Figure 50.
Install return-air duct panel
Duct Panel
with 1 1/2"-Flange
A
Unit Side
Unit Side
Unit T
op
B
1"
3 3/4"
Unit Top
Install the return-
air duct panel to
the return-air
opening with the
six screws
provided for the
filter rack
assembly.
Table 38. Opening size and part number EXH
EXH (60 Hz)
A (in.)
B (in.)
Duct Collar Part
Number
006-015
17-1/2
13
447411330100
018-024
20-1/2
16
447456280100
030-036
22-1/2
17
447411350100
042-070
26-1/2
19
447411360100
Installation
56
WSHP-SVX01W-EN
Ducted Filter Rack (GEH 0.5 to 5 tons and
EXH 0.5 to 6 ton only)
When it is necessary
to have filter access at
the unit in a ducted
return, a ducted filter
rack is available. This
option allows access
to the filter at the unit.
Vertical unit filter
racks are available in
right or left access
configurations.
Horizontal units are
available in top,
bottom or side access
configurations.
A
B
C
Table 39. Ducted filter opening size
Unit Size
A (in.)
B (in.)
C (in.)
GEH 006-015
21.1
15.4
5.4
GEH 018-030
24.5
18.4
5.6
GEH 035-042
26.4
19.4
5.5
GEH 048-060
30.7
21.4
5.5
GEV 006-015
20.7
17.1
5.5
GEV 018-030
20.7
23.1
5.5
GEV 036-042
25.7
22.4
4.3
GEV 048-060
30.7
26.6
5.5
EXH 006-015
21.1
15.4
5.4
EXH 018-030
24.5
18.4
5.6
EXH 036-042
26.4
19.4
5.5
EXH 048-070
30.7
21.4
5.5
EXV 006-015
20.7
17.1
5.5
EXV 018-030
20.7
23.1
5.5
EXV 036-042
25.7
22.4
4.3
EXV 048-070
30.7
26.6
5.5
Dual Filtration (GEH 0.5 to 5 ton and EXH
0.5 to 6 ton)
Note:
The dual-filtration design is typically used in a free-
return application.
The horizontal, GEH and EXH model, allows the installer
flexibility in design applications such as a dual filtration
option. With the dual filtration design, the unit will contain
a lower static which translates into a decrease in filter
maintenance. For installation of a dual filtration accessory
for the GEH and EXH model, verify that an extra set of
return-air filter racks and filter have been ordered from the
factory. This accessory will be shipped separate from the
unit, and should be located in a separate box than the unit.
1. Remove the return-air side panel from the GEH and
EXH unit. This panel is held in place by screws.
2. Install the top/bottom filter rack at the new opening.
The adjustable filter rack is held in place with four
screws that once held the panel.
3. Install the 1”or 2” filter.
Sound Attenuation Pad
For sound-sensitive installations, a vibration pad (field
provided) should be placed beneath the horizontal or
vertical equipment. For the horizontal unit, the pad should
be approximately twice the size of the unit foot print. For
the vertical unit, the pad should be 0.5 in. thick, and equal
to the overall unit foot print.
Hanging the Horizontal Unit
WARNING
Risk of Unit Dropping!
Failure to follow instruction below could result in death
or serious injury. To prevent modules/subassemblies
from dropping, ALWAYS place, assemble, and suspend
them one at a time.
To hang the horizontal configuration (see
1. Install the hanging isolators (located in the return-air
section of the unit) into the four hanging brackets.
Table 39. Ducted filter opening size (continued)
Unit Size
A (in.)
B (in.)
C (in.)
Содержание Axiom EXH Series
Страница 123: ......