BAS-SVP046A-EN
9
Figure 5. LonTalk protocol configuration
1. Verify the LonTalk adapter connection status is C
Co
on
nn
ne
ecctte
ed
d. If the adapter connection status is
another state, verify the LonTalk adapter is connected to a Symbio 800 USB port.
2. Verify the Link Status is O
On
nlliin
ne
e. If the Link Status is set to a different state, LonTalk network
management software such as Trane’s Rover software is needed to set the Link status to
Online.
3. The Service Pin button will send a service pin message to the LonTalk network. A service pin
will broadcast the Neuron ID to the LonTalk network so a LonTalk network management tool
can find a device and set its Domain, Subnet, Node address.
LonTalk communication wire is connected to the LonTalk adapter. LonTalk does not require wire
polarity but it is recommended that wire polarity be observed. Refer to the LonTalk standard for
detailed information on LonTalk wiring.
All LonTalk devices must have a unique DSN address and must have the same Domain value.
The Symbio 800 LonTalk adapter ships on the zero-length domain so it can be easily discovered
by LonTalk network managers and tools.