Trane 2TTB3 Series Скачать руководство пользователя страница 6

6

18-BC56D1-5

Installer’s Guide

SUBCOOLING CHARGING IN COOLING ABOVE 55°F OD AMBIENT

The manufacturer has always recommended installing
approved matched indoor and outdoor systems.

All 13 SEER split systems are AHRI rated with only TXV
indoor systems.

The benefits of installing approved indoor and outdoor split
systems are maximum efficiency, optimum performance and
the best overall system reliability.

The following charging methods are therefore prescribed for
systems with indoor TXVs.

1. Subcooling (in the cooling mode) is the only recommended

method of charging above 55°F ambient temperatures.

2. For best results - the indoor temperature should be kept

between 70°F to 80°F. Add system heat if needed.

3. At start-up, or whenever charge is removed or added, the

system must be operated for a minimum 20 minutes to
stabilize before accurate measurements can be made.

4. Measure Liquid Line Temperature and Refrigerant

Pressure at service valves.

5. Determine total refrigerant line length, and height (lift)

if indoor section is above the condenser.

6. Determine the Design Subcool Charging Temperature

from the unit nameplate.

7. Locate this value in the appropriate column of the

Subcooling Charging Table. Locate your liquid line
temperature in the left column of the table, and the
intersecting liquid line pressure under your nameplate
subcool value column. Add refrigerant to raise the pres-
sure to match the table, or remove refrigerant to lower
the pressure. Again, wait 20 minutes for the system
conditions to stabilize before adjusting charge again.

8. When system is correctly charged, you can refer to

System Pressure Curves (in Service Facts) to verify
typical performance.

Installer’s Guide

R-22 SUBCOOLING CHARGING TABLE

LIQUID

TEMP.

(°F)

DESIGN SUBCOOLING VALUES (°F)

8

10

12

14

LIQUID LINE PRESSURE (psi)

45

89

93

96

100

50

98

102

105

109

55

107

111

115

119

60

117

121

126

130

65

128

132

137

141

70

139

144

148

153

75

151

156

161

166

80

163

168

174

179

85

176

182

187

193

90

190

196

202

208

95

205

211

217

223

100

220

226

233

239

105

236

243

249

256

110

253

260

267

274

115

271

278

285

293

120

289

297

305

313

125

309

317

325

333

SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE

60
50
40
30
25

Add 5 psig to Subcool Charging Table Pressure

20
15

Use Design Subcool Value from Table

10

0

Subtract 5 psig from S.C. Table Pressure

10

20

25

30

40

60

80

TOTAL REFRIGERANT LINE LENGTH  (FEET)

REFRIGERANT

LINE LIFT (FEET)

Содержание 2TTB3 Series

Страница 1: ...d manufactured to withstand and operate in severe winter conditions However there are precautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur 1 Units should be elevated 3...

Страница 2: ...f rated line set C SERVICE VALVE OPERATION BRASS LIQUID AND GAS LINE SERVICE VALVES The Brass Liquid and Gas Line Service Valves are factory shipped in the seated position to hold factory nitrogen charge The pressure tap service port when depressed opens only to the field brazing side of the valve when the valve is in the seated position The liquid line valve is not a back seating valve see WARNIN...

Страница 3: ...500 microns in one 1 minute then evacuation is incomplete or system has a leak 7 If vacuum gauge does not rise above 500 microns in one 1 minute the evacuation should be complete 8 With vacuum pump and micron gauge blanked off weigh in HCFC 22 refrigerant based on the outdoor unit data plate and refrigerant line set length adjust ments noted on page 1 of the Service Facts 9 Close valve on HCFC 22 ...

Страница 4: ...ost initiates DEFROST CONTROL CHECKOUT Normal operation requires a LED on board flashing 1 time second b 24V AC between R B c 24V AC between Y B with unit operating d Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin If a defrost control problem is suspected refer to the service information in control box F COMPRESSOR START UP After all electrical wiring is complete SET THE THERMO ...

Страница 5: ... O R M E R C O N T A C T O R C O I L L O W V O L T A G E F U S E S T U C K C O M P R E S S O R I N E F F I C I E N T C O M P R E S S O R R E F R I G E R A N T U N D E R C H A R G E R E F R I G E R A N T O V E R C H A R G E E X C E S S I V E E V A P L O A D N O N C O N D E N S A B L E S R E S T R I C T E D O D A I R F L O W O D A I R R E C I R C U L A T I O N T X V S T U C K O P E N S U P E R H E A...

Страница 6: ...it nameplate 7 Locate this value in the appropriate column of the Subcooling Charging Table Locate your liquid line temperature in the left column of the table and the intersecting liquid line pressure under your nameplate subcool value column Add refrigerant to raise the pres sure to match the table or remove refrigerant to lower the pressure Again wait 20 minutes for the system conditions to sta...

Страница 7: ...8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 2TWB3060A 4 1 1045 41 1 8 946 37 1 4 870 34 1 4 1 1 8 3 8 152 6 98 3 7 8 219 8 5 8 86 3 3 8 508 20 MODELS BASE FIG A B C D E F G H J K 2TTB3018A 2 2 651 25 5 8 724 28 1 2 651 25 5 8 5 8 1 4 127 5 57 2 1 4 181 7 1 8 44 1 3 4 457 18 2TTB3024A 2 2 832 32 3 4 724 28 1 2 651 25 5 8 3 4 5 16 137 5 3 8 65 2 5 8 210 8 1 4 57 2 1 4 457 18 2TTB3030A 3 2 832 32 3 4 ...

Страница 8: ...nry been sealed If mortar is used prevent mortar from coming into direct contact with copper tubing 5 Verify tightness of all electrical connects 6 Observe outdoor fan during on cycle for clearance and smooth operation 7 Indoor coil drain line drains freely Pour water into drain pan 8 Supply registers and return grilles open and unobstructed 9 Return air filter installed 10 Thermostat thermometer ...

Отзывы: