BAS-SVP046A-EN
13
ACRB 350–500 Tons Data Points
Table 4. ACRB 350–500 tons configuration parameters
nv Index
Configuration
Variable Name
Variable Type
Variable description
Point Name
2
nciChillerType
UCPT_chiller_type
Chiller Information
Model Information
Enum list - See table in UNVT-UCPT.doc
Model Information
Unit Capacity
Capacity of Unit (in watts)
Chiller Design Capacity
Cooling Type
0 = Water Cooled
1 = Air Cooled
2 to 254 = Unused
Cooling Type
Number of Circuits
Number of Circuits on Unit
Number Of Circuits
Number of Compressors – Crt 1
Number of Compressors on Circuit 1
Number Of Compressors,
Circuit 1
Number of Compressors – Crt 2
Number of Compressors on Circuit 2
Number Of Compressors,
Circuit 2
5
nciMfgLocation
UCPT_manufacturing_location
Chiller Manufacturing Location
Manufacture Location
6
nciNoiseRdcnReq
SNVT_switch
Default for Noise Reduction Auto/On
Request
Noise Reduction request
7
nciRefrigerant
UCPT_refrig_type
Chiller Refrigerant Type
Refrigerant Type
8
nciCapacityLim
SCPTCapacityLimit
Capacity Limit
Demand Limit Setpoint
9
nciChillerEnable
SCPTChillerEnable
Default Value for nviChillerEnable
Chiller Enable
10
nciCoolsetpt
SCPTCoolSetpoint
Default Value for nviCoolSetpt
Chiller water Setpoint
11
nciDefaults
SCPTDefaultBehavior
Determines which set of values will be
used on power up and communications
failure, stated default values or a list of
manufacturer specified values
Default Values
12
nciDevMajVer
SCPTdevMajVer
The major version number for the device
Software Major Version
13
nciDevMinVer
SCPTdevMinVer
The minor version number for the device
Software Minor Version
15
nciLocation
SCPTlocation
Location Label
Location Label
16
nciMinOutTm
SCPTminSendTime
Minimum Send Time
Minimum Send Time
17
nciMode
SCPTHVACmode
Default Value for nviMode
Chiller Mode
18
nciPwrup
SCPTpwrUpDelay
Power Up Delay
Power Up Delay
19
nciRcvHrtBt
SCPTmaxRcvTime
Receive Heartbeat Time
Receive Heartbeat
20
nciSndHrtBt
SCPTmaxSendTime
Send Heartbeat Time (nciMAXSendTime)
Send Heartbeat
21
nciBuildNum
U16
Device Build Number
Manufacturer-defined
22
nciCRC
UCPT_crc
CRC calculation result
Manufacturer-defined
23
nciDeviceConfig
U16
Device Configuration Choices
Manufacturer-defined
Table 5. ACRB 350–500 tons network variable inputs
Profile Index
Network Variable
Name
Variable Type
Variable
description
Recv HrtBt
Point Name
24
nviChillerEnable
SNVT_switch
Request Start/Stop
Chiller
♥
BAS Chiller Auto Stop
Command
25
nviCoolSetpt
SNVT_temp_p
Desired Temp of Lvg
Chilled Wtr
♥
BAS Chilled Water Setpoint
26
nviCapacityLim
SNVT_lev_percent
Capacity Limit of
Chiller
♥
BAS Demand Limit Setpoint
28
nviMode
SNVT_Hvac_mode
Chiller Modes
♥
BAS Chiller Mode Command
32
nviNoiseRdcnReq
SNVT_switch (2-state)
Noise Reduction Auto/
On Request
♥
Noise Reduction Request BAS
35
nviRequest
SNVT_obj_request
Status Request
Status Request Input
36
nviTraneVar2
UNVT_c5c
Comm5 Status
Manufacturer-defined