86 3 3 8 210 8 1 4 79 3 1 8 508 20 2TWR1060A 4 1 841 33 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2TWR2018A 2 2 651 25 5...

Страница 7: ...18 BC51D2 3 7 Installer s Guide MOUNTING HOLE LOCATION Note All dimensions are in MM Inches NOTE For model base size see table on page 6 From Dwg 21D152637 Rev 1...

Страница 8: ...ompressor O D Fan Won t Start Compressor Will Not Start But O D Fan Runs O D Fan Won t Start Compressor Hums But Won t Start Compressor Cycles on IOL I D Blower Won t Start DEFROST Unit Won t Initiate...

Отзывы: